A DC motor (k = 0.5 V·s/rad, Ra = 1.5 Ω) runs from 110 V. At full load it draws 6 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.
V = 110 Vk = 0.5 V·s/radRa = 1.5 ΩIFL = 6 A
SR = %
4.DC motorsHard
A 110 V DC motor has an armature resistance of 1 Ω. Find the series starting resistance Rst that limits the starting current to 60 A.
V = 110 VRa = 1 ΩImax = 60 A
Rst = Ω
5.AC power & power factorMedium
A single-phase motor takes 26 kW at a power factor of 0.85 lagging from a 400 V supply. Find the reactive power Q it draws.
P = 26 kWpf = 0.85V = 400 V
Q = kvar
6.AC power & power factorHard
A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
P = 5 kWpf1 = 0.6pf2 = 0.95V = 230 Vf = 50 Hz
QC = kvar
7.Three-phase powerMedium
A balanced three-phase load draws a line current of 150 A from a supply with a line-to-line voltage of 208 V. The power factor is 0.92 lagging. Find the total real power P drawn by the load in kW.
VL = 208 VIL = 150 Acos φ = 0.92
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 150 kW at a power factor of 0.72 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 150 kWpf1 = 0.72pf2 = 0.95VL = 690 Vf = 60 Hz
Cph = µF
3Solutions
1.DC-DC converters
Answer: ΔIL = 0.6818 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 36/48 = 0.75
Inductor voltage during the on-time
While S is on, the inductor sits between Vin and Vo.
VL = 48 − 36 = 12 V
Ripple current
ΔIL = VL·D/(L·f) = 12·0.75/(330·10⁻⁶·40·10³) = 0.6818 A
Answer
ΔIL = 0.6818 A
2.DC-DC converters
Answer: ΔVo = 1.654 mV
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 4.5/9 = 0.5
Inductor ripple current
ΔIL = (9 − 4.5)·0.5/(68·10⁻⁶·500·10³) = 0.06618 A
Output ripple
ΔVo = 0.06618/(8·500·10³·10·10⁻⁶) = 1.654 mV
Answer
ΔVo = 1.654 mV
3.DC motors
Answer: SR = 8.911 %
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load and full-load speed
n₀ = 60·110/(2π·0.5) = 2101 rpm
nFL = 60·(110 − 6·1.5)/(2π·0.5) = 1929 rpm
Speed regulation
SR = (2101 − 1929)/1929·100 = 8.911 %
Answer
SR = 8.911 %
4.DC motors
Answer: Rst = 0.8333 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Total resistance
Ra + Rst = 110/60 = 1.833 Ω
Starting resistor
Rst = 1.833 − 1 = 0.8333 Ω
Answer
Rst = 0.8333 Ω
The resistor is cut out step by step as the motor speeds up and the back-EMF grows.
5.AC power & power factor
Answer: Q = 16.11 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Angle
φ = arccos(0.85) = 31.79°, tan φ = 0.6197
Reactive power
Q = P·tan φ = 26·0.6197 = 16.11 kvar
Answer
Q = 16.11 kvar
6.AC power & power factor
Answer: QC = 5.023 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 5·tan(53.13°) = 6.667 kvar
Q2 = P·tan φ2 = 5·tan(18.19°) = 1.643 kvar
QC = Q1 − Q2 = 5.023 kvar
Answer
QC = 5.023 kvar
7.Three-phase power
Answer: P = 49.72 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·208·150 = 54.04 kVA
Real power
P = S·cos φ = 54.04·0.92 = 49.72 kW
Answer
P = 49.72 kW
8.Three-phase power
Answer: Cph = 176.9 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 150·tan(acos 0.72) = 150·0.9639 = 144.6 kvar
Q2 = 150·tan(acos 0.95) = 150·0.3287 = 49.3 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 95.28 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.