Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Gypsum board, k = 0.1750 mmBrick, k = 0.7250 mm24 °C6 °CQ̇ = ?

A wall is made of 50 mm of gypsum board and 50 mm of brick, with an area of 6 m². The outer faces are at 24 °C and 6 °C. Find the heat flow Q̇ through the wall.

L1 = 50 mm, k1 = 0.17 W/(m·K)L2 = 50 mm, k2 = 0.72 W/(m·K)A = 6 m²T1 = 24 °CT3 = 6 °C
Q̇ = W
2.Heat conductionHard
Concrete, k = 1.4100 mmMineral wool, k = 0.0475 mmroom 20 °Coutside 5 °CQ̇ = ?

A wall of 100 mm concrete and 75 mm mineral wool separates a room at 20 °C from outside air at 5 °C. The convection coefficients are 8 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 10 m². Find the heat loss Q̇ through the wall.

L1 = 100 mm, k1 = 1.4 W/(m·K)L2 = 75 mm, k2 = 0.04 W/(m·K)A = 10 m²hi = 8 W/(m²·K)ho = 25 W/(m²·K)Troom = 20 °CTout = 5 °C
Q̇ = W
3.Heat exchangers (LMTD)Medium
lengthT90 °C65 °C70 °C30 °CΔT₁ΔT₂counter-flow

A counter-flow heat exchanger transfers 150 kW. The hot fluid cools from 90 to 65 °C and the cold fluid heats from 30 to 70 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 150 kWU = 800 W/(m²·K)Th: 90 → 65 °CTc: 30 → 70 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT140 °C75 °C?15 °CΔT₁ΔT₂counter-flow

In a counter-flow double-pipe heat exchanger, hot oil (0.5 kg/s, cp = 2.3 kJ/(kg·K)) flows in the inner tube and cools from 140 to 75 °C. Water (0.8 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 15 °C. The inner tube has a diameter of 40 mm, and U = 250 W/(m²·K) is based on this diameter. Find the tube length L needed.

ṁh = 0.5 kg/scp,h = 2.3 kJ/(kg·K)Th: 140 → 75 °Cṁc = 0.8 kg/sTc,in = 15 °CD = 40 mmU = 250 W/(m²·K)
L = m

3Solutions

1.Heat conduction

Answer: Q̇ = 297.1 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (50/1000)/(0.17·6) = 0.04902 K/W
R2 = L2/(k2A) = (50/1000)/(0.72·6) = 0.01157 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 18/0.06059 = 297.1 W

Answer

Q̇ = 297.1 W
2.Heat conduction

Answer: Q̇ = 71.04 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(8·10) = 0.0125 K/W
R1 = L1/(k1A) = (100/1000)/(1.4·10) = 0.007143 K/W
R2 = L2/(k2A) = (75/1000)/(0.04·10) = 0.1875 K/W
Ro = 1/(hoA) = 1/(25·10) = 0.004 K/W
ΣR = 0.2111 K/W

Heat loss

Q̇ = (20 − (5))/0.2111 = 71.04 W

Answer

Q̇ = 71.04 W
3.Heat exchangers (LMTD)

Answer: A = 6.995 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 90 − 70 = 20 K
ΔT₂ = Th,out − Tc,in = 65 − 30 = 35 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (20 − 35)/ln(20/35) = 26.8 K

Area

A = Q̇/(U·ΔTlm) = 150000/(800·26.8) = 6.995 m²

Answer

A = 6.995 m²
4.Heat exchangers (LMTD)

Answer: L = 29.96 m

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = 0.5·2.3·(140 − 75) = 74.75 kW
Tc,out = 15 + 74.75/(0.8·4.18) = 37.35 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 140 − 37.35 = 102.6 K
ΔT₂ = Th,out − Tc,in = 75 − 15 = 60 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (102.6 − 60)/ln(102.6/60) = 79.42 K

Area and length

A = 74750/(250·79.42) = 3.765 m²
L = A/(πD) = 3.765/(π·0.04) = 29.96 m

Answer

L = 29.96 m

ExamProblems · examproblems.com/courses/heat-transfer