Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 50 mm of brick and 100 mm of wood, with an area of 8 m². The outer faces are at 20 °C and 6 °C. Find the temperature Ti at the interface between the two layers.
A wall of 250 mm expanded polystyrene and 25 mm mineral wool separates a room at 21 °C from outside air at -11 °C. The convection coefficients are 7.7 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 6 m². Find the heat loss Q̇ through the wall.
A parallel-flow heat exchanger transfers 190 kW. The hot fluid cools from 90 to 70 °C and the cold fluid heats from 20 to 65 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) flows in the inner tube and cools from 155 to 75 °C. Water (0.2 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 20 °C. The inner tube has a diameter of 40 mm, and U = 150 W/(m²·K) is based on this diameter. Find the tube length L needed.
Answer: Ti = 18.52 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: Q̇ = 24.19 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 15.43 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In parallel flow both inlets are at the same end, and both outlets at the other.
Answer: L = 170.6 m
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.