Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VNZ = 24 + j7 Ωper phase

A balanced Y-connected load with an impedance of 24 + j7 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.

VL = 208 VZ = 24 + j7 Ω per phase
P = kW
2.Three-phase powerHard
P = 75 kWφ1​S1​Q2​QC​ = ?

A balanced three-phase load takes 75 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.

P = 75 kWpf1 = 0.75pf2 = 0.92VL = 480 Vf = 60 Hz
QC = kvar
3.TransformersMedium
2400 V240 VIHV​ILV​ = ?50 kVA

A single-phase 50 kVA, 2400/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.

S = 50 kVAV1 = 2400 VV2 = 240 V
ILV = A
4.TransformersHard
pf 0.95500 kVA, 25% load

A single-phase 500 kVA transformer has a core loss of 4000 W and a copper loss of 8000 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.

S = 500 kVAPcore = 4000 WPcu,fl = 8000 Wx = 0.25pf = 0.95
Ploss = W
5.AC power & power factorMedium
P = 22 kWQ = ?Sφ

A single-phase motor takes 22 kW at a power factor of 0.65 lagging from a 230 V supply. Find the reactive power Q it draws.

P = 22 kWpf = 0.65V = 230 V
Q = kvar
6.AC power & power factorHard
P = 30 kWQ1​S1​φ1​QC​

A single-phase load takes 30 kW at a power factor of 0.75 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.

P = 30 kWpf1 = 0.75pf2 = 0.92V = 400 Vf = 50 Hz
C = µF
7.AC impedance & phasorsMedium
10 V1000 HzR = 60 ΩL = 50 mHC = 2.2 µF

A series RLC circuit is connected to a 10 V (rms), 1000 Hz supply. Find the phase angle φ of the impedance, in degrees (positive when the current lags the voltage).

V = 10 V (rms)f = 1000 HzR = 60 ΩL = 50 mHC = 2.2 µF
φ = °
8.AC impedance & phasorsHard
24 V200 HzR = 80 ΩL = 100 mHC = 4.7 µFI

A series RLC circuit is connected to a 24 V (rms), 200 Hz supply. Find the rms current I.

V = 24 V (rms)f = 200 HzR = 80 ΩL = 100 mHC = 4.7 µF
I = A
9.DC motorsMedium
T (N·m)n (rpm)n0​ = ?

A DC motor with k = 0.4 V·s/rad runs from 110 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.

V = 110 Vk = 0.4 V·s/rad
n0 = rpm
10.DC motorsHard
+−120 VRa​ = 2.5 ΩM+−EωT

A small DC motor has an armature resistance of 2.5 Ω and runs from 120 V. Neglecting rotational losses, find the largest mechanical power Pmax it can develop at any speed.

V = 120 VRa = 2.5 Ω
Pmax = W

3Solutions

1.Three-phase power

Answer: P = 1.661 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Phase voltage

Vph = 208/√3 = 120.1 V

Phase current

|Z| = √(24² + 7²) = 25 Ω
Iph = 120.1/25 = 4.804 A

Total real power

Only the resistive part of each impedance absorbs real power.

P = 3·Iph²·R = 3·4.804²·24 = 1.661 kW

Answer

P = 1.661 kW

Check: cos φ = R/|Z| = 0.96, and √3·VL·IL·cos φ gives the same power.

2.Three-phase power

Answer: QC = 34.19 kvar

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 75·tan(acos 0.75) = 75·0.8819 = 66.14 kvar
Q2 = 75·tan(acos 0.92) = 75·0.426 = 31.95 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 34.19 kvar

Answer

QC = 34.19 kvar
3.Transformers

Answer: ILV = 208.3 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Rated current

Both windings carry the same apparent power.

ILV = S/V = 50000/240 = 208.3 A

Answer

ILV = 208.3 A
4.Transformers

Answer: Ploss = 4500 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss at this load

Pcu = x²·Pcu,fl = 0.0625·8000 = 500 W

Total losses

The core loss is the same at any load.

Ploss = 4000 + 500 = 4500 W

Answer

Ploss = 4500 W

The efficiency at this load is η = 96.35%.

5.AC power & power factor

Answer: Q = 25.72 kvar

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Angle

φ = arccos(0.65) = 49.46°, tan φ = 1.169

Reactive power

Q = P·tan φ = 22·1.169 = 25.72 kvar

Answer

Q = 25.72 kvar
6.AC power & power factor

Answer: C = 272.1 µF

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = P·tan φ1 = 30·tan(41.41°) = 26.46 kvar
Q2 = P·tan φ2 = 30·tan(23.07°) = 12.78 kvar
QC = Q1 − Q2 = 13.68 kvar

Capacitance

A capacitor across the supply delivers Q = V²·ωC.

C = QC/(2πf·V²) = 13678/(2π·50·400²) = 272.1 µF

Answer

C = 272.1 µF
7.AC impedance & phasors

Answer: φ = 76.07 °

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·1000 = 6283 rad/s
XL = ωL = 6283·0.05 = 314.2 Ω
XC = 1/(ωC) = 1/(6283·2.2·10⁻⁶) = 72.34 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(60² + (241.8)²) = 249.1 Ω

Phase angle

φ = arctan((XL − XC)/R) = arctan(241.8/60) = 76.07°

Answer

φ = 76.07°
8.AC impedance & phasors

Answer: I = 0.2633 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·200 = 1257 rad/s
XL = ωL = 1257·0.1 = 125.7 Ω
XC = 1/(ωC) = 1/(1257·4.7·10⁻⁶) = 169.3 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(80² + (−43.65)²) = 91.13 Ω

Current

The same current flows through every element of a series circuit.

I = V/|Z| = 24/91.13 = 0.2633 A

Answer

I = 0.2633 A
9.DC motors

Answer: n0 = 2626 rpm

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

No-load speed

ω₀ = V/k = 110/0.4 = 275 rad/s
n0 = 60·275/(2π) = 2626 rpm

Answer

n0 = 2626 rpm
10.DC motors

Answer: Pmax = 1440 W

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Power as a function of the back-EMF

P(E) = E·(V − E)/Ra
dP/dE = 0 → E = V/2 = 60 V

Maximum power

Pmax = (V/2)²/Ra = V²/(4Ra) = 120²/(4·2.5) = 1440 W

Answer

Pmax = 1440 W

At this point the efficiency is only 50 %, so real motors run well above half speed.

ExamProblems · examproblems.com/courses/power-systems