Find the Thévenin voltage Vth seen from terminals a–b.
V1 = 24 VR1 = 3 ΩR2 = 15 ΩR3 = 2 Ω
Vth = V
6.Thévenin & NortonHard
Find the Norton current IN: the current that flows from a to b if the terminals are shorted.
V1 = 36 VIs = 4 AR1 = 3 ΩR2 = 3 ΩR3 = 5 Ω
IN = A
7.RC & RL transientsMedium
The inductor carries a steady current of 2 A. At t = 0 the switch closes the loop through R and the source is removed, so the inductor current decays through R. Find the voltage vR across R at t = 1 ms.
i(0) = 2 AR = 33 ΩL = 33 mHt = 1 ms
vR = V
8.RC & RL transientsHard
A timer starts charging an uncharged capacitor through a resistor from a 12 V supply at t = 0. It must trigger when the capacitor voltage reaches 6 V, exactly 200 ms after the start. With R = 47 kΩ, find the capacitance C needed.
Vs = 12 VVth = 6 VT = 200 msR = 47 kΩ
C = µF
9.AC impedance & phasorsMedium
A series RLC circuit is connected to a 120 V (rms), 1000 Hz supply. Find the phase angle φ of the impedance, in degrees (positive when the current lags the voltage).
V = 120 V (rms)f = 1000 HzR = 15 ΩL = 20 mHC = 100 µF
φ = °
10.AC impedance & phasorsHard
A series RLC circuit is connected to a 10 V (rms), 100 Hz supply. Find the rms voltage VC across the capacitor.
V = 10 V (rms)f = 100 HzR = 30 ΩL = 200 mHC = 22 µF
VC = V
11.AC power & power factorMedium
A single-phase motor takes 40 kW at a power factor of 0.9 lagging from a 400 V supply. Find the line current I.
P = 40 kWpf = 0.9V = 400 V
I = A
12.AC power & power factorHard
A single-phase load takes 35 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
P = 35 kWpf1 = 0.6pf2 = 0.98V = 400 Vf = 60 Hz
C = µF
13.Three-phase powerMedium
A balanced Δ-connected load with an impedance of 5 + j12 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 400 V. Find the total real power P absorbed by the load in kW.
VL = 400 VZ = 5 + j12 Ω per phase
P = kW
14.Three-phase powerHard
A balanced three-phase load takes 200 kW at a power factor of 0.65 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
P = 200 kWpf1 = 0.65pf2 = 0.95VL = 480 Vf = 60 Hz
Cph = µF
15.TransformersMedium
A single-phase 250 kVA, 7200/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
S = 250 kVAV1 = 7200 VV2 = 240 V
ILV = A
16.TransformersHard
A single-phase 250 kVA transformer has a core loss of 2000 W and a copper loss of 8000 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
S = 250 kVAPcore = 2000 WPcu,fl = 8000 W
Sη,max = kVA
3Solutions
1.Series & parallel resistors
Answer: Req = 17.69 Ω
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R3 + R4 = 6 + 20 = 26 Ω
R2 ∥ 26 = 3·26/(3+26) = 2.69 Ω
Req = R1 + 2.69 = 15 + 2.69 = 17.69 Ω
Answer
Req = 17.69 Ω
2.Series & parallel resistors
Answer: IR1 = 7.96 A
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R5 + R6 = 20 + 15 = 35 Ω
R4 ∥ 35 = 4.375 Ω
R3 + 4.375 = 6.375 Ω
R2 ∥ 6.375 = 1.522 Ω
Req = R1 + 1.522 = 3 + 1.522 = 4.522 Ω
Current from the source
The source sees only Req, so Ohm’s law gives the current it delivers. That current flows through R₁.
IR1 = V1/Req = 36/4.522 = 7.96 A
Answer
IR1 = 7.96 A
3.Nodal analysis
Answer: VB = 9 V
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 6 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R2 + (VA − V1)/R1 + (VA − VB)/R3 = 0
VA/6 + (VA − 6)/5 + (VA − VB)/3 = 0
0.7·VA − 0.3333·VB = 1.2
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
VB/R4 + (VB − VA)/R3 = Is
VB/6 + (VB − VA)/3 = 2.5
−0.3333·VA + 0.5·VB = 2.5
Solve
Δ = (0.7)(0.5) − (−0.3333)(−0.3333) = 0.2389
VA = Δ1/Δ = 1.433/0.2389 = 6 V
VB = Δ2/Δ = 2.15/0.2389 = 9 V
Answer
VB = 9 V
4.Nodal analysis
Answer: IR1 = 0.9766 A
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 18 V, V2 = 5 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R3 + (VA − V1)/R1 + (VA − VB)/R2 = 0
VA/30 + (VA − 18)/15 + (VA − VB)/12 = 0
0.1833·VA − 0.08333·VB = 1.2
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 3·15/(3+15) = 2.5 Ω
Rth = (R1 ∥ R2) + R3 = 2.5 + 2 = 4.5 Ω
Find Vth, the open-circuit voltage
With a–b open, no current flows through R₃, so there is no drop across it and V_b = V_A. R₁ and R₂ form a voltage divider.
