A single-phase motor takes 31 kW at a power factor of 0.75 lagging from a 230 V supply. Find the reactive power Q it draws.
P = 31 kWpf = 0.75V = 230 V
Q = kvar
6.AC power & power factorHard
A single-phase load takes 26 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
P = 26 kWpf1 = 0.7V = 230 Vf = 50 HzC = 220 µF
cos φ =
7.Three-phase powerMedium
A three-phase induction motor delivers 55 kW of mechanical output power at full load. At this load its efficiency is 91% and its power factor is 0.85 lagging. The supply has a line-to-line voltage of 415 V. Find the line current IL.
Pout = 55 kWη = 91%cos φ = 0.85VL = 415 V
IL = A
8.Three-phase powerHard
A balanced three-phase load takes 150 kW at a power factor of 0.75 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 150 kWpf1 = 0.75pf2 = 0.95VL = 415 Vf = 50 Hz
QC = kvar
3Solutions
1.DC-DC converters
Answer: ΔIL = 0.84 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 84/(36 + 84) = 0.7
Inductor voltage during the on-time
While S is on, the inductor sits directly across Vin.
VL = 36 V
Ripple current
ΔIL = VL·D/(L·f) = 36·0.7/(150·10⁻⁶·200·10³) = 0.84 A
Answer
ΔIL = 0.84 A
2.DC-DC converters
Answer: Io,min = 0.045 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 18/24 = 0.75
Ripple current
ΔIL = 18·0.25/(100·10⁻⁶·500·10³) = 0.09 A
Boundary load current
Io,min = ΔIL/2 = 0.045 A
Answer
Io,min = 0.045 A
Below this current the converter enters discontinuous conduction and Vo rises above D·Vin.
3.DC motors
Answer: n0 = 1401 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load speed
ω₀ = V/k = 220/1.5 = 146.7 rad/s
n0 = 60·146.7/(2π) = 1401 rpm
Answer
n0 = 1401 rpm
4.DC motors
Answer: Rs = 18.45 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Current and back-EMF
Ia = 8/1 = 8 A
E = 1·62.83 = 62.83 V
Series resistance
Ra + Rs = (220 − 62.83)/8 = 19.65 Ω
Rs = 18.45 Ω
Answer
Rs = 18.45 Ω
The resistor wastes 1181 W; a chopper controls the speed with far less loss.
5.AC power & power factor
Answer: Q = 27.34 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Angle
φ = arccos(0.75) = 41.41°, tan φ = 0.8819
Reactive power
Q = P·tan φ = 31·0.8819 = 27.34 kvar
Answer
Q = 27.34 kvar
6.AC power & power factor
Answer: cos φ = 0.7509
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = 26·tan(arccos 0.7) = 26.53 kvar
QC = V²·2πf·C = 230²·2π·50·220·10⁻⁶ = 3656 var = 3.656 kvar
Q2 = 26.53 − 3.656 = 22.87 kvar
New apparent power
S2 = √(26² + 22.87²) = 34.63 kVA
New power factor
cos φ = P/S2 = 26/34.63 = 0.7509
Answer
cos φ = 0.7509
7.Three-phase power
Answer: IL = 98.92 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 55/0.91 = 60.44 kW
Line current
IL = Pin/(√3·VL·cos φ) = 60440/(√3·415·0.85) = 98.92 A
Answer
IL = 98.92 A
8.Three-phase power
Answer: QC = 82.98 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.