Identify the converter (buck, boost or buck-boost) and the duty cycle D from the voltage ratio.
Use volt-second balance on the inductor: the average inductor voltage over a period is zero.
Find the inductor voltage while the switch is on, then ΔIL = VL·D/(L·f).
For the output ripple, find the charge that flows in and out of the capacitor; for the CCM boundary, set the average inductor current equal to ΔIL/2.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
2Practice problems
1.DC-DC convertersMedium
An ideal boost converter turns 24 V into 60 V at 25 kHz with L = 330 µH. Find the peak-to-peak inductor ripple current ΔIL.
Vin = 24 VVo = 60 Vf = 25 kHzL = 330 µH
ΔIL = A
2.DC-DC convertersHard
An ideal buck-boost converter turns 48 V into −32 V for an 8 Ω load at 50 kHz. The output capacitor is 10 µF. Find the peak-to-peak output voltage ripple ΔVo in mV.
Vin = 48 VVo = −32 Vf = 50 kHzC = 10 µFR = 8 Ω
ΔVo = mV
3.DC motorsMedium
A DC motor (k = 0.4 V·s/rad, Ra = 1.5 Ω) runs from 120 V. At full load it draws 6 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.
V = 120 Vk = 0.4 V·s/radRa = 1.5 ΩIFL = 6 A
SR = %
4.DC motorsHard
A 48 V DC motor has an armature resistance of 1 Ω. Find the series starting resistance Rst that limits the starting current to 20 A.
V = 48 VRa = 1 ΩImax = 20 A
Rst = Ω
5.AC power & power factorMedium
Two loads are connected in parallel to a 400 V single-phase supply: a 4 kW load at a power factor of 0.85 lagging and a 4 kW load at a power factor of 0.8 lagging. Find the overall power factor cos φ seen by the supply.
A 120 V (rms), 1000 Hz source has an internal impedance Zs = 25 + j20 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Vs = 120 V (rms)f = 1000 HzZs = 25 + j20 Ω
C = µF
7.Three-phase powerMedium
A three-phase induction motor delivers 7.5 kW of mechanical output power at full load. At this load its efficiency is 91% and its power factor is 0.86 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.
Pout = 7.5 kWη = 91%cos φ = 0.86VL = 400 V
IL = A
8.Three-phase powerHard
A balanced three-phase load takes 200 kW at a power factor of 0.65 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 200 kWpf1 = 0.65pf2 = 0.9VL = 690 Vf = 60 Hz
Cph = µF
3Solutions
1.DC-DC converters
Answer: ΔIL = 1.745 A
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 1 − 24/60 = 0.6
Inductor voltage during the on-time
While S is on, the inductor sits directly across Vin.
VL = 24 V
Ripple current
ΔIL = VL·D/(L·f) = 24·0.6/(330·10⁻⁶·25·10³) = 1.745 A
Answer
ΔIL = 1.745 A
2.DC-DC converters
Answer: ΔVo = 3200 mV
DC-DC converters: a switch S turns on for the fraction D of each period T = 1/f. In steady state the average inductor voltage is zero (volt-second balance), which gives the ideal conversion ratios in continuous conduction: buck Vo = D·Vin, boost Vo = Vin/(1 − D), inverting buck-boost |Vo| = Vin·D/(1 − D). An ideal converter keeps the power: Vin·Iin = Vo·Io. While S is on the inductor current rises by ΔIL = VL·D·T/L, with VL = Vin − Vo for the buck and Vin for the boost and buck-boost. The output ripple is ΔVo = ΔIL/(8fC) for the buck and Io·D/(fC) for the boost and buck-boost. The inductor current just touches zero (the CCM boundary) when the average inductor current equals ΔIL/2.
Duty cycle
D = 32/(48 + 32) = 0.4
Load current
Io = 32/8 = 4 A
Output ripple
ΔVo = 4·0.4/(50·10³·10·10⁻⁶) = 3200 mV
Answer
ΔVo = 3200 mV
3.DC motors
Answer: SR = 8.108 %
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load and full-load speed
n₀ = 60·120/(2π·0.4) = 2865 rpm
nFL = 60·(120 − 6·1.5)/(2π·0.4) = 2650 rpm
Speed regulation
SR = (2865 − 2650)/2650·100 = 8.108 %
Answer
SR = 8.108 %
4.DC motors
Answer: Rst = 1.4 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Total resistance
Ra + Rst = 48/20 = 2.4 Ω
Starting resistor
Rst = 2.4 − 1 = 1.4 Ω
Answer
Rst = 1.4 Ω
The resistor is cut out step by step as the motor speeds up and the back-EMF grows.
5.AC power & power factor
Answer: cos φ = 0.8251
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of each load
A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).
Q1 = 4·tan(arccos 0.85) = 2.479 kvar
Q2 = 4·tan(arccos 0.8) = 3 kvar
Totals
P = 4 + 4 = 8 kW
Q = 2.479 + 3 = 5.479 kvar
S = √(8² + 5.479²) = 9.696 kVA
Overall power factor
cos φ = P/S = 8/9.696 = 0.8251 lagging
Answer
cos φ = 0.8251
6.AC power & power factor
Answer: C = 7.958 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Conjugate match
The load reactance cancels the source reactance, and the load resistance equals the source resistance.
ZL = Zs* = 25 − j20 Ω
Capacitance
XC = 20 Ω → C = 1/(2π·1000·20) = 7.958 µF
Answer
C = 7.958 µF
7.Three-phase power
Answer: IL = 13.83 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 7.5/0.91 = 8.242 kW
Line current
IL = Pin/(√3·VL·cos φ) = 8242/(√3·400·0.86) = 13.83 A
Answer
IL = 13.83 A
8.Three-phase power
Answer: Cph = 254.4 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 200·tan(acos 0.65) = 200·1.169 = 233.8 kvar
Q2 = 200·tan(acos 0.9) = 200·0.4843 = 96.86 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 137 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.