1Formulas and methods
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
Transformers
Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
AC impedance & phasors
Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z
Method
Convert the frequency: ω = 2πf.
Find each reactance: XL = ωL and XC = 1/(ωC).
Add impedances like resistors, with Z = R + jX.
Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
2Practice problems
1.Three-phase powerMedium
A balanced three-phase load draws a line current of 25 A from a supply with a line-to-line voltage of 415 V. The power factor is 0.92 lagging. Find the total real power P drawn by the load in kW.
VL = 415 VIL = 25 Acos φ = 0.92
P = kW
2.Three-phase powerHard
A balanced three-phase load takes 80 kW at a power factor of 0.72 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 80 kWpf1 = 0.72pf2 = 0.9VL = 690 Vf = 50 Hz
QC = kvar
3.TransformersMedium
An ideal transformer with a turns ratio N₁:N₂ = 10:1 has 1200 V applied to its primary winding. A 6 Ω resistor is connected across the secondary winding. Find the primary current I1.
N1:N2 = 10:1V1 = 1200 VRL = 6 Ω
I1 = A
4.TransformersHard
A single-phase 250 kVA transformer has a core loss of 2000 W. At rated load and a power factor of 0.8 lagging its efficiency is 96.5%. Find the full-load copper loss Pcu,fl in watts.
S = 250 kVAPcore = 2000 Wpf = 0.8η = 96.5%
Pcu,fl = W
5.AC power & power factorMedium
A single-phase motor takes 10 kW at a power factor of 0.65 lagging from a 400 V supply. Find the line current I.
P = 10 kWpf = 0.65V = 400 V
I = A
6.AC power & power factorHard
A single-phase load takes 20 kW at a power factor of 0.75 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
P = 20 kWpf1 = 0.75pf2 = 0.9V = 400 Vf = 50 Hz
Inew = A
7.AC impedance & phasorsMedium
A series RLC circuit is connected to a 12 V (rms), 100 Hz supply. Find the real power P taken from the supply.
V = 12 V (rms)f = 100 HzR = 15 ΩL = 50 mHC = 100 µF
P = W
8.AC impedance & phasorsHard
A resistor R1 is connected in series with a parallel combination of R2 and a capacitor C, across a 24 V (rms), 100 Hz supply. Find the rms current I.
V = 24 V (rms)f = 100 HzR1 = 50 ΩR2 = 40 ΩC = 100 µF
I = A
9.DC motorsMedium
A DC motor (k = 0.6 V·s/rad, Ra = 0.5 Ω) runs from 120 V. At full load it draws 20 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.
V = 120 Vk = 0.6 V·s/radRa = 0.5 ΩIFL = 20 A
SR = %
10.DC motorsHard
A small DC motor has an armature resistance of 4 Ω and runs from 48 V. Neglecting rotational losses, find the largest mechanical power Pmax it can develop at any speed.
V = 48 VRa = 4 Ω
Pmax = W
3Solutions
1.Three-phase power
Answer: P = 16.53 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Apparent power
S = √3·VL·IL = √3·415·25 = 17.97 kVA
Real power
P = S·cos φ = 17.97·0.92 = 16.53 kW
Answer
P = 16.53 kW
2.Three-phase power
Answer: QC = 38.36 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 80·tan(acos 0.72) = 80·0.9639 = 77.11 kvar
Q2 = 80·tan(acos 0.9) = 80·0.4843 = 38.75 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 38.36 kvar
Answer
QC = 38.36 kvar
3.Transformers
Answer: I1 = 2 A
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Secondary voltage and current
V2 = 1200/10 = 120 V
I2 = 120/6 = 20 A
Primary current
An ideal transformer has no losses: V₁·I₁ = V₂·I₂.
I1 = I2/10 = 2 A
Answer
I1 = 2 A
Check: the load seen from the primary is a²·RL = 600 Ω, and 1200/600 gives the same current.
4.Transformers
Answer: Pcu,fl = 5254 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.
Output and input power
Pout = 250·0.8 = 200 kW
Pin = 200000/0.965 = 207254 W
Total and copper losses
Ploss = 207254 − 200000 = 7254 W
Pcu,fl = 7254 − 2000 = 5254 W
Answer
Pcu,fl = 5254 W
5.AC power & power factor
Answer: I = 38.46 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 10000/(400·0.65) = 38.46 A
Answer
I = 38.46 A
6.AC power & power factor
Answer: Inew = 55.56 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 20·tan(41.41°) = 17.64 kvar
Q2 = P·tan φ2 = 20·tan(25.84°) = 9.686 kvar
QC = Q1 − Q2 = 7.952 kvar
New line current
Inew = P/(V·cos φ2) = 20000/(400·0.9) = 55.56 A
Answer
Inew = 55.56 A
7.AC impedance & phasors
Answer: P = 4.643 W
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
XL = 31.42 Ω, XC = 15.92 Ω
Impedance
|Z| = √(15² + (15.5)²) = 21.57 Ω
Real power
Inductors and capacitors only store and return energy; the resistor absorbs all of the real power.
I = 12/21.57 = 0.5563 A
P = I²·R = 0.5563²·15 = 4.643 W
Answer
P = 4.643 W
8.AC impedance & phasors
Answer: I = 0.42 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactance
XC = 1/(2π·100·100·10⁻⁶) = 15.92 Ω
Parallel combination
Multiply top and bottom by the complex conjugate to split Zp into real and imaginary parts.
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load and full-load speed
n₀ = 60·120/(2π·0.6) = 1910 rpm
nFL = 60·(120 − 20·0.5)/(2π·0.6) = 1751 rpm
Speed regulation
SR = (1910 − 1751)/1751·100 = 9.091 %
Answer
SR = 9.091 %
10.DC motors
Answer: Pmax = 144 W
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Power as a function of the back-EMF
P(E) = E·(V − E)/Ra
dP/dE = 0 → E = V/2 = 24 V
Maximum power
Pmax = (V/2)²/Ra = V²/(4Ra) = 48²/(4·4) = 144 W
Answer
Pmax = 144 W
At this point the efficiency is only 50 %, so real motors run well above half speed.