An ideal boost converter turns 36 V into 120 V for a 25 Ω load at 100 kHz. Find the smallest inductance Lcrit for continuous conduction.
Vin = 36 VVo = 120 Vf = 100 kHzR = 25 Ω
Lcrit = µH
3.DC motorsMedium
A DC motor delivers 0.75 kW of mechanical power at 3000 rpm. Find the shaft torque T.
P = 0.75 kWn = 3000 rpm
T = N·m
4.DC motorsHard
A separately excited DC motor on 110 V (Ra = 1.5 Ω) runs at 1000 rpm with an armature current of 6 A. The load changes and the current becomes 1.5 A, with the field unchanged. Find the new speed n2.
V = 110 VRa = 1.5 Ωn1 = 1000 rpmIa1 = 6 AIa2 = 1.5 A
n2 = rpm
5.AC power & power factorMedium
Two loads are connected in parallel to a 230 V single-phase supply: a 5 kW load at a power factor of 0.6 lagging and a 25 kW load at a power factor of 0.8 lagging. Find the total current I drawn from the supply.
A single-phase load takes 11 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
P = 11 kWpf1 = 0.65V = 400 Vf = 50 HzC = 220 µF
cos φ =
7.Three-phase powerMedium
A balanced three-phase load draws a line current of 25 A from a supply with a line-to-line voltage of 480 V. The power factor is 0.9 lagging. Find the total real power P drawn by the load in kW.
VL = 480 VIL = 25 Acos φ = 0.9
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 250 kW at a power factor of 0.78 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
P = 250 kWpf1 = 0.78pf2 = 0.92VL = 690 Vf = 60 Hz
Cph = µF
3Solutions
1.DC-DC converters
Answer: Imax = 0.624 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 4.8/12 = 0.4
Average and ripple current
Io = 4.8/10 = 0.48 A
ΔIL = VL·D/(L·f) = 7.2·0.4/(100·10⁻⁶·100·10³) = 0.288 A
Peak current
Imax = 0.48 + 0.288/2 = 0.624 A
Answer
Imax = 0.624 A
2.DC-DC converters
Answer: Lcrit = 7.875 µH
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 1 − 36/120 = 0.7
Boundary condition
Set the average inductor current equal to half the ripple current and solve for L.
Lcrit = D(1 − D)²·R/(2f)
Critical inductance
Lcrit = 0.7(1 − 0.7)²·25/(2100·10³) = 7.875 µH
Answer
Lcrit = 7.875 µH
3.DC motors
Answer: T = 2.387 N·m
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Speed in rad/s
ω = 2π·3000/60 = 314.2 rad/s
Torque
T = P/ω = 750/314.2 = 2.387 N·m
Answer
T = 2.387 N·m
4.DC motors
Answer: n2 = 1067 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Back-EMF before and after
E1 = 110 − 6·1.5 = 101 V
E2 = 110 − 1.5·1.5 = 107.8 V
New speed
n2 = 1000·107.8/101 = 1067 rpm
Answer
n2 = 1067 rpm
5.AC power & power factor
Answer: I = 171 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of each load
A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).
Q1 = 5·tan(arccos 0.6) = 6.667 kvar
Q2 = 25·tan(arccos 0.8) = 18.75 kvar
Totals
P = 5 + 25 = 30 kW
Q = 6.667 + 18.75 = 25.42 kvar
S = √(30² + 25.42²) = 39.32 kVA
Total current
I = S/V = 39319/230 = 171 A
Answer
I = 171 A
6.AC power & power factor
Answer: cos φ = 0.9868
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = 11·tan(arccos 0.65) = 12.86 kvar
QC = V²·2πf·C = 400²·2π·50·220·10⁻⁶ = 11058 var = 11.06 kvar
Q2 = 12.86 − 11.06 = 1.802 kvar
New apparent power
S2 = √(11² + 1.802²) = 11.15 kVA
New power factor
cos φ = P/S2 = 11/11.15 = 0.9868
Answer
cos φ = 0.9868
7.Three-phase power
Answer: P = 18.71 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·480·25 = 20.78 kVA
Real power
P = S·cos φ = 20.78·0.9 = 18.71 kW
Answer
P = 18.71 kW
8.Three-phase power
Answer: Cph = 524.1 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 250·tan(acos 0.78) = 250·0.8023 = 200.6 kvar
Q2 = 250·tan(acos 0.92) = 250·0.426 = 106.5 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 94.07 kvar
Capacitance per phase
In a Y bank each capacitor is connected between a line and the star point.