Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Brick, k = 0.72200 mmConcrete, k = 1.4100 mm24 °C-7 °CTi​ = ?Q̇

A wall is made of 200 mm of brick and 100 mm of concrete, with an area of 12 m². The outer faces are at 24 °C and -7 °C. Find the temperature Ti at the interface between the two layers.

L1 = 200 mm, k1 = 0.72 W/(m·K)L2 = 100 mm, k2 = 1.4 W/(m·K)A = 12 m²T1 = 24 °CT3 = -7 °C
Ti = °C
2.Heat conductionHard
Gypsum board, k = 0.17250 mmWood, k = 0.17100 mmroom 22 °Coutside -15 °CQ̇ = ?

A wall of 250 mm gypsum board and 100 mm wood separates a room at 22 °C from outside air at -15 °C. The convection coefficients are 10 W/(m²·K) inside and 30 W/(m²·K) outside, and the wall area is 10 m². Find the heat loss Q̇ through the wall.

L1 = 250 mm, k1 = 0.17 W/(m·K)L2 = 100 mm, k2 = 0.17 W/(m·K)A = 10 m²hi = 10 W/(m²·K)ho = 30 W/(m²·K)Troom = 22 °CTout = -15 °C
Q̇ = W
3.Heat exchangers (LMTD)Medium
lengthT180 °C25 °C65 °C10 °CΔT₁ΔT₂counter-flow

A counter-flow heat exchanger transfers 40 kW. The hot fluid cools from 180 to 25 °C and the cold fluid heats from 10 to 65 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 40 kWU = 300 W/(m²·K)Th: 180 → 25 °CTc: 10 → 65 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT165 °C??10 °CΔT₁ΔT₂counter-flow

In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 4 kW/K. The hot stream enters at 165 °C and the cold stream at 10 °C. The exchanger has A = 6 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.

Ch = Cc = 4 kW/KTh,in = 165 °CTc,in = 10 °CA = 6 m²U = 500 W/(m²·K)
Th,out = °C

3Solutions

1.Heat conduction

Answer: Ti = −0.6591 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (200/1000)/(0.72·12) = 0.02315 K/W
R2 = L2/(k2A) = (100/1000)/(1.4·12) = 0.005952 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 31/0.0291 = 1065 W

Interface temperature

The temperature drops across the first layer by Q̇·R₁.

Ti = T1 − Q̇·R1 = 24 − 1065·0.02315 = −0.6591 °C

Answer

Ti = −0.6591 °C
2.Heat conduction

Answer: Q̇ = 168.8 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(10·10) = 0.01 K/W
R1 = L1/(k1A) = (250/1000)/(0.17·10) = 0.1471 K/W
R2 = L2/(k2A) = (100/1000)/(0.17·10) = 0.05882 K/W
Ro = 1/(hoA) = 1/(30·10) = 0.003333 K/W
ΣR = 0.2192 K/W

Heat loss

Q̇ = (22 − (-15))/0.2192 = 168.8 W

Answer

Q̇ = 168.8 W
3.Heat exchangers (LMTD)

Answer: A = 2.716 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 180 − 65 = 115 K
ΔT₂ = Th,out − Tc,in = 25 − 10 = 15 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (115 − 15)/ln(115/15) = 49.09 K

Area

A = Q̇/(U·ΔTlm) = 40000/(300·49.09) = 2.716 m²

Answer

A = 2.716 m²
4.Heat exchangers (LMTD)

Answer: Th,out = 98.57 °C

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Constant temperature difference

The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.

ΔTlm = Th,out − Tc,in

Energy balance equals rate equation

4·(165 − Th,out) = 3·(Th,out − 10)
Th,out = (4·165 + 3·10)/(4 + 3) = 98.57 °C

Answer

Th,out = 98.57 °C

Heat transferred: Q̇ = 265.7 kW; the cold stream leaves at 76.43 °C.

ExamProblems · examproblems.com/courses/heat-transfer