Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 200 mm of mineral wool and 25 mm of gypsum board, with an area of 4 m². The outer faces are at 18 °C and 8 °C. Find the heat flow Q̇ through the wall.
A wall of 200 mm wood and 25 mm mineral wool separates a room at 21 °C from outside air at -7 °C. The convection coefficients are 10 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 20 m². Find the heat loss Q̇ through the wall.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 470 kW. The hot fluid cools from 150 to 65 °C and the cold fluid heats from 15 to 105 °C. The LMTD correction factor for this arrangement is F = 0.88, and U = 500 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 3 kW/K. The hot stream enters at 95 °C and the cold stream at 30 °C. The exchanger has A = 3 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Answer: Q̇ = 7.771 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: Q̇ = 287 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 22.51 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
Answer: Th,out = 66.11 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.
Heat transferred: Q̇ = 86.67 kW; the cold stream leaves at 58.89 °C.
ExamProblems · examproblems.com/courses/heat-transfer