1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Wood, k = 0.17100 mmMineral wool, k = 0.0425 mm15 °C0 °CQ̇ = ?

A wall is made of 100 mm of wood and 25 mm of mineral wool, with an area of 10 m². The outer faces are at 15 °C and 0 °C. Find the heat flow Q̇ through the wall.

L1 = 100 mm, k1 = 0.17 W/(m·K)L2 = 25 mm, k2 = 0.04 W/(m·K)A = 10 m²T1 = 15 °CT3 = 0 °C
Q̇ = W
2.Heat conductionHard
Brick, k = 0.72100 mmWood, k = 0.17100 mmroom 22 °Coutside -12 °CTs​ = ?Q̇

A wall of 100 mm brick and 100 mm wood separates a room at 22 °C from outside air at -12 °C. The convection coefficients are 6 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 6 m². Find the temperature Ts of the inside surface of the wall.

L1 = 100 mm, k1 = 0.72 W/(m·K)L2 = 100 mm, k2 = 0.17 W/(m·K)A = 6 m²hi = 6 W/(m²·K)ho = 20 W/(m²·K)Troom = 22 °CTout = -12 °C
Ts = °C
3.Heat exchangers (LMTD)Medium
lengthT180 °C165 °C45 °C15 °CΔT₁ΔT₂counter-flow

A counter-flow heat exchanger transfers 180 kW. The hot fluid cools from 180 to 165 °C and the cold fluid heats from 15 to 45 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 180 kWU = 800 W/(m²·K)Th: 180 → 165 °CTc: 15 → 45 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT120 °C20 °C?ΔT₁ΔT₂condensing steam

Steam condenses at a constant 120 °C on the outside of the tubes of a condenser with a heat transfer area of 4 m² and U = 2000 W/(m²·K). Cooling water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 20 °C. Find the water outlet temperature Tc,out.

Ts = 120 °CA = 4 m²U = 2000 W/(m²·K)ṁ = 1.5 kg/scp = 4.18 kJ/(kg·K)Tc,in = 20 °C
Tc,out = °C

3Solutions

1.Heat conduction

Answer: Q̇ = 123.6 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (100/1000)/(0.17·10) = 0.05882 K/W
R2 = L2/(k2A) = (25/1000)/(0.04·10) = 0.0625 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 15/0.1213 = 123.6 W

Answer

Q̇ = 123.6 W
2.Heat conduction

Answer: Ts = 16 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(6·6) = 0.02778 K/W
R1 = L1/(k1A) = (100/1000)/(0.72·6) = 0.02315 K/W
R2 = L2/(k2A) = (100/1000)/(0.17·6) = 0.09804 K/W
Ro = 1/(hoA) = 1/(20·6) = 0.008333 K/W
ΣR = 0.1573 K/W

Heat loss

Q̇ = (22 − (-12))/0.1573 = 216.1 W
Ts = Troom − Q̇·Ri = 22 − 216.1·0.02778 = 16 °C

Answer

Ts = 16 °C
3.Heat exchangers (LMTD)

Answer: A = 1.58 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 180 − 45 = 135 K
ΔT₂ = Th,out − Tc,in = 165 − 15 = 150 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (135 − 150)/ln(135/150) = 142.4 K

Area

A = Q̇/(U·ΔTlm) = 180000/(800·142.4) = 1.58 m²

Answer

A = 1.58 m²
4.Heat exchangers (LMTD)

Answer: Tc,out = 92.08 °C

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Combine the energy balance and the rate equation

With ΔT₁ = Ts − Tc,in and ΔT₂ = Ts − Tc,out, the difference ΔT₁ − ΔT₂ equals the water temperature rise, so the rise cancels.

ṁcp(ΔT₁ − ΔT₂) = U·A·(ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂)
ln(ΔT₁/ΔT₂) = U·A/(ṁcp) = 2000·4/(1.5·4180) = 1.276

Outlet temperature

ΔT₂ = ΔT₁·e−1.276 = 100·0.2792 = 27.92 K
Tc,out = 120 − 27.92 = 92.08 °C

Answer

Tc,out = 92.08 °C

Heat transferred: Q̇ = 452 kW.