Vth = V1·R2/(R1+R2) = 24·15/(3+15) = 20 V
6.Thévenin & Norton
Answer: IN = −1.231 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 3·3/(3+3) = 1.5 Ω
Rth = (R1 ∥ R2) + R3 = 1.5 + 5 = 6.5 Ω
Find Vth, the open-circuit voltage
With a–b open, the only path for Iₛ is through R₃ into node A. Find V_A by superposition of V₁ and Iₛ, then add the drop across R₃.
VA = V1·R2/(R1+R2) + Is·(R1∥R2) = 18 + (−4)·1.5 = 12 V
Vth = VB = VA + Is·R3 = 12 + (−4)·5 = −8 V
Norton equivalent
A Norton source is the same circuit seen as a current source in parallel with R_th. Its current is the short-circuit current at a–b.
IN = Vth/Rth = −8/6.5 = −1.231 A
7.RC & RL transients
Answer: vR = 24.28 V
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Time constant
τ = L/R = 33 mH / 33 Ω = 1 ms
Decay of the current
i(t) = 2·e−1/1 = 0.7358 A
vR = R·i = 33·0.7358 = 24.28 V
Answer
vR = 24.28 V
8.RC & RL transients
Answer: C = 6.139 µF
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Required time constant
6 = 12·(1 − e−200/τ) → τ = 200/ln(12/(12 − 6))
τ = 200/0.6931 = 288.5 ms
Capacitance
kΩ times µF gives milliseconds.
C = τ/R = 288.5/47 = 6.139 µF
Answer
C = 6.139 µF
9.AC impedance & phasors
Answer: φ = 83.11 °
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·1000 = 6283 rad/s
XL = ωL = 6283·0.02 = 125.7 Ω
XC = 1/(ωC) = 1/(6283·100·10⁻⁶) = 1.592 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·100 = 628.3 rad/s
XL = ωL = 628.3·0.2 = 125.7 Ω
XC = 1/(ωC) = 1/(628.3·22·10⁻⁶) = 72.34 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 10/61.18 = 0.1635 A
Voltage across the capacitor
VC = I·XC = 0.1635·72.34 = 11.82 V
Answer
VC = 11.82 V
11.AC power & power factor
Answer: I = 111.1 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 40000/(400·0.9) = 111.1 A
Answer
I = 111.1 A
12.AC power & power factor
Answer: C = 655.8 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 35·tan(53.13°) = 46.67 kvar
Q2 = P·tan φ2 = 35·tan(11.48°) = 7.107 kvar
QC = Q1 − Q2 = 39.56 kvar
Capacitance
A capacitor across the supply delivers Q = V²·ωC.
C = QC/(2πf·V²) = 39560/(2π·60·400²) = 655.8 µF
Answer
C = 655.8 µF
13.Three-phase power
Answer: P = 14.2 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Phase voltage
Vph = VL = 400 V
Phase current
|Z| = √(5² + 12²) = 13 Ω
Iph = 400/13 = 30.77 A
Total real power
Only the resistive part of each impedance absorbs real power.
P = 3·Iph²·R = 3·30.77²·5 = 14.2 kW
Answer
P = 14.2 kW
Check: cos φ = R/|Z| = 0.3846, and √3·VL·IL·cos φ gives the same power.
14.Three-phase power
Answer: Cph = 1935 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 200·tan(acos 0.65) = 200·1.169 = 233.8 kvar
Q2 = 200·tan(acos 0.95) = 200·0.3287 = 65.74 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 168.1 kvar
Capacitance per phase
In a Y bank each capacitor is connected between a line and the star point.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
ILV = S/V = 250000/240 = 1042 A
Answer
ILV = 1042 A
16.Transformers
Answer: Sη,max = 125 kVA
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.