Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VIL​ = 50 Acos φ = 0.7lagging

A balanced three-phase load draws a line current of 50 A from a supply with a line-to-line voltage of 208 V. The power factor is 0.7 lagging. Find the total real power P drawn by the load in kW.

VL = 208 VIL = 50 Acos φ = 0.7
P = kW
2.Three-phase powerHard
P = 150 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 150 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 150 kWpf1 = 0.75pf2 = 0.92VL = 480 Vf = 50 Hz
Cph = µF
3.TransformersMedium
RL​ = 60 Ω21240 VV2​I1​ = ?I2​

An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 240 V applied to its primary winding. A 60 Ω resistor is connected across the secondary winding. Find the primary current I1.

N1:N2 = 2:1V1 = 240 VRL = 60 Ω
I1 = A
4.TransformersHard
50 kVA

A single-phase 50 kVA transformer has a core loss of 400 W and a copper loss of 800 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?

S = 50 kVAPcore = 400 WPcu,fl = 800 W
Sη,max = kVA
5.AC power & power factorMedium
240 VR + jXP = 2856 W14 A

An inductive load takes 14 A and 2856 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.

V = 240 VI = 14 AP = 2856 W
X = Ω
6.AC power & power factorHard
P = 20 kWQ1​S1​φ1​QC​

A single-phase load takes 20 kW at a power factor of 0.8 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.

P = 20 kWpf1 = 0.8pf2 = 0.92V = 230 Vf = 60 Hz
Inew = A
7.AC impedance & phasorsMedium
230 V60 HzR = 30 ΩC = 22 µFI

A resistor and a capacitor are connected in parallel across a 230 V (rms), 60 Hz supply. Find the magnitude of the impedance |Z|.

V = 230 V (rms)f = 60 HzR = 30 ΩC = 22 µF
|Z| = Ω
8.AC impedance & phasorsHard
VfR = 20 ΩL = 20 mHC = 0.022 µF

A series RLC circuit has R = 20 Ω, L = 20 mH and C = 0.022 µF. Find its bandwidth B (the width of the band between the half-power frequencies), in Hz.

R = 20 ΩL = 20 mHC = 0.022 µF
B = Hz
9.DC motorsMedium
T (N·m)n (rpm)Tst​ = ?n0​

A DC motor with k = 0.12 N·m/A and Ra = 1.5 Ω is connected to 24 V. Find its stall torque Tstall, the torque at zero speed.

V = 24 Vk = 0.12 N·m/ARa = 1.5 Ω
Tstall = N·m
10.DC motorsHard
+−110 VRa​ = 1 ΩIa​: 8 → 4.8 AM+−En = ?T

A separately excited DC motor on 110 V (Ra = 1 Ω) runs at 1500 rpm with an armature current of 8 A. The load changes and the current becomes 4.8 A, with the field unchanged. Find the new speed n2.

V = 110 VRa = 1 Ωn1 = 1500 rpmIa1 = 8 AIa2 = 4.8 A
n2 = rpm

3Solutions

1.Three-phase power

Answer: P = 12.61 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Apparent power

S = √3·VL·IL = √3·208·50 = 18.01 kVA

Real power

P = S·cos φ = 18.01·0.7 = 12.61 kW

Answer

P = 12.61 kW
2.Three-phase power

Answer: Cph = 944.8 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 150·tan(acos 0.75) = 150·0.8819 = 132.3 kvar
Q2 = 150·tan(acos 0.92) = 150·0.426 = 63.9 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 68.39 kvar

Capacitance per phase

In a Y bank each capacitor is connected between a line and the star point.

V = 480/√3 = 277.1 V, ω = 2π·50 = 314.2 rad/s
Cph = (QC/3)/(ω·V²) = 22796/(314.2·277.1²) = 944.8 µF

Answer

Cph = 944.8 µF
3.Transformers

Answer: I1 = 1 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Secondary voltage and current

V2 = 240/2 = 120 V
I2 = 120/60 = 2 A

Primary current

An ideal transformer has no losses: V₁·I₁ = V₂·I₂.

I1 = I2/2 = 1 A

Answer

I1 = 1 A

Check: the load seen from the primary is a²·RL = 240 Ω, and 240/240 gives the same current.

4.Transformers

Answer: Sη,max = 35.36 kVA

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss equals core loss

x²·800 = 400 → x = √(400/800) = 0.7071

Load at maximum efficiency

Sη,max = x·S = 0.7071·50 = 35.36 kVA

Answer

Sη,max = 35.36 kVA
5.AC power & power factor

Answer: X = 9.031 Ω

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Resistance from the real power

R = P/I² = 2856/14² = 14.57 Ω

Reactance from the impedance

|Z| = V/I = 240/14 = 17.14 Ω
X = √(|Z|² − R²) = √(17.14² − 14.57²) = 9.031 Ω

Answer

X = 9.031 Ω
6.AC power & power factor

Answer: Inew = 94.52 A

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = P·tan φ1 = 20·tan(36.87°) = 15 kvar
Q2 = P·tan φ2 = 20·tan(23.07°) = 8.52 kvar
QC = Q1 − Q2 = 6.48 kvar

New line current

Inew = P/(V·cos φ2) = 20000/(230·0.92) = 94.52 A

Answer

Inew = 94.52 A
7.AC impedance & phasors

Answer: |Z| = 29.11 Ω

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactance

XC = 1/(ωC) = 1/(2π·60·22·10⁻⁶) = 120.6 Ω

Branch currents

Both branches are connected straight across the supply, so each sees the full voltage V.

IR = V/R = 230/30 = 7.667 A
IX = V/XC = 230/120.6 = 1.908 A

Total current

The resistor current is in phase with V and the reactive current is 90° out of phase, so they add like the sides of a right triangle.

I = √(IR² + IX²) = √(7.667² + 1.908²) = 7.9 A

Impedance

|Z| = V/I = 230/7.9 = 29.11 Ω

Answer

|Z| = 29.11 Ω
8.AC impedance & phasors

Answer: B = 159.2 Hz

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonant frequency

f0 = 1/(2π·√(0.02·0.022·10⁻⁶)) = 7587 Hz

Quality factor

Q compares the reactance at resonance with the resistance: Q = ω₀L/R.

Q = (1/R)·√(L/C) = (1/20)·√(0.02/(0.022·10⁻⁶)) = 47.67

Bandwidth

B = f0/Q = 7587/47.67 = 159.2 Hz

Answer

B = 159.2 Hz
9.DC motors

Answer: Tstall = 1.92 N·m

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Stall current

Ia = V/Ra = 24/1.5 = 16 A

Stall torque

Tstall = 0.12·16 = 1.92 N·m

Answer

Tstall = 1.92 N·m
10.DC motors

Answer: n2 = 1547 rpm

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Back-EMF before and after

E1 = 110 − 8·1 = 102 V
E2 = 110 − 4.8·1 = 105.2 V

New speed

n2 = 1500·105.2/102 = 1547 rpm

Answer

n2 = 1547 rpm