The inductor carries a steady current of 0.5 A. At t = 0 the switch closes the loop through R and the source is removed, so the inductor current decays through R. How long does it take for the current to fall to 0.125 A? Find t.
i(0) = 0.5 AR = 20 ΩL = 22 mH
t = ms
8.RC & RL transientsHard
Just before the switch closes at t = 0, the capacitor holds 30 V with the polarity shown. Find the capacitor voltage vC at t = 250 ms.
Vs = 6 VR = 3.3 kΩC = 33 µFvC(0) = 30 Vt = 250 ms
vC = V
9.AC impedance & phasorsMedium
A series RLC circuit is connected to a 230 V (rms), 200 Hz supply. Find the power factor cos φ of the circuit.
V = 230 V (rms)f = 200 HzR = 30 ΩL = 200 mHC = 22 µF
cos φ =
10.AC impedance & phasorsHard
A series RLC circuit is connected to a 10 V (rms), 100 Hz supply. Find the rms voltage VC across the capacitor.
V = 10 V (rms)f = 100 HzR = 100 ΩL = 150 mHC = 22 µF
VC = V
11.AC power & power factorMedium
A single-phase motor takes 19 kW at a power factor of 0.85 lagging from a 230 V supply. Find the reactive power Q it draws.
P = 19 kWpf = 0.85V = 230 V
Q = kvar
12.AC power & power factorHard
A single-phase load takes 5 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
P = 5 kWpf1 = 0.65pf2 = 0.92V = 230 Vf = 60 Hz
C = µF
13.Three-phase powerMedium
A three-phase induction motor delivers 18.5 kW of mechanical output power at full load. At this load its efficiency is 88% and its power factor is 0.8 lagging. The supply has a line-to-line voltage of 415 V. Find the line current IL.
Pout = 18.5 kWη = 88%cos φ = 0.8VL = 415 V
IL = A
14.Three-phase powerHard
A balanced three-phase load takes 150 kW at a power factor of 0.65 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 150 kWpf1 = 0.65pf2 = 0.9VL = 415 Vf = 50 Hz
Cph = µF
15.TransformersMedium
A single-phase 500 kVA, 4800/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
S = 500 kVAV1 = 4800 VV2 = 240 V
IHV = A
16.TransformersHard
A single-phase 50 kVA transformer has a core loss of 400 W and a copper loss of 1600 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R3 + R4 = 6 + 5 = 11 Ω
R2 ∥ 11 = 4·11/(4+11) = 2.933 Ω
Req = R1 + 2.933 = 12 + 2.933 = 14.93 Ω
Answer
Req = 14.93 Ω
2.Series & parallel resistors
Answer: Req = 19.86 Ω
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R5 + R6 = 20 + 15 = 35 Ω
R4 ∥ 35 = 2.763 Ω
R3 + 2.763 = 22.76 Ω
R2 ∥ 22.76 = 7.858 Ω
Req = R1 + 7.858 = 12 + 7.858 = 19.86 Ω
Answer
Req = 19.86 Ω
3.Nodal analysis
Answer: PIs = 90.77 W
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R2 + (VA − V1)/R1 + (VA − VB)/R3 = 0
VA/2 + (VA − 30)/4 + (VA − VB)/6 = 0
0.9167·VA − 0.1667·VB = 7.5
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
The source pushes Iₛ up into node B, from ground (0 V) to VB. A source whose current leaves its + end delivers P = V·I.
PIs = VB·Is = 22.69·4 = 90.77 W
Answer
PIs = 90.77 W
4.Nodal analysis
Answer: Is = 7.215 A
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
KCL at node A
VA is known, so this equation gives VB.
(VA − V1)/R1 + VA/R2 + (VA − VB)/R3 = 0
(11 − 15)/12 + 11/8 = (VB − 11)/25
1.042 = (VB − 11)/25 → VB = 37.04 V
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
Is = (VB − VA)/R3 + VB/R4 = (37.04 − 11)/25 + 37.04/6 = 7.215 A
Answer
Is = 7.215 A
5.Thévenin & Norton
Answer: Vth = 1.364 V
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 20·2/(20+2) = 1.818 Ω
Rth = (R1 ∥ R2) + R3 = 1.818 + 20 = 21.82 Ω
Find Vth, the open-circuit voltage
With a–b open, no current flows through R₃, so there is no drop across it and V_b = V_A. R₁ and R₂ form a voltage divider.
