A load with impedance Z = 15 + j20 Ω is connected to a 240 V (rms) single-phase supply. Find the apparent power S.
V = 240 VZ = 15 + j20 Ω
S = VA
6.AC power & power factorHard
A single-phase load takes 15 kW at a power factor of 0.75 lagging from a 240 V, 50 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new line current I.
P = 15 kWpf1 = 0.75V = 240 Vf = 50 HzC = 150 µF
I = A
7.Three-phase powerMedium
A balanced three-phase load draws a line current of 120 A from a supply with a line-to-line voltage of 690 V. The power factor is 0.75 lagging. Find the total real power P drawn by the load in kW.
VL = 690 VIL = 120 Acos φ = 0.75
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 120 kW at a power factor of 0.7 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 120 kWpf1 = 0.7pf2 = 0.9VL = 480 Vf = 50 Hz
QC = kvar
3Solutions
1.DC-DC converters
Answer: IL = 96 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 1 − 48/192 = 0.75
Load current
Io = 192/8 = 24 A
Inductor current
IL = Io/(1 − D) = 24/0.25 = 96 A
Answer
IL = 96 A
2.DC-DC converters
Answer: Lcrit = 20 µH
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 9/15 = 0.6
Boundary condition
Set the average inductor current equal to half the ripple current and solve for L.
Lcrit = (1 − D)·R/(2f)
Critical inductance
Lcrit = (1 − 0.6)·25/(2250·10³) = 20 µH
Answer
Lcrit = 20 µH
3.DC motors
Answer: n = 1738 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Armature current
Ia = T/k = 1.25/0.25 = 5 A
Back-EMF and speed
E = 48 − 5·0.5 = 45.5 V
ω = E/k = 182 rad/s → n = 1738 rpm
Answer
n = 1738 rpm
4.DC motors
Answer: Rs = 12.45 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Current and back-EMF
Ia = 8/0.8 = 10 A
E = 0.8·125.7 = 100.5 V
Series resistance
Ra + Rs = (240 − 100.5)/10 = 13.95 Ω
Rs = 12.45 Ω
Answer
Rs = 12.45 Ω
The resistor wastes 1245 W; a chopper controls the speed with far less loss.
5.AC power & power factor
Answer: S = 2304 VA
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Current
|Z| = √(15² + 20²) = 25 Ω
I = V/|Z| = 240/25 = 9.6 A
Apparent power
S = V·I = 240·9.6 = 2304 VA
Answer
S = 2304 VA
6.AC power & power factor
Answer: I = 76.33 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = 15·tan(arccos 0.75) = 13.23 kvar
QC = V²·2πf·C = 240²·2π·50·150·10⁻⁶ = 2714 var = 2.714 kvar
Q2 = 13.23 − 2.714 = 10.51 kvar
New apparent power
S2 = √(15² + 10.51²) = 18.32 kVA
New line current
I = S2/V = 18318/240 = 76.33 A
Answer
I = 76.33 A
7.Three-phase power
Answer: P = 107.6 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·690·120 = 143.4 kVA
Real power
P = S·cos φ = 143.4·0.75 = 107.6 kW
Answer
P = 107.6 kW
8.Three-phase power
Answer: QC = 64.31 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.