An ideal boost converter turns 9 V into 36 V for a 5 Ω load at 25 kHz. The output capacitor is 470 µF. Find the peak-to-peak output voltage ripple ΔVo in mV.
Vin = 9 VVo = 36 Vf = 25 kHzC = 470 µFR = 5 Ω
ΔVo = mV
3.DC motorsMedium
A DC motor delivers 1.5 kW of mechanical power at 1450 rpm. Find the shaft torque T.
P = 1.5 kWn = 1450 rpm
T = N·m
4.DC motorsHard
A 220 V DC motor has an armature resistance of 0.8 Ω. Find the series starting resistance Rst that limits the starting current to 60 A.
V = 220 VRa = 0.8 ΩImax = 60 A
Rst = Ω
5.AC power & power factorMedium
Two loads are connected in parallel to a 400 V single-phase supply: a 5 kW load at a power factor of 0.85 lagging and a 25 kW load at a power factor of 0.9 leading. Find the total current I drawn from the supply.
V = 400 VP1 = 5 kW, pf1 = 0.85 laggingP2 = 25 kW, pf2 = 0.9 leading
I = A
6.AC power & power factorHard
A single-phase load takes 17 kW at a power factor of 0.65 lagging from a 400 V, 60 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
P = 17 kWpf1 = 0.65V = 400 Vf = 60 HzC = 220 µF
cos φ =
7.Three-phase powerMedium
A balanced three-phase load draws a line current of 50 A from a supply with a line-to-line voltage of 208 V. The power factor is 0.7 lagging. Find the total real power P drawn by the load in kW.
VL = 208 VIL = 50 Acos φ = 0.7
P = kW
8.Three-phase powerHard
A balanced three-phase load takes 150 kW at a power factor of 0.65 lagging from a 400 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 150 kWpf1 = 0.65pf2 = 0.92VL = 400 Vf = 50 Hz
Cph = µF
3Solutions
1.DC-DC converters
Answer: Imax = 0.8378 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 14.4/24 = 0.6
Average and ripple current
Io = 14.4/25 = 0.576 A
ΔIL = VL·D/(L·f) = 9.6·0.6/(220·10⁻⁶·50·10³) = 0.5236 A
Peak current
Imax = 0.576 + 0.5236/2 = 0.8378 A
Answer
Imax = 0.8378 A
2.DC-DC converters
Answer: ΔVo = 459.6 mV
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 1 − 9/36 = 0.75
Load current
Io = 36/5 = 7.2 A
Output ripple
ΔVo = 7.2·0.75/(25·10³·470·10⁻⁶) = 459.6 mV
Answer
ΔVo = 459.6 mV
3.DC motors
Answer: T = 9.879 N·m
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Speed in rad/s
ω = 2π·1450/60 = 151.8 rad/s
Torque
T = P/ω = 1500/151.8 = 9.879 N·m
Answer
T = 9.879 N·m
4.DC motors
Answer: Rst = 2.867 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Total resistance
Ra + Rst = 220/60 = 3.667 Ω
Starting resistor
Rst = 3.667 − 0.8 = 2.867 Ω
Answer
Rst = 2.867 Ω
The resistor is cut out step by step as the motor speeds up and the back-EMF grows.
5.AC power & power factor
Answer: I = 78.31 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of each load
A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).
Q1 = 5·tan(arccos 0.85) = 3.099 kvar
Q2 = −25·tan(arccos 0.9) = −12.11 kvar
Totals
P = 5 + 25 = 30 kW
Q = 3.099 + (−12.11) = −9.009 kvar
S = √(30² + (−9.009)²) = 31.32 kVA
Total current
I = S/V = 31324/400 = 78.31 A
Answer
I = 78.31 A
6.AC power & power factor
Answer: cos φ = 0.9321
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = 17·tan(arccos 0.65) = 19.88 kvar
QC = V²·2πf·C = 400²·2π·60·220·10⁻⁶ = 13270 var = 13.27 kvar
Q2 = 19.88 − 13.27 = 6.605 kvar
New apparent power
S2 = √(17² + 6.605²) = 18.24 kVA
New power factor
cos φ = P/S2 = 17/18.24 = 0.9321
Answer
cos φ = 0.9321
7.Three-phase power
Answer: P = 12.61 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·208·50 = 18.01 kVA
Real power
P = S·cos φ = 18.01·0.7 = 12.61 kW
Answer
P = 12.61 kW
8.Three-phase power
Answer: Cph = 739.2 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 150·tan(acos 0.65) = 150·1.169 = 175.4 kvar
Q2 = 150·tan(acos 0.92) = 150·0.426 = 63.9 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 111.5 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.