In the print window, choose “Save as PDF” to keep a copy on your device.
1Formulas and methods
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
Transformers
Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
AC impedance & phasors
Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z
Method
Convert the frequency: ω = 2πf.
Find each reactance: XL = ωL and XC = 1/(ωC).
Add impedances like resistors, with Z = R + jX.
Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
2Practice problems
1.Three-phase powerMedium
A three-phase induction motor delivers 7.5 kW of mechanical output power at full load. At this load its efficiency is 93% and its power factor is 0.88 lagging. The supply has a line-to-line voltage of 690 V. Find the line current IL.
Pout = 7.5 kWη = 93%cos φ = 0.88VL = 690 V
IL = A
2.Three-phase powerHard
A balanced three-phase load takes 200 kW at a power factor of 0.7 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
P = 200 kWpf1 = 0.7pf2 = 0.95VL = 480 Vf = 60 Hz
Cph = µF
3.TransformersMedium
A single-phase 250 kVA, 480/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
S = 250 kVAV1 = 480 VV2 = 240 V
ILV = A
4.TransformersHard
A single-phase 50 kVA transformer has a core loss of 250 W and a copper loss of 750 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
S = 50 kVAPcore = 250 WPcu,fl = 750 W
Sη,max = kVA
5.AC power & power factorMedium
A single-phase motor takes 28 kW at a power factor of 0.9 lagging from a 230 V supply. Find the line current I.
P = 28 kWpf = 0.9V = 230 V
I = A
6.AC power & power factorHard
A single-phase load takes 6 kW at a power factor of 0.75 lagging from a 230 V, 60 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
P = 6 kWpf1 = 0.75V = 230 Vf = 60 HzC = 150 µF
cos φ =
7.AC impedance & phasorsMedium
A series RLC circuit is connected to a 230 V (rms), 50 Hz supply. Find the rms current I.
V = 230 V (rms)f = 50 HzR = 60 ΩL = 50 mHC = 10 µF
I = A
8.AC impedance & phasorsHard
A series RLC circuit is connected to a 12 V (rms), 500 Hz supply. Find the rms current I.
V = 12 V (rms)f = 500 HzR = 60 ΩL = 150 mHC = 10 µF
I = A
9.DC motorsMedium
A DC motor draws 6 A from a 110 V supply. Its armature resistance is 1 Ω and its rotational (friction, windage and iron) losses are 31 W. Find its efficiency η.
V = 110 VIa = 6 ARa = 1 ΩProt = 31 W
η = %
10.DC motorsHard
A separately excited DC motor on 220 V (Ra = 0.5 Ω) runs at 1500 rpm with an armature current of 15 A. The load changes and the current becomes 22.5 A, with the field unchanged. Find the new speed n2.
V = 220 VRa = 0.5 Ωn1 = 1500 rpmIa1 = 15 AIa2 = 22.5 A
n2 = rpm
3Solutions
1.Three-phase power
Answer: IL = 7.668 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 7.5/0.93 = 8.065 kW
Line current
IL = Pin/(√3·VL·cos φ) = 8065/(√3·690·0.88) = 7.668 A
Answer
IL = 7.668 A
2.Three-phase power
Answer: Cph = 1592 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 200·tan(acos 0.7) = 200·1.02 = 204 kvar
Q2 = 200·tan(acos 0.95) = 200·0.3287 = 65.74 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 138.3 kvar
Capacitance per phase
In a Y bank each capacitor is connected between a line and the star point.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
ILV = S/V = 250000/240 = 1042 A
Answer
ILV = 1042 A
4.Transformers
Answer: Sη,max = 28.87 kVA
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.
Copper loss equals core loss
x²·750 = 250 → x = √(250/750) = 0.5774
Load at maximum efficiency
Sη,max = x·S = 0.5774·50 = 28.87 kVA
Answer
Sη,max = 28.87 kVA
5.AC power & power factor
Answer: I = 135.3 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 28000/(230·0.9) = 135.3 A
Answer
I = 135.3 A
6.AC power & power factor
Answer: cos φ = 0.9337
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = 6·tan(arccos 0.75) = 5.292 kvar
QC = V²·2πf·C = 230²·2π·60·150·10⁻⁶ = 2991 var = 2.991 kvar
Q2 = 5.292 − 2.991 = 2.3 kvar
New apparent power
S2 = √(6² + 2.3²) = 6.426 kVA
New power factor
cos φ = P/S2 = 6/6.426 = 0.9337
Answer
cos φ = 0.9337
7.AC impedance & phasors
Answer: I = 0.7456 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·50 = 314.2 rad/s
XL = ωL = 314.2·0.05 = 15.71 Ω
XC = 1/(ωC) = 1/(314.2·10·10⁻⁶) = 318.3 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 230/308.5 = 0.7456 A
Answer
I = 0.7456 A
8.AC impedance & phasors
Answer: I = 0.02706 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·500 = 3142 rad/s
XL = ωL = 3142·0.15 = 471.2 Ω
XC = 1/(ωC) = 1/(3142·10·10⁻⁶) = 31.83 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 12/443.5 = 0.02706 A
Answer
I = 0.02706 A
9.DC motors
Answer: η = 89.85 %
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Powers
Pin = 110·6 = 660 W
Pdev = 104·6 = 624 W
Pout = 624 − 31 = 593 W
Efficiency
η = 593/660·100 = 89.85 %
Answer
η = 89.85 %
10.DC motors
Answer: n2 = 1474 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.