Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Glass, k = 0.9650 mmExpanded polystyrene, k = 0.03525 mm25 °C8 °CQ̇ = ?

A wall is made of 50 mm of glass and 25 mm of expanded polystyrene, with an area of 4 m². The outer faces are at 25 °C and 8 °C. Find the heat flow Q̇ through the wall.

L1 = 50 mm, k1 = 0.96 W/(m·K)L2 = 25 mm, k2 = 0.035 W/(m·K)A = 4 m²T1 = 25 °CT3 = 8 °C
Q̇ = W
2.Heat conductionHard
Brick, k = 0.72250 mmGlass, k = 0.96100 mmroom 21 °Coutside -13 °CQ̇

A wall of 250 mm brick and 100 mm glass separates a room at 21 °C from outside air at -13 °C. The convection coefficients are 7.7 W/(m²·K) inside and 30 W/(m²·K) outside, and the wall area is 15 m². Find the overall heat transfer coefficient U of the wall.

L1 = 250 mm, k1 = 0.72 W/(m·K)L2 = 100 mm, k2 = 0.96 W/(m·K)A = 15 m²hi = 7.7 W/(m²·K)ho = 30 W/(m²·K)Troom = 21 °CTout = -13 °C
U = W/(m²·K)
3.Heat exchangers (LMTD)Medium
lengthT145 °C100 °C30 °C80 °CΔT₁ΔT₂parallel flow

A parallel-flow heat exchanger transfers 160 kW. The hot fluid cools from 145 to 100 °C and the cold fluid heats from 30 to 80 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 160 kWU = 300 W/(m²·K)Th: 145 → 100 °CTc: 30 → 80 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT100 °C75 °C31.75 °C15 °CΔT₁ΔT₂counter-flow

Hot oil (2 kg/s, cp = 2.1 kJ/(kg·K)) cools from 100 to 75 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.

ṁh = 2 kg/scp,h = 2.1 kJ/(kg·K)Th: 100 → 75 °Cṁc = 1.5 kg/scp,c = 4.18 kJ/(kg·K)Tc,in = 15 °CU = 500 W/(m²·K)
A = m²

3Solutions

1.Heat conduction

Answer: Q̇ = 88.73 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (50/1000)/(0.96·4) = 0.01302 K/W
R2 = L2/(k2A) = (25/1000)/(0.035·4) = 0.1786 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 17/0.1916 = 88.73 W

Answer

Q̇ = 88.73 W
2.Heat conduction

Answer: U = 1.627 W/(m²·K)

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(7.7·15) = 0.008658 K/W
R1 = L1/(k1A) = (250/1000)/(0.72·15) = 0.02315 K/W
R2 = L2/(k2A) = (100/1000)/(0.96·15) = 0.006944 K/W
Ro = 1/(hoA) = 1/(30·15) = 0.002222 K/W
ΣR = 0.04097 K/W

Overall coefficient

U = 1/(A·ΣR) = 1/(15·0.04097) = 1.627 W/(m²·K)

Answer

U = 1.627 W/(m²·K)
3.Heat exchangers (LMTD)

Answer: A = 9.82 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In parallel flow both inlets are at the same end, and both outlets at the other.

ΔT₁ = Th,in − Tc,in = 145 − 30 = 115 K
ΔT₂ = Th,out − Tc,out = 100 − 80 = 20 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (115 − 20)/ln(115/20) = 54.31 K

Area

A = Q̇/(U·ΔTlm) = 160000/(300·54.31) = 9.82 m²

Answer

A = 9.82 m²
4.Heat exchangers (LMTD)

Answer: A = 3.279 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = ṁhcp,h(Th,in − Th,out) = 2·2.1·25 = 105 kW
Tc,out = 15 + 105/(1.5·4.18) = 31.75 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 100 − 31.75 = 68.25 K
ΔT₂ = Th,out − Tc,in = 75 − 15 = 60 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (68.25 − 60)/ln(68.25/60) = 64.04 K

Area

A = Q̇/(U·ΔTlm) = 105000/(500·64.04) = 3.279 m²

Answer

A = 3.279 m²

ExamProblems · examproblems.com/courses/heat-transfer