Vth = V1·R2/(R1+R2) = 15·2/(20+2) = 1.364 V
6.Thévenin & Norton
Answer: IL = 2.69 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 10·2/(10+2) = 1.667 Ω
Rth = (R1 ∥ R2) + R3 = 1.667 + 25 = 26.67 Ω
Find Vth, the open-circuit voltage
With a–b open, the only path for Iₛ is through R₃ into node A. Find V_A by superposition of V₁ and Iₛ, then add the drop across R₃.
VA = V1·R2/(R1+R2) + Is·(R1∥R2) = 2.5 + 3·1.667 = 7.5 V
Vth = VB = VA + Is·R3 = 7.5 + 3·25 = 82.5 V
Connect the load to the Thévenin equivalent
The Thévenin source and R_th in series behave exactly like the original circuit at a–b, so the load sees a simple series loop.
IL = Vth/(Rth + RL) = 82.5/(26.67 + 4) = 2.69 A
7.RC & RL transients
Answer: t = 1.525 ms
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Time constant
τ = L/R = 22 mH / 20 Ω = 1.1 ms
Solve for the time
0.125 = 0.5·e−t/τ → t = τ·ln(0.5/0.125)
t = 1.1·ln(4) = 1.525 ms
Answer
t = 1.525 ms
8.RC & RL transients
Answer: vC = 8.417 V
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Initial value, final value, time constant
The capacitor voltage cannot jump, so it starts at its stored value and heads for the source voltage.
vC(0) = 30 V, vC(∞) = Vs = 6 V
τ = R·C = 3.3 kΩ · 33 µF = 108.9 ms
vC(t) = 6 + (30 − 6)·e−t/τ
Voltage at the given time
vC(250) = 6 + (24)·e−250/108.9 = 8.417 V
Answer
vC = 8.417 V
9.AC impedance & phasors
Answer: cos φ = 0.1381
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
XL = 251.3 Ω, XC = 36.17 Ω
Impedance
|Z| = √(30² + (215.2)²) = 217.2 Ω
Power factor
cos φ = R/|Z| = 30/217.2 = 0.1381
The circuit is inductive, so the power factor is lagging.
Answer
cos φ = 0.1381
10.AC impedance & phasors
Answer: VC = 7.067 V
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·100 = 628.3 rad/s
XL = ωL = 628.3·0.15 = 94.25 Ω
XC = 1/(ωC) = 1/(628.3·22·10⁻⁶) = 72.34 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 10/102.4 = 0.09768 A
Voltage across the capacitor
VC = I·XC = 0.09768·72.34 = 7.067 V
Answer
VC = 7.067 V
11.AC power & power factor
Answer: Q = 11.78 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Angle
φ = arccos(0.85) = 31.79°, tan φ = 0.6197
Reactive power
Q = P·tan φ = 19·0.6197 = 11.78 kvar
Answer
Q = 11.78 kvar
12.AC power & power factor
Answer: C = 186.3 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 5·tan(49.46°) = 5.846 kvar
Q2 = P·tan φ2 = 5·tan(23.07°) = 2.13 kvar
QC = Q1 − Q2 = 3.716 kvar
Capacitance
A capacitor across the supply delivers Q = V²·ωC.
C = QC/(2πf·V²) = 3716/(2π·60·230²) = 186.3 µF
Answer
C = 186.3 µF
13.Three-phase power
Answer: IL = 36.56 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 18.5/0.88 = 21.02 kW
Line current
IL = Pin/(√3·VL·cos φ) = 21023/(√3·415·0.8) = 36.56 A
Answer
IL = 36.56 A
14.Three-phase power
Answer: Cph = 632.8 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 150·tan(acos 0.65) = 150·1.169 = 175.4 kvar
Q2 = 150·tan(acos 0.9) = 150·0.4843 = 72.65 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 102.7 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
IHV = S/V = 500000/4800 = 104.2 A
Answer
IHV = 104.2 A
16.Transformers
Answer: Ploss = 800 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.