A DC motor (k = 0.75 V·s/rad, Ra = 1 Ω) runs from 220 V. At full load it draws 25 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.
V = 220 Vk = 0.75 V·s/radRa = 1 ΩIFL = 25 A
SR = %
4.DC motorsHard
A DC motor (k = 0.6 V·s/rad, Ra = 0.4 Ω) on a fixed 240 V supply drives a load of 18 N·m. Find the series resistance Rs that slows it down to 600 rpm.
A single-phase motor takes 7 kW at a power factor of 0.6 lagging from a 230 V supply. Find the line current I.
P = 7 kWpf = 0.6V = 230 V
I = A
6.AC power & power factorHard
A 100 V (rms), 60 Hz source has an internal impedance Zs = 50 + j15 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Vs = 100 V (rms)f = 60 HzZs = 50 + j15 Ω
C = µF
7.Three-phase powerMedium
A balanced Y-connected load with an impedance of 3 + j4 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.
VL = 415 VZ = 3 + j4 Ω per phase
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 300 kW at a power factor of 0.65 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 300 kWpf1 = 0.65pf2 = 0.92VL = 480 Vf = 60 Hz
QC = kvar
3Solutions
1.DC-DC converters
Answer: IL = 9.6 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 1 − 15/60 = 0.75
Load current
Io = 60/25 = 2.4 A
Inductor current
IL = Io/(1 − D) = 2.4/0.25 = 9.6 A
Answer
IL = 9.6 A
2.DC-DC converters
Answer: C = 19.09 µF
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 8.4/12 = 0.7
Inductor ripple current
ΔIL = (12 − 8.4)·0.7/(330·10⁻⁶·50·10³) = 0.1527 A
Capacitance
C = 0.1527/(8·50·10³·20·10⁻³) = 19.09 µF
Answer
C = 19.09 µF
3.DC motors
Answer: SR = 12.82 %
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load and full-load speed
n₀ = 60·220/(2π·0.75) = 2801 rpm
nFL = 60·(220 − 25·1)/(2π·0.75) = 2483 rpm
Speed regulation
SR = (2801 − 2483)/2483·100 = 12.82 %
Answer
SR = 12.82 %
4.DC motors
Answer: Rs = 6.343 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Current and back-EMF
Ia = 18/0.6 = 30 A
E = 0.6·62.83 = 37.7 V
Series resistance
Ra + Rs = (240 − 37.7)/30 = 6.743 Ω
Rs = 6.343 Ω
Answer
Rs = 6.343 Ω
The resistor wastes 5709 W; a chopper controls the speed with far less loss.
5.AC power & power factor
Answer: I = 50.72 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 7000/(230·0.6) = 50.72 A
Answer
I = 50.72 A
6.AC power & power factor
Answer: C = 176.8 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Conjugate match
The load reactance cancels the source reactance, and the load resistance equals the source resistance.
ZL = Zs* = 50 − j15 Ω
Capacitance
XC = 15 Ω → C = 1/(2π·60·15) = 176.8 µF
Answer
C = 176.8 µF
7.Three-phase power
Answer: P = 20.67 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Phase voltage
Vph = 415/√3 = 239.6 V
Phase current
|Z| = √(3² + 4²) = 5 Ω
Iph = 239.6/5 = 47.92 A
Total real power
Only the resistive part of each impedance absorbs real power.
P = 3·Iph²·R = 3·47.92²·3 = 20.67 kW
Answer
P = 20.67 kW
Check: cos φ = R/|Z| = 0.6, and √3·VL·IL·cos φ gives the same power.
8.Three-phase power
Answer: QC = 222.9 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.