The voltage source Vₛ between A and B has its + terminal at A, so it makes VA − VB = Vₛ. Use nodal analysis with a supernode to find the current IR1 through R1 in the direction of the arrow.
Find the Thévenin voltage Vth seen from terminals a–b.
V1 = 30 VR1 = 6 ΩR2 = 5 ΩR3 = 12 Ω
Vth = V
6.Thévenin & NortonHard
Find the Thévenin voltage Vth seen from terminals a–b.
V1 = 5 VIs = 3 AR1 = 25 ΩR2 = 25 ΩR3 = 10 Ω
Vth = V
7.RC & RL transientsMedium
The inductor carries no current before the switch closes at t = 0. Find the current i at t = 1 ms.
Vs = 24 VR = 68 ΩL = 33 mHt = 1 ms
i = A
8.RC & RL transientsHard
The switch has been closed for a long time, so the circuit is in steady state. At t = 0 the switch opens. Find the current i2 through R2 at t = 20 ms.
Vs = 24 VR1 = 3.3 kΩR2 = 4.7 kΩC = 10 µFt = 20 ms
i2 = mA
9.AC impedance & phasorsMedium
A series RLC circuit is connected to a 120 V (rms), 50 Hz supply. Find the rms current I.
V = 120 V (rms)f = 50 HzR = 40 ΩL = 100 mHC = 22 µF
I = A
10.AC impedance & phasorsHard
A series RLC circuit is connected to a 100 V (rms), 200 Hz supply. Find the rms voltage VC across the capacitor.
V = 100 V (rms)f = 200 HzR = 25 ΩL = 50 mHC = 47 µF
VC = V
11.AC power & power factorMedium
A single-phase motor takes 37 kW at a power factor of 0.75 lagging from a 230 V supply. Find the line current I.
P = 37 kWpf = 0.75V = 230 V
I = A
12.AC power & power factorHard
A single-phase load takes 35 kW at a power factor of 0.7 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
P = 35 kWpf1 = 0.7pf2 = 0.9V = 240 Vf = 50 Hz
Inew = A
13.Three-phase powerMedium
A balanced three-phase load draws a line current of 40 A from a supply with a line-to-line voltage of 400 V. The power factor is 0.95 lagging. Find the total real power P drawn by the load in kW.
VL = 400 VIL = 40 Acos φ = 0.95
P = kW
14.Three-phase powerHard
A balanced three-phase load takes 75 kW at a power factor of 0.75 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
P = 75 kWpf1 = 0.75pf2 = 0.95VL = 690 Vf = 50 Hz
Cph = µF
15.TransformersMedium
A single-phase 10 kVA, 4800/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
S = 10 kVAV1 = 4800 VV2 = 240 V
IHV = A
16.TransformersHard
A single-phase 75 kVA transformer has a core loss of 225 W and a copper loss of 675 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
S = 75 kVAPcore = 225 WPcu,fl = 675 W
Sη,max = kVA
3Solutions
1.Series & parallel resistors
Answer: IR2 = 0.863 A
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R3 + R4 = 15 + 6 = 21 Ω
R2 ∥ 21 = 20·21/(20+21) = 10.24 Ω
Req = R1 + 10.24 = 4 + 10.24 = 14.24 Ω
Current from the source
The source sees only Req, so Ohm’s law gives the current it delivers. That current flows through R₁.
IR1 = V1/Req = 24/14.24 = 1.685 A
Current through R₂
Subtract the drop across R₁ to get the voltage at node A, which is the voltage across R₂.
VA = V1 − IR1·R1 = 24 − 1.685·4 = 17.26 V
IR2 = VA/R2 = 17.26/20 = 0.863 A
Answer
IR2 = 0.863 A
2.Series & parallel resistors
Answer: IR2 = 0.4317 A
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R5 + R6 = 10 + 25 = 35 Ω
R4 ∥ 35 = 14.58 Ω
R3 + 14.58 = 44.58 Ω
R2 ∥ 44.58 = 4.496 Ω
Req = R1 + 4.496 = 8 + 4.496 = 12.5 Ω
Current from the source
The source sees only Req, so Ohm’s law gives the current it delivers. That current flows through R₁.
IR1 = V1/Req = 6/12.5 = 0.4802 A
Current through R₂
Subtract the drop across R₁ to get the voltage at node A, which is the voltage across R₂.
