Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VIL​ = 12 Acos φ = 0.92lagging

A balanced three-phase load draws a line current of 12 A from a supply with a line-to-line voltage of 208 V. The power factor is 0.92 lagging. Find the total real power P drawn by the load in kW.

VL = 208 VIL = 12 Acos φ = 0.92
P = kW
2.Three-phase powerHard
P = 50 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 50 kW at a power factor of 0.7 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.

P = 50 kWpf1 = 0.7pf2 = 0.95VL = 690 Vf = 60 Hz
Cph = µF
3.TransformersMedium
16 Ω101

A 16 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 10:1. Find the resistance R1′ seen looking into the primary winding.

N1:N2 = 10:1RL = 16 Ω
R1′ = Ω
4.TransformersHard
pf 0.8550 kVA, η = 97%

A single-phase 50 kVA transformer has a core loss of 250 W. At rated load and a power factor of 0.85 lagging its efficiency is 97%. Find the full-load copper loss Pcu,fl in watts.

S = 50 kVAPcore = 250 Wpf = 0.85η = 97%
Pcu,fl = W
5.AC power & power factorMedium
P = 22 kWQSφ

A single-phase motor takes 22 kW at a power factor of 0.8 lagging from a 400 V supply. Find the line current I.

P = 22 kWpf = 0.8V = 400 V
I = A
6.AC power & power factorHard
P = 10 kWQ1​S1​φ1​QC​

A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.

P = 10 kWpf1 = 0.6pf2 = 0.98V = 400 Vf = 60 Hz
C = µF
7.AC impedance & phasorsMedium
50 V50 HzR = 100 ΩL = 200 mHC = 4.7 µFI

A series RLC circuit is connected to a 50 V (rms), 50 Hz supply. Find the real power P taken from the supply.

V = 50 V (rms)f = 50 HzR = 100 ΩL = 200 mHC = 4.7 µF
P = W
8.AC impedance & phasorsHard
VfR = 10 ΩL = 2 mHC = 0.1 µF

A series RLC circuit has R = 10 Ω, L = 2 mH and C = 0.1 µF. Find its bandwidth B (the width of the band between the half-power frequencies), in Hz.

R = 10 ΩL = 2 mHC = 0.1 µF
B = Hz
9.DC motorsMedium
T (N·m)n (rpm)n0​ = ?

A DC motor with k = 0.6 V·s/rad runs from 110 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.

V = 110 Vk = 0.6 V·s/rad
n0 = rpm
10.DC motorsHard
T (N·m)n (rpm)3 N·m1200 rpm

A DC motor with k = 0.6 V·s/rad and Ra = 2 Ω must drive a load of 3 N·m at 1200 rpm. Find the armature voltage V it needs.

k = 0.6 V·s/radRa = 2 ΩT = 3 N·mn = 1200 rpm
V = V

3Solutions

1.Three-phase power

Answer: P = 3.977 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Apparent power

S = √3·VL·IL = √3·208·12 = 4.323 kVA

Real power

P = S·cos φ = 4.323·0.92 = 3.977 kW

Answer

P = 3.977 kW
2.Three-phase power

Answer: Cph = 64.21 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 50·tan(acos 0.7) = 50·1.02 = 51.01 kvar
Q2 = 50·tan(acos 0.95) = 50·0.3287 = 16.43 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 34.58 kvar

Capacitance per phase

In a Δ bank each capacitor is connected between two lines.

V = 690 V, ω = 2π·60 = 377 rad/s
Cph = (QC/3)/(ω·V²) = 11525/(377·690²) = 64.21 µF

Answer

Cph = 64.21 µF
3.Transformers

Answer: R1′ = 1600 Ω

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Referred resistance

The voltage goes up by a and the current down by a, so the ratio V/I goes up by a².

R1′ = a²·RL = 10²·16 = 1600 Ω

Answer

R1′ = 1600 Ω
4.Transformers

Answer: Pcu,fl = 1064 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Output and input power

Pout = 50·0.85 = 42.5 kW
Pin = 42500/0.97 = 43814 W

Total and copper losses

Ploss = 43814 − 42500 = 1314 W
Pcu,fl = 1314 − 250 = 1064 W

Answer

Pcu,fl = 1064 W
5.AC power & power factor

Answer: I = 68.75 A

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Line current

Only the real part of the power does work, so divide by the power factor.

I = P/(V·cos φ) = 22000/(400·0.8) = 68.75 A

Answer

I = 68.75 A
6.AC power & power factor

Answer: C = 187.4 µF

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = P·tan φ1 = 10·tan(53.13°) = 13.33 kvar
Q2 = P·tan φ2 = 10·tan(11.48°) = 2.031 kvar
QC = Q1 − Q2 = 11.3 kvar

Capacitance

A capacitor across the supply delivers Q = V²·ωC.

C = QC/(2πf·V²) = 11303/(2π·60·400²) = 187.4 µF

Answer

C = 187.4 µF
7.AC impedance & phasors

Answer: P = 0.6451 W

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

XL = 62.83 Ω, XC = 677.3 Ω

Impedance

|Z| = √(100² + (−614.4)²) = 622.5 Ω

Real power

Inductors and capacitors only store and return energy; the resistor absorbs all of the real power.

I = 50/622.5 = 0.08032 A
P = I²·R = 0.08032²·100 = 0.6451 W

Answer

P = 0.6451 W
8.AC impedance & phasors

Answer: B = 795.8 Hz

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonant frequency

f0 = 1/(2π·√(0.002·0.1·10⁻⁶)) = 11254 Hz

Quality factor

Q compares the reactance at resonance with the resistance: Q = ω₀L/R.

Q = (1/R)·√(L/C) = (1/10)·√(0.002/(0.1·10⁻⁶)) = 14.14

Bandwidth

B = f0/Q = 11254/14.14 = 795.8 Hz

Answer

B = 795.8 Hz
9.DC motors

Answer: n0 = 1751 rpm

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

No-load speed

ω₀ = V/k = 110/0.6 = 183.3 rad/s
n0 = 60·183.3/(2π) = 1751 rpm

Answer

n0 = 1751 rpm
10.DC motors

Answer: V = 85.4 V

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Back-EMF

E = 0.6·125.7 = 75.4 V

Armature current

Ia = 3/0.6 = 5 A

Armature voltage

V = 75.4 + 5·2 = 85.4 V

Answer

V = 85.4 V

ExamProblems · examproblems.com/courses/power-systems