1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 415 VZ = 24 + j18 Ωper phase

A balanced Δ-connected load with an impedance of 24 + j18 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.

VL = 415 VZ = 24 + j18 Ω per phase
P = kW
2.Three-phase powerHard
P = 300 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 300 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 300 kWpf1 = 0.75pf2 = 0.9VL = 480 Vf = 50 Hz
Cph = µF
3.TransformersMedium
4 ΩN1​N2​400 Ω

An amplifier with an output resistance of 400 Ω drives a 4 Ω loudspeaker through an ideal transformer. For maximum power transfer the loudspeaker must look like 400 Ω from the amplifier. Find the turns ratio a = N₁/N₂.

Rs = 400 ΩRL = 4 Ω
a =
4.TransformersHard
pf 0.9150 kVA, 25% load

A single-phase 150 kVA transformer has a core loss of 450 W and a copper loss of 1800 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.9 lagging. Find the total losses Ploss in watts at this load.

S = 150 kVAPcore = 450 WPcu,fl = 1800 Wx = 0.25pf = 0.9
Ploss = W
5.AC power & power factorMedium
240 V19 kW, 0.7228 kW, 0.8I

Two loads are connected in parallel to a 240 V single-phase supply: a 9 kW load at a power factor of 0.7 lagging and a 28 kW load at a power factor of 0.8 lagging. Find the overall power factor cos φ seen by the supply.

V = 240 VP1 = 9 kW, pf1 = 0.7 laggingP2 = 28 kW, pf2 = 0.8 lagging
cos φ =
6.AC power & power factorHard
240 V50 Hzload2 kW, 0.65C22 µFI

A single-phase load takes 2 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A 22 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.

P = 2 kWpf1 = 0.65V = 240 Vf = 50 HzC = 22 µF
cos φ =
7.AC impedance & phasorsMedium
100 V200 HzR = 80 ΩL = 50 mHC = 10 µF

A series RLC circuit is connected to a 100 V (rms), 200 Hz supply. Find the phase angle φ of the impedance, in degrees (positive when the current lags the voltage).

V = 100 V (rms)f = 200 HzR = 80 ΩL = 50 mHC = 10 µF
φ = °
8.AC impedance & phasorsHard
230 V500 HzR1​ = 30 ΩR2​ = 150 ΩC = 2.2 µFI

A resistor R1 is connected in series with a parallel combination of R2 and a capacitor C, across a 230 V (rms), 500 Hz supply. Find the rms current I.

V = 230 V (rms)f = 500 HzR1 = 30 ΩR2 = 150 ΩC = 2.2 µF
I = A
9.DC motorsMedium
T (N·m)n (rpm)3 N·mn0​nFL​

A DC motor (k = 0.15 V·s/rad, Ra = 0.25 Ω) runs from 48 V. At full load it draws 20 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.

V = 48 Vk = 0.15 V·s/radRa = 0.25 ΩIFL = 20 A
SR = %
10.DC motorsHard
+−240 VD = ?Ra​ = 1.5 ΩM+−En = 500 rpmT = 1.5 N·m

A DC chopper feeds a motor (k = 0.3 V·s/rad, Ra = 1.5 Ω) from a 240 V DC bus. The average armature voltage is D·240 V. Find the duty cycle D that runs the motor at 500 rpm with a load of 1.5 N·m.

Vdc = 240 Vk = 0.3 V·s/radRa = 1.5 ΩT = 1.5 N·mn = 500 rpm
D = %

3Solutions

1.Three-phase power

Answer: P = 13.78 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Phase voltage

Vph = VL = 415 V

Phase current

|Z| = √(24² + 18²) = 30 Ω
Iph = 415/30 = 13.83 A

Total real power

Only the resistive part of each impedance absorbs real power.

P = 3·Iph²·R = 3·13.83²·24 = 13.78 kW

Answer

P = 13.78 kW

Check: cos φ = R/|Z| = 0.8, and √3·VL·IL·cos φ gives the same power.

