The diamond is a voltage-controlled current source that pushes a current of 0.25·VA (in A, with VA in V) up into node B. Use nodal analysis to find the current IR4 through R4 in the direction of the arrow.
The inductor carries no current before the switch closes at t = 0. How long after the switch closes does the current reach 95% of its final value? Find t.
Vs = 9 VR = 15 ΩL = 22 mH
t = ms
8.RC & RL transientsHard
The switch across R2 has been closed for a long time, so the inductor current is steady. At t = 0 the switch opens. How long after t = 0 does the inductor current reach 1.44 A? Find t.
Vs = 24 VR1 = 15 ΩR2 = 5 ΩL = 100 mH
t = ms
9.AC impedance & phasorsMedium
A series RLC circuit is connected to a 24 V (rms), 60 Hz supply. Find the power factor cos φ of the circuit.
V = 24 V (rms)f = 60 HzR = 60 ΩL = 100 mHC = 47 µF
cos φ =
10.AC impedance & phasorsHard
A series RLC circuit is driven by a 12 V (rms) source whose frequency is set to the resonant frequency of the circuit. Find the rms voltage VL across the inductor.
V = 12 V (rms)R = 15 ΩL = 200 mHC = 0.47 µF
VL = V
11.AC power & power factorMedium
Two loads are connected in parallel to a 400 V single-phase supply: an 8 kW load at a power factor of 0.7 lagging and an 8 kW load at a power factor of 0.85 lagging. Find the total current I drawn from the supply.
A 150 kVA single-phase transformer supplies a load of 77 kW at a power factor of 0.7 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Smax = 150 kVAP1 = 77 kWpf1 = 0.7
ΔP = kW
13.Three-phase powerMedium
A three-phase induction motor delivers 15 kW of mechanical output power at full load. At this load its efficiency is 88% and its power factor is 0.88 lagging. The supply has a line-to-line voltage of 480 V. Find the line current IL.
Pout = 15 kWη = 88%cos φ = 0.88VL = 480 V
IL = A
14.Three-phase powerHard
A balanced three-phase load takes 250 kW at a power factor of 0.65 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 250 kWpf1 = 0.65pf2 = 0.92VL = 690 Vf = 60 Hz
QC = kvar
15.TransformersMedium
A single-phase 250 kVA, 480/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
S = 250 kVAV1 = 480 VV2 = 240 V
IHV = A
16.TransformersHard
A single-phase 100 kVA transformer has a core loss of 600 W and a copper loss of 1800 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R3 + R4 = 12 + 10 = 22 Ω
R2 ∥ 22 = 2·22/(2+22) = 1.833 Ω
Req = R1 + 1.833 = 5 + 1.833 = 6.833 Ω
Answer
Req = 6.833 Ω
2.Series & parallel resistors
Answer: IR1 = 0.5227 A
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R5 + R6 = 6 + 25 = 31 Ω
R4 ∥ 31 = 10.11 Ω
R3 + 10.11 = 40.11 Ω
R2 ∥ 40.11 = 5.219 Ω
Req = R1 + 5.219 = 12 + 5.219 = 17.22 Ω
Current from the source
The source sees only Req, so Ohm’s law gives the current it delivers. That current flows through R₁.
IR1 = V1/Req = 9/17.22 = 0.5227 A
Answer
IR1 = 0.5227 A
3.Nodal analysis
Answer: VA = 8.205 V
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 10 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R2 + (VA − V1)/R1 + (VA − VB)/R3 = 0
VA/12 + (VA − 10)/2 + (VA − VB)/10 = 0
0.6833·VA − 0.1·VB = 5
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
VB/R4 + (VB − VA)/R3 = Is
VB/5 + (VB − VA)/10 = 1
−0.1·VA + 0.3·VB = 1
Solve
Δ = (0.6833)(0.3) − (−0.1)(−0.1) = 0.195
VA = Δ1/Δ = 1.6/0.195 = 8.205 V
VB = Δ2/Δ = 1.183/0.195 = 6.068 V
Answer
VA = 8.205 V
4.Nodal analysis
Answer: IR4 = 5.682 A
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
(VA − V1)/R1 + VA/R2 + (VA − VB)/R3 = 0
0.54·VA − 0.25·VB = 7.5
KCL at node B
The dependent source pushes g·VA into node B. Treat it like an independent source, then move the VA term to the left-hand side.
(VB − VA)/R3 + VB/R4 = 0.25·VA
−0.5·VA + 0.3333·VB = 0
Solve
Δ = (0.54)(0.3333) − (−0.25)(−0.5) = 0.055
VA = Δ1/Δ = 2.5/0.055 = 45.45 V
VB = Δ2/Δ = 3.75/0.055 = 68.18 V
Current through R₄
IR4 = VB/R4 = 68.18/12 = 5.682 A
Answer
IR4 = 5.682 A
5.Thévenin & Norton
Answer: IN = 0.2744 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 20·6/(20+6) = 4.615 Ω
Rth = (R1 ∥ R2) + R3 = 4.615 + 8 = 12.62 Ω
Find Vth, the open-circuit voltage
With a–b open, no current flows through R₃, so there is no drop across it and V_b = V_A. R₁ and R₂ form a voltage divider.