VA = V1 − IR1·R1 = 6 − 0.4802·8 = 2.159 V
IR2 = VA/R2 = 2.159/5 = 0.4317 A
Answer
IR2 = 0.4317 A
3.Nodal analysis
Answer: IR3 = 0.1429 A
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 30 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R2 + (VA − V1)/R1 + (VA − VB)/R3 = 0
VA/8 + (VA − 30)/8 + (VA − VB)/5 = 0
0.45·VA − 0.2·VB = 3.75
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
VB/R4 + (VB − VA)/R3 = Is
VB/12 + (VB − VA)/5 = 1
−0.2·VA + 0.2833·VB = 1
Solve
Δ = (0.45)(0.2833) − (−0.2)(−0.2) = 0.0875
VA = Δ1/Δ = 1.262/0.0875 = 14.43 V
VB = Δ2/Δ = 1.2/0.0875 = 13.71 V
Answer
IR3 = (VA − VB)/R3 = (14.43 − 13.71)/5 = 0.1429 A
4.Nodal analysis
Answer: IR1 = −0.7304 A
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Form a supernode
The voltage source between A and B carries an unknown current, so KCL cannot be written at A or B separately. Enclose A, B and the source in one supernode: the current entering it equals the current leaving it.
VB = VA − 8
(VA − V1)/R1 + VA/R2 + VB/R3 = Is
Solve
(VA − 12)/15 + VA/15 + (VA − 8)/4 = 6
VA·(1/15 + 1/15 + 1/4) = 6 + 12/15 + 8/4 = 8.8
VA = 8.8/0.3833 = 22.96 V
VB = 14.96 V
Current through R₁
IR1 = (V1 − VA)/R1 = (12 − 22.96)/15 = −0.7304 A
Answer
IR1 = −0.7304 A
A negative result means the real current flows against the arrow.
5.Thévenin & Norton
Answer: Vth = 13.64 V
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 6·5/(6+5) = 2.727 Ω
Rth = (R1 ∥ R2) + R3 = 2.727 + 12 = 14.73 Ω
Find Vth, the open-circuit voltage
With a–b open, no current flows through R₃, so there is no drop across it and V_b = V_A. R₁ and R₂ form a voltage divider.
Vth = V1·R2/(R1+R2) = 30·5/(6+5) = 13.64 V
6.Thévenin & Norton
Answer: Vth = 70 V
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 25·25/(25+25) = 12.5 Ω
Rth = (R1 ∥ R2) + R3 = 12.5 + 10 = 22.5 Ω
Find Vth, the open-circuit voltage
With a–b open, the only path for Iₛ is through R₃ into node A. Find V_A by superposition of V₁ and Iₛ, then add the drop across R₃.
VA = V1·R2/(R1+R2) + Is·(R1∥R2) = 2.5 + 3·12.5 = 40 V
Vth = VB = VA + Is·R3 = 40 + 3·10 = 70 V
7.RC & RL transients
Answer: i = 0.308 A
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Time constant and final current
Long after the switch closes the inductor behaves like a short circuit, so the final current is set by R alone.
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Initial capacitor voltage
In steady state the capacitor is an open circuit, so R₁ and R₂ form a voltage divider. The capacitor voltage cannot jump when the switch opens.
vC(0) = 24·4.7/(3.3 + 4.7) = 14.1 V
Time constant after the switch opens
τ = R2·C = 4.7·10 = 47 ms
Discharge
vC(t) = 14.1·e−20/47 = 9.213 V
i2 = vC/R2 = 9.213/4.7 = 1.96 mA
Answer
i2 = 1.96 mA
9.AC impedance & phasors
Answer: I = 0.999 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·50 = 314.2 rad/s
XL = ωL = 314.2·0.1 = 31.42 Ω
XC = 1/(ωC) = 1/(314.2·22·10⁻⁶) = 144.7 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 120/120.1 = 0.999 A
Answer
I = 0.999 A
10.AC impedance & phasors
Answer: VC = 32.39 V
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·200 = 1257 rad/s
XL = ωL = 1257·0.05 = 62.83 Ω
XC = 1/(ωC) = 1/(1257·47·10⁻⁶) = 16.93 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 100/52.27 = 1.913 A
Voltage across the capacitor
VC = I·XC = 1.913·16.93 = 32.39 V
Answer
VC = 32.39 V
11.AC power & power factor
Answer: I = 214.5 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 37000/(230·0.75) = 214.5 A
Answer
I = 214.5 A
12.AC power & power factor
Answer: Inew = 162 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 35·tan(45.57°) = 35.71 kvar
Q2 = P·tan φ2 = 35·tan(25.84°) = 16.95 kvar
QC = Q1 − Q2 = 18.76 kvar
New line current
Inew = P/(V·cos φ2) = 35000/(240·0.9) = 162 A
Answer
Inew = 162 A
13.Three-phase power
Answer: P = 26.33 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·400·40 = 27.71 kVA
Real power
P = S·cos φ = 27.71·0.95 = 26.33 kW
Answer
P = 26.33 kW
14.Three-phase power
Answer: Cph = 277.4 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 75·tan(acos 0.75) = 75·0.8819 = 66.14 kvar
Q2 = 75·tan(acos 0.95) = 75·0.3287 = 24.65 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 41.49 kvar
Capacitance per phase
In a Y bank each capacitor is connected between a line and the star point.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
IHV = S/V = 10000/4800 = 2.083 A
Answer
IHV = 2.083 A
16.Transformers
Answer: Sη,max = 43.3 kVA
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.