Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VIL​ = 10 Acos φ = 0.8lagging

A balanced three-phase load draws a line current of 10 A from a supply with a line-to-line voltage of 208 V. The power factor is 0.8 lagging. Find the total real power P drawn by the load in kW.

VL = 208 VIL = 10 Acos φ = 0.8
P = kW
2.Three-phase powerHard
P = 250 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 250 kW at a power factor of 0.7 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.

P = 250 kWpf1 = 0.7pf2 = 0.9VL = 415 Vf = 50 Hz
Cph = µF
3.TransformersMedium
7200 V240 VIHV​ = ?ILV​500 kVA

A single-phase 500 kVA, 7200/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.

S = 500 kVAV1 = 7200 VV2 = 240 V
IHV = A
4.TransformersHard
200 kVA

A single-phase 200 kVA transformer has a core loss of 600 W and a copper loss of 1800 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?

S = 200 kVAPcore = 600 WPcu,fl = 1800 W
Sη,max = kVA
5.AC power & power factorMedium
P = 6 kWQ = ?Sφ

A single-phase motor takes 6 kW at a power factor of 0.85 lagging from a 240 V supply. Find the reactive power Q it draws.

P = 6 kWpf = 0.85V = 240 V
Q = kvar
6.AC power & power factorHard
P = 5 kWQ1​S1​φ1​QC​

A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.

P = 5 kWpf1 = 0.6pf2 = 0.98V = 400 Vf = 60 Hz
C = µF
7.AC impedance & phasorsMedium
50 V50 HzR = 100 ΩL = 20 mHC = 10 µF

A series RLC circuit is connected to a 50 V (rms), 50 Hz supply. Find the phase angle φ of the impedance, in degrees (positive when the current lags the voltage).

V = 50 V (rms)f = 50 HzR = 100 ΩL = 20 mHC = 10 µF
φ = °
8.AC impedance & phasorsHard
2 Vf0​R = 20 ΩL = 5 mHC = 0.47 µF

A series RLC circuit is driven by a 2 V (rms) source whose frequency is set to the resonant frequency of the circuit. Find the rms voltage VL across the inductor.

V = 2 V (rms)R = 20 ΩL = 5 mHC = 0.47 µF
VL = V
9.DC motorsMedium
+−VRa​M+−En = 2900 rpmT = ?

A DC motor delivers 0.75 kW of mechanical power at 2900 rpm. Find the shaft torque T.

P = 0.75 kWn = 2900 rpm
T = N·m
10.DC motorsHard
+−48 VRst​ = ?Ra​ = 1.5 Ω25 AM+−E = 0n = 0T

A 48 V DC motor has an armature resistance of 1.5 Ω. Find the series starting resistance Rst that limits the starting current to 25 A.

V = 48 VRa = 1.5 ΩImax = 25 A
Rst = Ω

3Solutions

1.Three-phase power

Answer: P = 2.882 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Apparent power

S = √3·VL·IL = √3·208·10 = 3.603 kVA

Real power

P = S·cos φ = 3.603·0.8 = 2.882 kW

Answer

P = 2.882 kW
2.Three-phase power

Answer: Cph = 825.4 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 250·tan(acos 0.7) = 250·1.02 = 255.1 kvar
Q2 = 250·tan(acos 0.9) = 250·0.4843 = 121.1 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 134 kvar

Capacitance per phase

In a Δ bank each capacitor is connected between two lines.

V = 415 V, ω = 2π·50 = 314.2 rad/s
Cph = (QC/3)/(ω·V²) = 44657/(314.2·415²) = 825.4 µF

Answer

Cph = 825.4 µF
3.Transformers

Answer: IHV = 69.44 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Rated current

Both windings carry the same apparent power.

IHV = S/V = 500000/7200 = 69.44 A

Answer

IHV = 69.44 A
4.Transformers

Answer: Sη,max = 115.5 kVA

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss equals core loss

x²·1800 = 600 → x = √(600/1800) = 0.5774

Load at maximum efficiency

Sη,max = x·S = 0.5774·200 = 115.5 kVA

Answer

Sη,max = 115.5 kVA
5.AC power & power factor

Answer: Q = 3.718 kvar

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Angle

φ = arccos(0.85) = 31.79°, tan φ = 0.6197

Reactive power

Q = P·tan φ = 6·0.6197 = 3.718 kvar

Answer

Q = 3.718 kvar
6.AC power & power factor

Answer: C = 93.69 µF

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = P·tan φ1 = 5·tan(53.13°) = 6.667 kvar
Q2 = P·tan φ2 = 5·tan(11.48°) = 1.015 kvar
QC = Q1 − Q2 = 5.651 kvar

Capacitance

A capacitor across the supply delivers Q = V²·ωC.

C = QC/(2πf·V²) = 5651/(2π·60·400²) = 93.69 µF

Answer

C = 93.69 µF
7.AC impedance & phasors

Answer: φ = −72.23 °

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·50 = 314.2 rad/s
XL = ωL = 314.2·0.02 = 6.283 Ω
XC = 1/(ωC) = 1/(314.2·10·10⁻⁶) = 318.3 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(100² + (−312)²) = 327.7 Ω

Phase angle

φ = arctan((XL − XC)/R) = arctan(−312/100) = −72.23°

Answer

φ = −72.23°
8.AC impedance & phasors

Answer: VL = 10.31 V

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonance

At resonance the reactances cancel, so the impedance is just R.

ω₀ = 1/√(LC) = 1/√(0.005·0.47·10⁻⁶) = 20628 rad/s
I = V/R = 2/20 = 0.1 A

Voltage across the inductor

XL = ω₀L = 20628·0.005 = 103.1 Ω
VL = I·XL = 0.1·103.1 = 10.31 V

Answer

VL = 10.31 V

This is Q = 5.157 times the supply voltage.

9.DC motors

Answer: T = 2.47 N·m

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Speed in rad/s

ω = 2π·2900/60 = 303.7 rad/s

Torque

T = P/ω = 750/303.7 = 2.47 N·m

Answer

T = 2.47 N·m
10.DC motors

Answer: Rst = 0.42 Ω

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Total resistance

Ra + Rst = 48/25 = 1.92 Ω

Starting resistor

Rst = 1.92 − 1.5 = 0.42 Ω

Answer

Rst = 0.42 Ω

The resistor is cut out step by step as the motor speeds up and the back-EMF grows.

ExamProblems · examproblems.com/courses/power-systems