Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 50 mm of mineral wool and 75 mm of expanded polystyrene, with an area of 15 m². The outer faces are at 19 °C and 0 °C. Find the heat flow Q̇ through the wall.
A wall of 150 mm wood and 75 mm expanded polystyrene separates a room at 21 °C from outside air at 5 °C. The convection coefficients are 7.7 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 8 m². Find the heat loss Q̇ through the wall.
A parallel-flow heat exchanger transfers 280 kW. The hot fluid cools from 155 to 105 °C and the cold fluid heats from 20 to 45 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 4 kW/K. The hot stream enters at 125 °C and the cold stream at 15 °C. The exchanger has A = 4 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Answer: Q̇ = 84 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: Q̇ = 39.94 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 10.09 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In parallel flow both inlets are at the same end, and both outlets at the other.
Answer: Th,out = 88.33 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.
Heat transferred: Q̇ = 146.7 kW; the cold stream leaves at 51.67 °C.