Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 150 mm of glass and 25 mm of concrete, with an area of 8 m². The outer faces are at 25 °C and 5 °C. Find the temperature Ti at the interface between the two layers.
A wall of 200 mm concrete and 100 mm expanded polystyrene separates a room at 22 °C from outside air at -5 °C. The convection coefficients are 8 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 6 m². Find the overall heat transfer coefficient U of the wall.
In a condenser, steam condenses at a constant 130 °C on the outside of the tubes. Cooling water (4 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 25 to 45 °C. The overall heat transfer coefficient is 3000 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1.5 kW/K. The hot stream enters at 105 °C and the cold stream at 20 °C. The exchanger has A = 1.5 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Answer: Ti = 7.051 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: U = 0.316 W/(m²·K)
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 1.178 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
Answer: Th,out = 67.22 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.
Heat transferred: Q̇ = 56.67 kW; the cold stream leaves at 57.78 °C.
ExamProblems · examproblems.com/courses/heat-transfer