Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 50 mm of concrete and 25 mm of wood, with an area of 10 m². The outer faces are at 21 °C and 5 °C. Find the temperature Ti at the interface between the two layers.
A wall of 250 mm mineral wool and 100 mm gypsum board separates a room at 20 °C from outside air at 3 °C. The convection coefficients are 10 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 20 m². Find the overall heat transfer coefficient U of the wall.
A parallel-flow heat exchanger transfers 260 kW. Its heat transfer area is 12 m². The hot fluid cools from 135 to 115 °C and the cold fluid heats from 20 to 60 °C. Find the overall heat transfer coefficient U.
Hot oil (1.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 85 to 55 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. With U = 1500 W/(m²·K), find the heat transfer area A needed.
Answer: Ti = 17.87 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: U = 0.1433 W/(m²·K)
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: U = 266.4 W/(m²·K)
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In parallel flow both inlets are at the same end, and both outlets at the other.
Answer: A = 1.837 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
ExamProblems · examproblems.com/courses/heat-transfer