Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Brick, k = 0.72200 mmWood, k = 0.17100 mm16 °C-11 °CTi​ = ?Q̇

A wall is made of 200 mm of brick and 100 mm of wood, with an area of 10 m². The outer faces are at 16 °C and -11 °C. Find the temperature Ti at the interface between the two layers.

L1 = 200 mm, k1 = 0.72 W/(m·K)L2 = 100 mm, k2 = 0.17 W/(m·K)A = 10 m²T1 = 16 °CT3 = -11 °C
Ti = °C
2.Heat conductionHard
Gypsum board, k = 0.17200 mmMineral wool, k = 0.04100 mmroom 22 °Coutside -5 °CTs​ = ?Q̇

A wall of 200 mm gypsum board and 100 mm mineral wool separates a room at 22 °C from outside air at -5 °C. The convection coefficients are 10 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 10 m². Find the temperature Ts of the inside surface of the wall.

L1 = 200 mm, k1 = 0.17 W/(m·K)L2 = 100 mm, k2 = 0.04 W/(m·K)A = 10 m²hi = 10 W/(m²·K)ho = 20 W/(m²·K)Troom = 22 °CTout = -5 °C
Ts = °C
3.Heat exchangers (LMTD)Medium
lengthT100 °C85 °C40 °C15 °CΔT₁ΔT₂counter-flow

A counter-flow heat exchanger transfers 370 kW. The hot fluid cools from 100 to 85 °C and the cold fluid heats from 15 to 40 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 370 kWU = 200 W/(m²·K)Th: 100 → 85 °CTc: 15 → 40 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT85 °C35 °C14.59 °C10 °CΔT₁ΔT₂counter-flow

Hot oil (0.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 85 to 35 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 1500 W/(m²·K), find the heat transfer area A needed.

ṁh = 0.5 kg/scp,h = 2.3 kJ/(kg·K)Th: 85 → 35 °Cṁc = 3 kg/scp,c = 4.18 kJ/(kg·K)Tc,in = 10 °CU = 1500 W/(m²·K)
A = m²

3Solutions

1.Heat conduction

Answer: Ti = 7.34 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (200/1000)/(0.72·10) = 0.02778 K/W
R2 = L2/(k2A) = (100/1000)/(0.17·10) = 0.05882 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 27/0.0866 = 311.8 W

Interface temperature

The temperature drops across the first layer by Q̇·R₁.

Ti = T1 − Q̇·R1 = 16 − 311.8·0.02778 = 7.34 °C

Answer

Ti = 7.34 °C
2.Heat conduction

Answer: Ts = 21.29 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(10·10) = 0.01 K/W
R1 = L1/(k1A) = (200/1000)/(0.17·10) = 0.1176 K/W
R2 = L2/(k2A) = (100/1000)/(0.04·10) = 0.25 K/W
Ro = 1/(hoA) = 1/(20·10) = 0.005 K/W
ΣR = 0.3826 K/W

Heat loss

Q̇ = (22 − (-5))/0.3826 = 70.56 W
Ts = Troom − Q̇·Ri = 22 − 70.56·0.01 = 21.29 °C

Answer

Ts = 21.29 °C
3.Heat exchangers (LMTD)

Answer: A = 28.52 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 100 − 40 = 60 K
ΔT₂ = Th,out − Tc,in = 85 − 15 = 70 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (60 − 70)/ln(60/70) = 64.87 K

Area

A = Q̇/(U·ΔTlm) = 370000/(200·64.87) = 28.52 m²

Answer

A = 28.52 m²
4.Heat exchangers (LMTD)

Answer: A = 0.8741 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = ṁhcp,h(Th,in − Th,out) = 0.5·2.3·50 = 57.5 kW
Tc,out = 10 + 57.5/(3·4.18) = 14.59 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 85 − 14.59 = 70.41 K
ΔT₂ = Th,out − Tc,in = 35 − 10 = 25 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (70.41 − 25)/ln(70.41/25) = 43.86 K

Area

A = Q̇/(U·ΔTlm) = 57500/(1500·43.86) = 0.8741 m²

Answer

A = 0.8741 m²

ExamProblems · examproblems.com/courses/heat-transfer