Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 100 mm of concrete and 100 mm of mineral wool, with an area of 6 m². The outer faces are at 25 °C and -1 °C. Find the temperature Ti at the interface between the two layers.
A wall of 200 mm mineral wool and 150 mm gypsum board separates a room at 22 °C from outside air at 4 °C. The convection coefficients are 8 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 8 m². Find the temperature Ts of the inside surface of the wall.
A parallel-flow heat exchanger transfers 340 kW. The hot fluid cools from 110 to 65 °C and the cold fluid heats from 20 to 45 °C. The overall heat transfer coefficient is 1500 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 2 kW/K. The hot stream enters at 85 °C and the cold stream at 10 °C. The exchanger has A = 5 m² and U = 300 W/(m²·K). Find the hot outlet temperature Th,out.
Answer: Ti = 24.28 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: Ts = 21.63 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 4.87 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In parallel flow both inlets are at the same end, and both outlets at the other.
Answer: Th,out = 52.86 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.
Heat transferred: Q̇ = 64.29 kW; the cold stream leaves at 42.14 °C.