A DC motor with k = 0.12 V·s/rad runs from 48 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.
V = 48 Vk = 0.12 V·s/rad
n0 = rpm
4.DC motorsHard
A DC motor with k = 0.08 V·s/rad and Ra = 0.5 Ω must drive a load of 0.4 N·m at 1200 rpm. Find the armature voltage V it needs.
k = 0.08 V·s/radRa = 0.5 ΩT = 0.4 N·mn = 1200 rpm
V = V
5.AC power & power factorMedium
A single-phase motor takes 29 kW at a power factor of 0.8 lagging from a 400 V supply. Find the reactive power Q it draws.
P = 29 kWpf = 0.8V = 400 V
Q = kvar
6.AC power & power factorHard
A single-phase load takes 15 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
P = 15 kWpf1 = 0.7pf2 = 0.9V = 230 Vf = 50 Hz
Inew = A
7.Three-phase powerMedium
A balanced Y-connected load with an impedance of 20 + j15 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.
VL = 415 VZ = 20 + j15 Ω per phase
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 100 kW at a power factor of 0.72 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 100 kWpf1 = 0.72pf2 = 0.9VL = 690 Vf = 60 Hz
QC = kvar
3Solutions
1.DC-DC converters
Answer: IL = 1.067 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 1 − 15/20 = 0.25
Load current
Io = 20/25 = 0.8 A
Inductor current
IL = Io/(1 − D) = 0.8/0.75 = 1.067 A
Answer
IL = 1.067 A
2.DC-DC converters
Answer: C = 16.8 µF
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 14.4/48 = 0.3
Inductor ripple current
ΔIL = (48 − 14.4)·0.3/(150·10⁻⁶·100·10³) = 0.672 A
Capacitance
C = 0.672/(8·100·10³·50·10⁻³) = 16.8 µF
Answer
C = 16.8 µF
3.DC motors
Answer: n0 = 3820 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load speed
ω₀ = V/k = 48/0.12 = 400 rad/s
n0 = 60·400/(2π) = 3820 rpm
Answer
n0 = 3820 rpm
4.DC motors
Answer: V = 12.55 V
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Back-EMF
E = 0.08·125.7 = 10.05 V
Armature current
Ia = 0.4/0.08 = 5 A
Armature voltage
V = 10.05 + 5·0.5 = 12.55 V
Answer
V = 12.55 V
5.AC power & power factor
Answer: Q = 21.75 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Angle
φ = arccos(0.8) = 36.87°, tan φ = 0.75
Reactive power
Q = P·tan φ = 29·0.75 = 21.75 kvar
Answer
Q = 21.75 kvar
6.AC power & power factor
Answer: Inew = 72.46 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 15·tan(45.57°) = 15.3 kvar
Q2 = P·tan φ2 = 15·tan(25.84°) = 7.265 kvar
QC = Q1 − Q2 = 8.038 kvar
New line current
Inew = P/(V·cos φ2) = 15000/(230·0.9) = 72.46 A
Answer
Inew = 72.46 A
7.Three-phase power
Answer: P = 5.511 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Phase voltage
Vph = 415/√3 = 239.6 V
Phase current
|Z| = √(20² + 15²) = 25 Ω
Iph = 239.6/25 = 9.584 A
Total real power
Only the resistive part of each impedance absorbs real power.
P = 3·Iph²·R = 3·9.584²·20 = 5.511 kW
Answer
P = 5.511 kW
Check: cos φ = R/|Z| = 0.8, and √3·VL·IL·cos φ gives the same power.
8.Three-phase power
Answer: QC = 47.95 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.