2.Three-phase power

Answer: Cph = 1648 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 300·tan(acos 0.75) = 300·0.8819 = 264.6 kvar
Q2 = 300·tan(acos 0.9) = 300·0.4843 = 145.3 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 119.3 kvar

Capacitance per phase

In a Y bank each capacitor is connected between a line and the star point.

V = 480/√3 = 277.1 V, ω = 2π·50 = 314.2 rad/s
Cph = (QC/3)/(ω·V²) = 39759/(314.2·277.1²) = 1648 µF

Answer

Cph = 1648 µF
3.Transformers

Answer: a = 10

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Match the referred load

a²·4 = 400
a = √(400/4) = √100 = 10

Answer

a = 10
4.Transformers

Answer: Ploss = 562.5 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss at this load

Pcu = x²·Pcu,fl = 0.0625·1800 = 112.5 W

Total losses

The core loss is the same at any load.

Ploss = 450 + 112.5 = 562.5 W

Answer

Ploss = 562.5 W

The efficiency at this load is η = 98.36%.

5.AC power & power factor

Answer: cos φ = 0.7749

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power of each load

A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).

Q1 = 9·tan(arccos 0.7) = 9.182 kvar
Q2 = 28·tan(arccos 0.8) = 21 kvar

Totals

P = 9 + 28 = 37 kW
Q = 9.182 + 21 = 30.18 kvar
S = √(37² + 30.18²) = 47.75 kVA

Overall power factor

cos φ = P/S = 37/47.75 = 0.7749 lagging

Answer

cos φ = 0.7749
6.AC power & power factor

Answer: cos φ = 0.7178

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = 2·tan(arccos 0.65) = 2.338 kvar
QC = V²·2πf·C = 240²·2π·50·22·10⁻⁶ = 398.1 var = 0.3981 kvar
Q2 = 2.338 − 0.3981 = 1.94 kvar

New apparent power

S2 = √(2² + 1.94²) = 2.786 kVA

New power factor

cos φ = P/S2 = 2/2.786 = 0.7178

Answer

cos φ = 0.7178
7.AC impedance & phasors

Answer: φ = −11.82 °

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·200 = 1257 rad/s
XL = ωL = 1257·0.05 = 62.83 Ω
XC = 1/(ωC) = 1/(1257·10·10⁻⁶) = 79.58 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(80² + (−16.75)²) = 81.73 Ω

Phase angle

φ = arctan((XL − XC)/R) = arctan(−16.75/80) = −11.82°

Answer

φ = −11.82°
8.AC impedance & phasors

Answer: I = 1.814 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactance

XC = 1/(2π·500·2.2·10⁻⁶) = 144.7 Ω

Parallel combination

Multiply top and bottom by the complex conjugate to split Zp into real and imaginary parts.

Zp = R₂·(−jXC)/(R₂ − jXC) = (R₂·XC² − jR₂²·XC)/(R₂² + XC²)
Zp = 72.3 − j74.95 Ω

Total impedance

Z = 30 + 72.3 − j74.95 = 102.3 − j74.95 Ω
|Z| = √(102.3² + 74.95²) = 126.8 Ω

Current

I = V/|Z| = 230/126.8 = 1.814 A

Answer

I = 1.814 A
9.DC motors

Answer: SR = 11.63 %

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

No-load and full-load speed

n₀ = 60·48/(2π·0.15) = 3056 rpm
nFL = 60·(48 − 20·0.25)/(2π·0.15) = 2737 rpm

Speed regulation

SR = (3056 − 2737)/2737·100 = 11.63 %

Answer

SR = 11.63 %
10.DC motors

Answer: D = 9.67 %

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Required armature voltage

Va = 0.3·52.36 + 5·1.5 = 23.21 V

Duty cycle

D = 23.21/240 = 9.67 %

Answer

D = 9.67 %

ExamProblems · examproblems.com/courses/power-systems