The diamond is a voltage-controlled current source that pushes a current of 0.25·VA (in A, with VA in V) up into node B. Use nodal analysis to find the node voltage VB (measured from ground).
The source Vₛ charges the capacitor through R₁, and R₂ is connected in parallel with C. The capacitor is uncharged when the switch closes at t = 0. Find the time constant τ of the circuit after the switch closes.
Vs = 9 VR1 = 2.2 kΩR2 = 6.8 kΩC = 220 µF
τ = ms
8.RC & RL transientsHard
Just before the switch closes at t = 0, the capacitor holds 3 V with the polarity shown. Find the capacitor voltage vC at t = 20 ms.
Vs = 9 VR = 2.2 kΩC = 33 µFvC(0) = 3 Vt = 20 ms
vC = V
9.AC impedance & phasorsMedium
A series RLC circuit is connected to a 230 V (rms), 200 Hz supply. Find the power factor cos φ of the circuit.
V = 230 V (rms)f = 200 HzR = 50 ΩL = 150 mHC = 22 µF
cos φ =
10.AC impedance & phasorsHard
A series RLC circuit is connected to a 230 V (rms), 1000 Hz supply. Find the rms voltage VC across the capacitor.
V = 230 V (rms)f = 1000 HzR = 20 ΩL = 50 mHC = 47 µF
VC = V
11.AC power & power factorMedium
A single-phase motor takes 39 kW at a power factor of 0.65 lagging from a 400 V supply. Find the reactive power Q it draws.
P = 39 kWpf = 0.65V = 400 V
Q = kvar
12.AC power & power factorHard
A single-phase load takes 20 kW at a power factor of 0.6 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
P = 20 kWpf1 = 0.6pf2 = 0.9V = 400 Vf = 50 Hz
C = µF
13.Three-phase powerMedium
A three-phase induction motor delivers 22 kW of mechanical output power at full load. At this load its efficiency is 88% and its power factor is 0.8 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.
Pout = 22 kWη = 88%cos φ = 0.8VL = 400 V
IL = A
14.Three-phase powerHard
A balanced three-phase load takes 75 kW at a power factor of 0.8 lagging from a 400 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 75 kWpf1 = 0.8pf2 = 0.9VL = 400 Vf = 60 Hz
Cph = µF
15.TransformersMedium
A single-phase 50 kVA, 10000/400 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
S = 50 kVAV1 = 10000 VV2 = 400 V
IHV = A
16.TransformersHard
A single-phase 100 kVA transformer has a core loss of 300 W. At rated load and a power factor of 0.95 lagging its efficiency is 98.2%. Find the full-load copper loss Pcu,fl in watts.
S = 100 kVAPcore = 300 Wpf = 0.95η = 98.2%
Pcu,fl = W
3Solutions
1.Series & parallel resistors
Answer: IR2 = 0.902 A
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R3 + R4 = 15 + 8 = 23 Ω
R2 ∥ 23 = 15·23/(15+23) = 9.079 Ω
Req = R1 + 9.079 = 3 + 9.079 = 12.08 Ω
Current from the source
The source sees only Req, so Ohm’s law gives the current it delivers. That current flows through R₁.
IR1 = V1/Req = 18/12.08 = 1.49 A
Current through R₂
Subtract the drop across R₁ to get the voltage at node A, which is the voltage across R₂.
VA = V1 − IR1·R1 = 18 − 1.49·3 = 13.53 V
IR2 = VA/R2 = 13.53/15 = 0.902 A
Answer
IR2 = 0.902 A
2.Series & parallel resistors
Answer: IR2 = 1.608 A
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R5 + R6 = 12 + 8 = 20 Ω
R4 ∥ 20 = 2.609 Ω
R3 + 2.609 = 22.61 Ω
R2 ∥ 22.61 = 4.742 Ω
Req = R1 + 4.742 = 10 + 4.742 = 14.74 Ω
Current from the source
The source sees only Req, so Ohm’s law gives the current it delivers. That current flows through R₁.
IR1 = V1/Req = 30/14.74 = 2.035 A
Current through R₂
Subtract the drop across R₁ to get the voltage at node A, which is the voltage across R₂.
VA = V1 − IR1·R1 = 30 − 2.035·10 = 9.649 V
IR2 = VA/R2 = 9.649/6 = 1.608 A
Answer
IR2 = 1.608 A
3.Nodal analysis
Answer: VB = 11.02 V
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 10 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R2 + (VA − V1)/R1 + (VA − VB)/R3 = 0
VA/5 + (VA − 10)/4 + (VA − VB)/6 = 0
0.6167·VA − 0.1667·VB = 2.5
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
(VA − V1)/R1 + VA/R2 + (VA − VB)/R3 = 0
0.54·VA − 0.04·VB = 3
KCL at node B
The dependent source pushes g·VA into node B. Treat it like an independent source, then move the VA term to the left-hand side.
