Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Wood, k = 0.17200 mmBrick, k = 0.72100 mm20 °C0 °CQ̇ = ?

A wall is made of 200 mm of wood and 100 mm of brick, with an area of 10 m². The outer faces are at 20 °C and 0 °C. Find the heat flow Q̇ through the wall.

L1 = 200 mm, k1 = 0.17 W/(m·K)L2 = 100 mm, k2 = 0.72 W/(m·K)A = 10 m²T1 = 20 °CT3 = 0 °C
Q̇ = W
2.Heat conductionHard
Brick, k = 0.72250 mmGlass, k = 0.9625 mmroom 21 °Coutside 2 °CQ̇

A wall of 250 mm brick and 25 mm glass separates a room at 21 °C from outside air at 2 °C. The convection coefficients are 7.7 W/(m²·K) inside and 30 W/(m²·K) outside, and the wall area is 12 m². Find the overall heat transfer coefficient U of the wall.

L1 = 250 mm, k1 = 0.72 W/(m·K)L2 = 25 mm, k2 = 0.96 W/(m·K)A = 12 m²hi = 7.7 W/(m²·K)ho = 30 W/(m²·K)Troom = 21 °CTout = 2 °C
U = W/(m²·K)
3.Heat exchangers (LMTD)Medium
lengthT110 °C15 °C80 °CΔT₁ΔT₂condensing steam

In a condenser, steam condenses at a constant 110 °C on the outside of the tubes. Cooling water (2 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 15 to 80 °C. The overall heat transfer coefficient is 2500 W/(m²·K). Find the heat transfer area A needed.

Ts = 110 °Cṁ = 2 kg/scp = 4.18 kJ/(kg·K)Tc: 15 → 80 °CU = 2500 W/(m²·K)
A = m²
4.Heat exchangers (LMTD)Hard
lengthT150 °C70 °C45.14 °C15 °CΔT₁ΔT₂counter-flow

Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 150 to 70 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.

ṁh = 1.5 kg/scp,h = 2.1 kJ/(kg·K)Th: 150 → 70 °Cṁc = 2 kg/scp,c = 4.18 kJ/(kg·K)Tc,in = 15 °CU = 800 W/(m²·K)
A = m²

3Solutions

1.Heat conduction

Answer: Q̇ = 152 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (200/1000)/(0.17·10) = 0.1176 K/W
R2 = L2/(k2A) = (100/1000)/(0.72·10) = 0.01389 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 20/0.1315 = 152 W

Answer

Q̇ = 152 W
2.Heat conduction

Answer: U = 1.864 W/(m²·K)

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(7.7·12) = 0.01082 K/W
R1 = L1/(k1A) = (250/1000)/(0.72·12) = 0.02894 K/W
R2 = L2/(k2A) = (25/1000)/(0.96·12) = 0.00217 K/W
Ro = 1/(hoA) = 1/(30·12) = 0.002778 K/W
ΣR = 0.04471 K/W

Overall coefficient

U = 1/(A·ΣR) = 1/(12·0.04471) = 1.864 W/(m²·K)

Answer

U = 1.864 W/(m²·K)
3.Heat exchangers (LMTD)

Answer: A = 3.855 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty from the water side

Q̇ = 2·4.18·(80 − 15) = 543.4 kW

End temperature differences

ΔT₁ = 110 − 15 = 95 K
ΔT₂ = 110 − 80 = 30 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (95 − 30)/ln(95/30) = 56.39 K

Area

A = Q̇/(U·ΔTlm) = 543400/(2500·56.39) = 3.855 m²

Answer

A = 3.855 m²
4.Heat exchangers (LMTD)

Answer: A = 4.077 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = ṁhcp,h(Th,in − Th,out) = 1.5·2.1·80 = 252 kW
Tc,out = 15 + 252/(2·4.18) = 45.14 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 150 − 45.14 = 104.9 K
ΔT₂ = Th,out − Tc,in = 70 − 15 = 55 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (104.9 − 55)/ln(104.9/55) = 77.27 K

Area

A = Q̇/(U·ΔTlm) = 252000/(800·77.27) = 4.077 m²

Answer

A = 4.077 m²

ExamProblems · examproblems.com/courses/heat-transfer