Vth = V1·R2/(R1+R2) = 15·6/(20+6) = 3.462 V
Norton equivalent
A Norton source is the same circuit seen as a current source in parallel with R_th. Its current is the short-circuit current at a–b.
IN = Vth/Rth = 3.462/12.62 = 0.2744 A
6.Thévenin & Norton
Answer: IL = 5.611 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 6·25/(6+25) = 4.839 Ω
Rth = (R1 ∥ R2) + R3 = 4.839 + 30 = 34.84 Ω
Find Vth, the open-circuit voltage
With a–b open, the only path for Iₛ is through R₃ into node A. Find V_A by superposition of V₁ and Iₛ, then add the drop across R₃.
VA = V1·R2/(R1+R2) + Is·(R1∥R2) = 14.52 + 6·4.839 = 43.55 V
Vth = VB = VA + Is·R3 = 43.55 + 6·30 = 223.5 V
Connect the load to the Thévenin equivalent
The Thévenin source and R_th in series behave exactly like the original circuit at a–b, so the load sees a simple series loop.
IL = Vth/(Rth + RL) = 223.5/(34.84 + 5) = 5.611 A
7.RC & RL transients
Answer: t = 4.394 ms
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Time constant and final current
Long after the switch closes the inductor behaves like a short circuit, so the final current is set by R alone.
τ = L/R = 22 mH / 15 Ω = 1.467 ms
i(∞) = Vs/R = 9/15 = 0.6 A
Solve for the time
0.95 = 1 − e−t/τ → t = −τ·ln(1 − 0.95)
t = −1.467·ln(0.05) = 4.394 ms
Answer
t = 4.394 ms
8.RC & RL transients
Answer: t = 2.554 ms
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Initial value, final value, time constant
Before t = 0 the closed switch bypasses R₂; afterwards R₁ and R₂ are both in the loop.
i(0) = 24/15 = 1.6 A
i(∞) = 24/(15 + 5) = 1.2 A
τ = L/R = 100/20 = 5 ms
i(t) = 1.2 + (1.6 − 1.2)·e−t/τ
Solve for the time
e−t/τ = (1.44 − 1.2)/(1.6 − 1.2) = 0.6
t = 5·ln(1.667) = 2.554 ms
Answer
t = 2.554 ms
9.AC impedance & phasors
Answer: cos φ = 0.9545
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
XL = 37.7 Ω, XC = 56.44 Ω
Impedance
|Z| = √(60² + (−18.74)²) = 62.86 Ω
Power factor
cos φ = R/|Z| = 60/62.86 = 0.9545
The circuit is capacitive, so the power factor is leading.
Answer
cos φ = 0.9545
10.AC impedance & phasors
Answer: VL = 521.9 V
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Resonance
At resonance the reactances cancel, so the impedance is just R.
ω₀ = 1/√(LC) = 1/√(0.2·0.47·10⁻⁶) = 3262 rad/s
I = V/R = 12/15 = 0.8 A
Voltage across the inductor
XL = ω₀L = 3262·0.2 = 652.3 Ω
VL = I·XL = 0.8·652.3 = 521.9 V
Answer
VL = 521.9 V
This is Q = 43.49 times the supply voltage.
11.AC power & power factor
Answer: I = 51.73 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of each load
A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).
Q1 = 8·tan(arccos 0.7) = 8.162 kvar
Q2 = 8·tan(arccos 0.85) = 4.958 kvar
Totals
P = 8 + 8 = 16 kW
Q = 8.162 + 4.958 = 13.12 kvar
S = √(16² + 13.12²) = 20.69 kVA
Total current
I = S/V = 20691/400 = 51.73 A
Answer
I = 51.73 A
12.AC power & power factor
Answer: ΔP = 50.78 kW
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of the existing load
Q1 = 77·tan(arccos 0.7) = 78.56 kvar
Largest total real power
At full rating S = Smax, and Q is unchanged by the resistive load.
P = √(Smax² − Q1²) = √(150² − 78.56²) = 127.8 kW
Extra real power
ΔP = 127.8 − 77 = 50.78 kW
Answer
ΔP = 50.78 kW
13.Three-phase power
Answer: IL = 23.3 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 15/0.88 = 17.05 kW
Line current
IL = Pin/(√3·VL·cos φ) = 17045/(√3·480·0.88) = 23.3 A
Answer
IL = 23.3 A
14.Three-phase power
Answer: QC = 185.8 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 250·tan(acos 0.65) = 250·1.169 = 292.3 kvar
Q2 = 250·tan(acos 0.92) = 250·0.426 = 106.5 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 185.8 kvar
Answer
QC = 185.8 kvar
15.Transformers
Answer: IHV = 520.8 A
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
IHV = S/V = 250000/480 = 520.8 A
Answer
IHV = 520.8 A
16.Transformers
Answer: Ploss = 1050 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.