(VB − VA)/R3 + VB/R4 = 0.25·VA
−0.29·VA + 0.24·VB = 0
Solve
Δ = (0.54)(0.24) − (−0.04)(−0.29) = 0.118
VA = Δ1/Δ = 0.72/0.118 = 6.102 V
VB = Δ2/Δ = 0.87/0.118 = 7.373 V
Answer
VB = 7.373 V
5.Thévenin & Norton
Answer: IL = 0.8889 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 5·5/(5+5) = 2.5 Ω
Rth = (R1 ∥ R2) + R3 = 2.5 + 8 = 10.5 Ω
Find Vth, the open-circuit voltage
With a–b open, no current flows through R₃, so there is no drop across it and V_b = V_A. R₁ and R₂ form a voltage divider.
Vth = V1·R2/(R1+R2) = 24·5/(5+5) = 12 V
Connect the load to the Thévenin equivalent
The Thévenin source and R_th in series behave exactly like the original circuit at a–b, so the load sees a simple series loop.
IL = Vth/(Rth + RL) = 12/(10.5 + 3) = 0.8889 A
6.Thévenin & Norton
Answer: IL = 2.067 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 12·12/(12+12) = 6 Ω
Rth = (R1 ∥ R2) + R3 = 6 + 5 = 11 Ω
Find Vth, the open-circuit voltage
With a–b open, the only path for Iₛ is through R₃ into node A. Find V_A by superposition of V₁ and Iₛ, then add the drop across R₃.
VA = V1·R2/(R1+R2) + Is·(R1∥R2) = 9 + 2·6 = 21 V
Vth = VB = VA + Is·R3 = 21 + 2·5 = 31 V
Connect the load to the Thévenin equivalent
The Thévenin source and R_th in series behave exactly like the original circuit at a–b, so the load sees a simple series loop.
IL = Vth/(Rth + RL) = 31/(11 + 4) = 2.067 A
7.RC & RL transients
Answer: τ = 365.7 ms
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Thévenin equivalent seen by the capacitor
Short the source to find Rth; open the capacitor to find the voltage it will settle at.
Rth = R1 ∥ R2 = 2.2·6.8/(2.2 + 6.8) = 1.662 kΩ
vC(∞) = 9·6.8/(2.2 + 6.8) = 6.8 V
Time constant
τ = Rth·C = 1.662·220 = 365.7 ms
Answer
τ = 365.7 ms
8.RC & RL transients
Answer: vC = 4.445 V
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Initial value, final value, time constant
The capacitor voltage cannot jump, so it starts at its stored value and heads for the source voltage.
vC(0) = 3 V, vC(∞) = Vs = 9 V
τ = R·C = 2.2 kΩ · 33 µF = 72.6 ms
vC(t) = 9 + (3 − 9)·e−t/τ
Voltage at the given time
vC(20) = 9 + (−6)·e−20/72.6 = 4.445 V
Answer
vC = 4.445 V
9.AC impedance & phasors
Answer: cos φ = 0.3119
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
XL = 188.5 Ω, XC = 36.17 Ω
Impedance
|Z| = √(50² + (152.3)²) = 160.3 Ω
Power factor
cos φ = R/|Z| = 50/160.3 = 0.3119
The circuit is inductive, so the power factor is lagging.
Answer
cos φ = 0.3119
10.AC impedance & phasors
Answer: VC = 2.501 V
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·1000 = 6283 rad/s
XL = ωL = 6283·0.05 = 314.2 Ω
XC = 1/(ωC) = 1/(6283·47·10⁻⁶) = 3.386 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 230/311.4 = 0.7386 A
Voltage across the capacitor
VC = I·XC = 0.7386·3.386 = 2.501 V
Answer
VC = 2.501 V
11.AC power & power factor
Answer: Q = 45.6 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Angle
φ = arccos(0.65) = 49.46°, tan φ = 1.169
Reactive power
Q = P·tan φ = 39·1.169 = 45.6 kvar
Answer
Q = 45.6 kvar
12.AC power & power factor
Answer: C = 337.8 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 20·tan(53.13°) = 26.67 kvar
Q2 = P·tan φ2 = 20·tan(25.84°) = 9.686 kvar
QC = Q1 − Q2 = 16.98 kvar
Capacitance
A capacitor across the supply delivers Q = V²·ωC.
C = QC/(2πf·V²) = 16980/(2π·50·400²) = 337.8 µF
Answer
C = 337.8 µF
13.Three-phase power
Answer: IL = 45.11 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 22/0.88 = 25 kW
Line current
IL = Pin/(√3·VL·cos φ) = 25000/(√3·400·0.8) = 45.11 A
Answer
IL = 45.11 A
14.Three-phase power
Answer: Cph = 110.1 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 75·tan(acos 0.8) = 75·0.75 = 56.25 kvar
Q2 = 75·tan(acos 0.9) = 75·0.4843 = 36.32 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 19.93 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.
V = 400 V, ω = 2π·60 = 377 rad/s
Cph = (QC/3)/(ω·V²) = 6642/(377·400²) = 110.1 µF
Answer
Cph = 110.1 µF
15.Transformers
Answer: IHV = 5 A
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
IHV = S/V = 50000/10000 = 5 A
Answer
IHV = 5 A
16.Transformers
Answer: Pcu,fl = 1441 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.