Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 50 mm of brick and 100 mm of glass, with an area of 10 m². The outer faces are at 16 °C and 10 °C. Find the heat flow Q̇ through the wall.
A wall of 200 mm gypsum board and 75 mm concrete separates a room at 22 °C from outside air at -10 °C. The convection coefficients are 7.7 W/(m²·K) inside and 30 W/(m²·K) outside, and the wall area is 15 m². Find the overall heat transfer coefficient U of the wall.
A counter-flow heat exchanger transfers 410 kW. The hot fluid cools from 180 to 90 °C and the cold fluid heats from 15 to 155 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
Steam condenses at a constant 120 °C on the outside of the tubes of a condenser with a heat transfer area of 3 m² and U = 2500 W/(m²·K). Cooling water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 20 °C. Find the water outlet temperature Tc,out.
Answer: Q̇ = 345.6 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: U = 0.7177 W/(m²·K)
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 30.03 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
Answer: Tc,out = 89.77 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
With ΔT₁ = Ts − Tc,in and ΔT₂ = Ts − Tc,out, the difference ΔT₁ − ΔT₂ equals the water temperature rise, so the rise cancels.
Heat transferred: Q̇ = 437.4 kW.
ExamProblems · examproblems.com/courses/heat-transfer