An inductive load takes 2.5 A and 403 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
V = 230 VI = 2.5 AP = 403 W
R = Ω
6.AC power & power factorHard
A 200 kVA single-phase transformer supplies a load of 103 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Smax = 200 kVAP1 = 103 kWpf1 = 0.8
ΔP = kW
7.Three-phase powerMedium
A balanced three-phase load draws a line current of 10 A from a supply with a line-to-line voltage of 415 V. The power factor is 0.95 lagging. Find the total real power P drawn by the load in kW.
VL = 415 VIL = 10 Acos φ = 0.95
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 80 kW at a power factor of 0.8 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 80 kWpf1 = 0.8pf2 = 0.9VL = 480 Vf = 50 Hz
QC = kvar
3Solutions
1.DC-DC converters
Answer: ΔIL = 0.1964 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 5.4/9 = 0.6
Inductor voltage during the on-time
While S is on, the inductor sits between Vin and Vo.
VL = 9 − 5.4 = 3.6 V
Ripple current
ΔIL = VL·D/(L·f) = 3.6·0.6/(220·10⁻⁶·50·10³) = 0.1964 A
Answer
ΔIL = 0.1964 A
2.DC-DC converters
Answer: Lcrit = 9 µH
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 10.5/15 = 0.7
Boundary condition
Set the average inductor current equal to half the ripple current and solve for L.
Lcrit = (1 − D)·R/(2f)
Critical inductance
Lcrit = (1 − 0.7)·12/(2200·10³) = 9 µH
Answer
Lcrit = 9 µH
3.DC motors
Answer: n0 = 1050 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load speed
ω₀ = V/k = 220/2 = 110 rad/s
n0 = 60·110/(2π) = 1050 rpm
Answer
n0 = 1050 rpm
4.DC motors
Answer: Rs = 17.12 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Current and back-EMF
Ia = 3.2/0.8 = 4 A
E = 0.8·41.89 = 33.51 V
Series resistance
Ra + Rs = (110 − 33.51)/4 = 19.12 Ω
Rs = 17.12 Ω
Answer
Rs = 17.12 Ω
The resistor wastes 274 W; a chopper controls the speed with far less loss.
5.AC power & power factor
Answer: R = 64.48 Ω
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Resistance from the real power
R = P/I² = 403/2.5² = 64.48 Ω
Answer
R = 64.48 Ω
6.AC power & power factor
Answer: ΔP = 81.48 kW
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of the existing load
Q1 = 103·tan(arccos 0.8) = 77.25 kvar
Largest total real power
At full rating S = Smax, and Q is unchanged by the resistive load.
P = √(Smax² − Q1²) = √(200² − 77.25²) = 184.5 kW
Extra real power
ΔP = 184.5 − 103 = 81.48 kW
Answer
ΔP = 81.48 kW
7.Three-phase power
Answer: P = 6.829 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·415·10 = 7.188 kVA
Real power
P = S·cos φ = 7.188·0.95 = 6.829 kW
Answer
P = 6.829 kW
8.Three-phase power
Answer: QC = 21.25 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.