Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Concrete, k = 1.4250 mmMineral wool, k = 0.0475 mm20 °C9 °CTi​ = ?Q̇

A wall is made of 250 mm of concrete and 75 mm of mineral wool, with an area of 20 m². The outer faces are at 20 °C and 9 °C. Find the temperature Ti at the interface between the two layers.

L1 = 250 mm, k1 = 1.4 W/(m·K)L2 = 75 mm, k2 = 0.04 W/(m·K)A = 20 m²T1 = 20 °CT3 = 9 °C
Ti = °C
2.Heat conductionHard
Mineral wool, k = 0.04100 mmGlass, k = 0.96150 mmroom 20 °Coutside 3 °CQ̇ = ?

A wall of 100 mm mineral wool and 150 mm glass separates a room at 20 °C from outside air at 3 °C. The convection coefficients are 8 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 12 m². Find the heat loss Q̇ through the wall.

L1 = 100 mm, k1 = 0.04 W/(m·K)L2 = 150 mm, k2 = 0.96 W/(m·K)A = 12 m²hi = 8 W/(m²·K)ho = 20 W/(m²·K)Troom = 20 °CTout = 3 °C
Q̇ = W
3.Heat exchangers (LMTD)Medium
lengthT150 °C110 °C30 °C90 °CΔT₁ΔT₂parallel flow

A parallel-flow heat exchanger transfers 430 kW. The hot fluid cools from 150 to 110 °C and the cold fluid heats from 30 to 90 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 430 kWU = 800 W/(m²·K)Th: 150 → 110 °CTc: 30 → 90 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT160 °C95 °C18.94 °C10 °CΔT₁ΔT₂counter-flow

Hot oil (0.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 160 to 95 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 300 W/(m²·K), find the heat transfer area A needed.

ṁh = 0.5 kg/scp,h = 2.3 kJ/(kg·K)Th: 160 → 95 °Cṁc = 2 kg/scp,c = 4.18 kJ/(kg·K)Tc,in = 10 °CU = 300 W/(m²·K)
A = m²

3Solutions

1.Heat conduction

Answer: Ti = 19.04 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (250/1000)/(1.4·20) = 0.008929 K/W
R2 = L2/(k2A) = (75/1000)/(0.04·20) = 0.09375 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 11/0.1027 = 107.1 W

Interface temperature

The temperature drops across the first layer by Q̇·R₁.

Ti = T1 − Q̇·R1 = 20 − 107.1·0.008929 = 19.04 °C

Answer

Ti = 19.04 °C
2.Heat conduction

Answer: Q̇ = 72.05 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(8·12) = 0.01042 K/W
R1 = L1/(k1A) = (100/1000)/(0.04·12) = 0.2083 K/W
R2 = L2/(k2A) = (150/1000)/(0.96·12) = 0.01302 K/W
Ro = 1/(hoA) = 1/(20·12) = 0.004167 K/W
ΣR = 0.2359 K/W

Heat loss

Q̇ = (20 − (3))/0.2359 = 72.05 W

Answer

Q̇ = 72.05 W
3.Heat exchangers (LMTD)

Answer: A = 9.631 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In parallel flow both inlets are at the same end, and both outlets at the other.

ΔT₁ = Th,in − Tc,in = 150 − 30 = 120 K
ΔT₂ = Th,out − Tc,out = 110 − 90 = 20 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (120 − 20)/ln(120/20) = 55.81 K

Area

A = Q̇/(U·ΔTlm) = 430000/(800·55.81) = 9.631 m²

Answer

A = 9.631 m²
4.Heat exchangers (LMTD)

Answer: A = 2.251 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = ṁhcp,h(Th,in − Th,out) = 0.5·2.3·65 = 74.75 kW
Tc,out = 10 + 74.75/(2·4.18) = 18.94 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 160 − 18.94 = 141.1 K
ΔT₂ = Th,out − Tc,in = 95 − 10 = 85 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (141.1 − 85)/ln(141.1/85) = 110.7 K

Area

A = Q̇/(U·ΔTlm) = 74750/(300·110.7) = 2.251 m²

Answer

A = 2.251 m²

ExamProblems · examproblems.com/courses/heat-transfer