1Formulas and methods
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
Transformers
Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
AC impedance & phasors
Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z
Method
Convert the frequency: ω = 2πf.
Find each reactance: XL = ωL and XC = 1/(ωC).
Add impedances like resistors, with Z = R + jX.
Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
2Practice problems
1.Three-phase powerMedium
A balanced Δ-connected load with an impedance of 24 + j18 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.
VL = 415 VZ = 24 + j18 Ω per phase
P = kW
2.Three-phase powerHard
A balanced three-phase load takes 150 kW at a power factor of 0.65 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 150 kWpf1 = 0.65pf2 = 0.95VL = 415 Vf = 50 Hz
Cph = µF
3.TransformersMedium
An amplifier with an output resistance of 45 Ω drives a 5 Ω loudspeaker through an ideal transformer. For maximum power transfer the loudspeaker must look like 45 Ω from the amplifier. Find the turns ratio a = N₁/N₂.
Rs = 45 ΩRL = 5 Ω
a =
4.TransformersHard
A single-phase 100 kVA transformer has a core loss of 500 W. At rated load and a power factor of 0.85 lagging its efficiency is 98.5%. Find the full-load copper loss Pcu,fl in watts.
S = 100 kVAPcore = 500 Wpf = 0.85η = 98.5%
Pcu,fl = W
5.AC power & power factorMedium
Two loads are connected in parallel to a 230 V single-phase supply: a 26 kW load at a power factor of 0.6 lagging and a 23 kW load at a power factor of 0.85 leading. Find the total current I drawn from the supply.
V = 230 VP1 = 26 kW, pf1 = 0.6 laggingP2 = 23 kW, pf2 = 0.85 leading
I = A
6.AC power & power factorHard
A single-phase load takes 12 kW at a power factor of 0.7 lagging from a 400 V, 60 Hz supply. A 22 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
P = 12 kWpf1 = 0.7V = 400 Vf = 60 HzC = 22 µF
cos φ =
7.AC impedance & phasorsMedium
A resistor and an inductor are connected in parallel across a 24 V (rms), 100 Hz supply. Find the phase angle φ of the impedance, in degrees (positive when the current lags the voltage).
V = 24 V (rms)f = 100 HzR = 80 ΩL = 50 mH
φ = °
8.AC impedance & phasorsHard
A series RLC circuit is connected to a 120 V (rms), 50 Hz supply. Find the rms voltage VC across the capacitor.
V = 120 V (rms)f = 50 HzR = 50 ΩL = 200 mHC = 4.7 µF
VC = V
9.DC motorsMedium
A DC motor delivers 5.5 kW of mechanical power at 1200 rpm. Find the shaft torque T.
P = 5.5 kWn = 1200 rpm
T = N·m
10.DC motorsHard
A DC motor (k = 0.6 V·s/rad, Ra = 1 Ω) on a fixed 240 V supply drives a load of 6 N·m. Find the series resistance Rs that slows it down to 900 rpm.
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Phase voltage
Vph = VL = 415 V
Phase current
|Z| = √(24² + 18²) = 30 Ω
Iph = 415/30 = 13.83 A
Total real power
Only the resistive part of each impedance absorbs real power.
P = 3·Iph²·R = 3·13.83²·24 = 13.78 kW
Answer
P = 13.78 kW
Check: cos φ = R/|Z| = 0.8, and √3·VL·IL·cos φ gives the same power.
2.Three-phase power
Answer: Cph = 776.7 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 150·tan(acos 0.65) = 150·1.169 = 175.4 kvar
Q2 = 150·tan(acos 0.95) = 150·0.3287 = 49.3 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 126.1 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Match the referred load
a²·5 = 45
a = √(45/5) = √9 = 3
Answer
a = 3
4.Transformers
Answer: Pcu,fl = 794.4 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.
Output and input power
Pout = 100·0.85 = 85 kW
Pin = 85000/0.985 = 86294 W
Total and copper losses
Ploss = 86294 − 85000 = 1294 W
Pcu,fl = 1294 − 500 = 794.4 W
Answer
Pcu,fl = 794.4 W
5.AC power & power factor
Answer: I = 230.8 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of each load
A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).
Q1 = 26·tan(arccos 0.6) = 34.67 kvar
Q2 = −23·tan(arccos 0.85) = −14.25 kvar
Totals
P = 26 + 23 = 49 kW
Q = 34.67 + (−14.25) = 20.41 kvar
S = √(49² + 20.41²) = 53.08 kVA
Total current
I = S/V = 53082/230 = 230.8 A
Answer
I = 230.8 A
6.AC power & power factor
Answer: cos φ = 0.7397
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = 12·tan(arccos 0.7) = 12.24 kvar
QC = V²·2πf·C = 400²·2π·60·22·10⁻⁶ = 1327 var = 1.327 kvar
Q2 = 12.24 − 1.327 = 10.92 kvar
New apparent power
S2 = √(12² + 10.92²) = 16.22 kVA
New power factor
cos φ = P/S2 = 12/16.22 = 0.7397
Answer
cos φ = 0.7397
7.AC impedance & phasors
Answer: φ = 68.56 °
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactance
XL = ωL = 2π·100·0.05 = 31.42 Ω
Branch currents
Both branches are connected straight across the supply, so each sees the full voltage V.
IR = V/R = 24/80 = 0.3 A
IX = V/XL = 24/31.42 = 0.7639 A
Total current
The resistor current is in phase with V and the reactive current is 90° out of phase, so they add like the sides of a right triangle.
I = √(IR² + IX²) = √(0.3² + 0.7639²) = 0.8207 A
Phase angle
The inductor current lags V, so the total current lags and the angle is positive.
φ = arctan(IX/IR) = arctan(0.7639/0.3) = 68.56°
Answer
φ = 68.56°
8.AC impedance & phasors
Answer: VC = 131.8 V
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·50 = 314.2 rad/s
XL = ωL = 314.2·0.2 = 62.83 Ω
XC = 1/(ωC) = 1/(314.2·4.7·10⁻⁶) = 677.3 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 120/616.5 = 0.1947 A
Voltage across the capacitor
VC = I·XC = 0.1947·677.3 = 131.8 V
Answer
VC = 131.8 V
9.DC motors
Answer: T = 43.77 N·m
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Speed in rad/s
ω = 2π·1200/60 = 125.7 rad/s
Torque
T = P/ω = 5500/125.7 = 43.77 N·m
Answer
T = 43.77 N·m
10.DC motors
Answer: Rs = 17.35 Ω
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Current and back-EMF
Ia = 6/0.6 = 10 A
E = 0.6·94.25 = 56.55 V
Series resistance
Ra + Rs = (240 − 56.55)/10 = 18.35 Ω
Rs = 17.35 Ω
Answer
Rs = 17.35 Ω
The resistor wastes 1735 W; a chopper controls the speed with far less loss.