An ideal buck converter turns 15 V into 9 V for an 8 Ω load at 50 kHz. Find the smallest inductance Lcrit for continuous conduction.
Vin = 15 VVo = 9 Vf = 50 kHzR = 8 Ω
Lcrit = µH
3.DC motorsMedium
A DC motor with k = 0.6 V·s/rad runs from 220 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.
V = 220 Vk = 0.6 V·s/rad
n0 = rpm
4.DC motorsHard
A separately excited DC motor (k = 0.2 V·s/rad at full field, Ra = 1.5 Ω, V = 48 V) drives a constant load torque of 0.4 N·m. The field flux is reduced to 90 % of its full value. Find the new speed n.
A single-phase motor takes 24 kW at a power factor of 0.85 lagging from a 400 V supply. Find the line current I.
P = 24 kWpf = 0.85V = 400 V
I = A
6.AC power & power factorHard
A single-phase load takes 15 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
P = 15 kWpf1 = 0.75pf2 = 0.98V = 240 Vf = 60 Hz
C = µF
7.Three-phase powerMedium
A balanced Δ-connected load with an impedance of 6 + j8 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 480 V. Find the total real power P absorbed by the load in kW.
VL = 480 VZ = 6 + j8 Ω per phase
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 150 kW at a power factor of 0.65 lagging from a 400 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
P = 150 kWpf1 = 0.65pf2 = 0.98VL = 400 Vf = 50 Hz
Cph = µF
3Solutions
1.DC-DC converters
Answer: Imax = 7.855 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 28.8/48 = 0.6
Average and ripple current
Io = 28.8/4 = 7.2 A
ΔIL = VL·D/(L·f) = 19.2·0.6/(220·10⁻⁶·40·10³) = 1.309 A
Peak current
Imax = 7.2 + 1.309/2 = 7.855 A
Answer
Imax = 7.855 A
2.DC-DC converters
Answer: Lcrit = 32 µH
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 9/15 = 0.6
Boundary condition
Set the average inductor current equal to half the ripple current and solve for L.
Lcrit = (1 − D)·R/(2f)
Critical inductance
Lcrit = (1 − 0.6)·8/(250·10³) = 32 µH
Answer
Lcrit = 32 µH
3.DC motors
Answer: n0 = 3501 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load speed
ω₀ = V/k = 220/0.6 = 366.7 rad/s
n0 = 60·366.7/(2π) = 3501 rpm
Answer
n0 = 3501 rpm
4.DC motors
Answer: n = 2370 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Field weakening is how a DC drive runs above its base speed.
5.AC power & power factor
Answer: I = 70.59 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 24000/(400·0.85) = 70.59 A
Answer
I = 70.59 A
6.AC power & power factor
Answer: C = 468.9 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 15·tan(41.41°) = 13.23 kvar
Q2 = P·tan φ2 = 15·tan(11.48°) = 3.046 kvar
QC = Q1 − Q2 = 10.18 kvar
Capacitance
A capacitor across the supply delivers Q = V²·ωC.
C = QC/(2πf·V²) = 10183/(2π·60·240²) = 468.9 µF
Answer
C = 468.9 µF
7.Three-phase power
Answer: P = 41.47 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Phase voltage
Vph = VL = 480 V
Phase current
|Z| = √(6² + 8²) = 10 Ω
Iph = 480/10 = 48 A
Total real power
Only the resistive part of each impedance absorbs real power.
P = 3·Iph²·R = 3·48²·6 = 41.47 kW
Answer
P = 41.47 kW
Check: cos φ = R/|Z| = 0.6, and √3·VL·IL·cos φ gives the same power.
8.Three-phase power
Answer: Cph = 2883 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 150·tan(acos 0.65) = 150·1.169 = 175.4 kvar
Q2 = 150·tan(acos 0.98) = 150·0.2031 = 30.46 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 144.9 kvar
Capacitance per phase
In a Y bank each capacitor is connected between a line and the star point.