1Formulas and methods
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
Transformers
Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
AC impedance & phasors
Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z
Method
Convert the frequency: ω = 2πf.
Find each reactance: XL = ωL and XC = 1/(ωC).
Add impedances like resistors, with Z = R + jX.
Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
2Practice problems
1.Three-phase powerMedium
A three-phase induction motor delivers 110 kW of mechanical output power at full load. At this load its efficiency is 88% and its power factor is 0.8 lagging. The supply has a line-to-line voltage of 415 V. Find the line current IL.
Pout = 110 kWη = 88%cos φ = 0.8VL = 415 V
IL = A
2.Three-phase powerHard
A balanced three-phase load takes 300 kW at a power factor of 0.75 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 300 kWpf1 = 0.75pf2 = 0.98VL = 690 Vf = 50 Hz
Cph = µF
3.TransformersMedium
An ideal transformer with a turns ratio N₁:N₂ = 5:1 has 1200 V applied to its primary winding. An 8 Ω resistor is connected across the secondary winding. Find the primary current I1.
N1:N2 = 5:1V1 = 1200 VRL = 8 Ω
I1 = A
4.TransformersHard
A single-phase 200 kVA transformer has a core loss of 1600 W and a copper loss of 4800 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.
A single-phase motor takes 15 kW at a power factor of 0.75 lagging from a 230 V supply. Find the line current I.
P = 15 kWpf = 0.75V = 230 V
I = A
6.AC power & power factorHard
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
P = 50 kWpf1 = 0.65pf2 = 0.98V = 400 Vf = 50 Hz
C = µF
7.AC impedance & phasorsMedium
A series RLC circuit is connected to a 50 V (rms), 500 Hz supply. Find the power factor cos φ of the circuit.
V = 50 V (rms)f = 500 HzR = 15 ΩL = 50 mHC = 4.7 µF
cos φ =
8.AC impedance & phasorsHard
A series RLC circuit is connected to a 230 V (rms), 1000 Hz supply. Find the rms current I.
V = 230 V (rms)f = 1000 HzR = 15 ΩL = 50 mHC = 4.7 µF
I = A
9.DC motorsMedium
A DC motor with k = 2 V·s/rad runs from 240 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.
V = 240 Vk = 2 V·s/rad
n0 = rpm
10.DC motorsHard
A small DC motor has an armature resistance of 1.5 Ω and runs from 24 V. Neglecting rotational losses, find the largest mechanical power Pmax it can develop at any speed.
V = 24 VRa = 1.5 Ω
Pmax = W
3Solutions
1.Three-phase power
Answer: IL = 217.4 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 110/0.88 = 125 kW
Line current
IL = Pin/(√3·VL·cos φ) = 125000/(√3·415·0.8) = 217.4 A
Answer
IL = 217.4 A
2.Three-phase power
Answer: Cph = 453.9 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 300·tan(acos 0.75) = 300·0.8819 = 264.6 kvar
Q2 = 300·tan(acos 0.98) = 300·0.2031 = 60.92 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 203.7 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Secondary voltage and current
V2 = 1200/5 = 240 V
I2 = 240/8 = 30 A
Primary current
An ideal transformer has no losses: V₁·I₁ = V₂·I₂.
I1 = I2/5 = 6 A
Answer
I1 = 6 A
Check: the load seen from the primary is a²·RL = 200 Ω, and 1200/200 gives the same current.
4.Transformers
Answer: Ploss = 1900 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.
Copper loss at this load
Pcu = x²·Pcu,fl = 0.0625·4800 = 300 W
Total losses
The core loss is the same at any load.
Ploss = 1600 + 300 = 1900 W
Answer
Ploss = 1900 W
The efficiency at this load is η = 95.47%.
5.AC power & power factor
Answer: I = 86.96 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Line current
Only the real part of the power does work, so divide by the power factor.
I = P/(V·cos φ) = 15000/(230·0.75) = 86.96 A
Answer
I = 86.96 A
6.AC power & power factor
Answer: C = 961 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 50·tan(49.46°) = 58.46 kvar
Q2 = P·tan φ2 = 50·tan(11.48°) = 10.15 kvar
QC = Q1 − Q2 = 48.3 kvar
Capacitance
A capacitor across the supply delivers Q = V²·ωC.
C = QC/(2πf·V²) = 48304/(2π·50·400²) = 961 µF
Answer
C = 961 µF
7.AC impedance & phasors
Answer: cos φ = 0.1656
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
XL = 157.1 Ω, XC = 67.73 Ω
Impedance
|Z| = √(15² + (89.35)²) = 90.6 Ω
Power factor
cos φ = R/|Z| = 15/90.6 = 0.1656
The circuit is inductive, so the power factor is lagging.
Answer
cos φ = 0.1656
8.AC impedance & phasors
Answer: I = 0.8194 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·1000 = 6283 rad/s
XL = ωL = 6283·0.05 = 314.2 Ω
XC = 1/(ωC) = 1/(6283·4.7·10⁻⁶) = 33.86 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 230/280.7 = 0.8194 A
Answer
I = 0.8194 A
9.DC motors
Answer: n0 = 1146 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load speed
ω₀ = V/k = 240/2 = 120 rad/s
n0 = 60·120/(2π) = 1146 rpm
Answer
n0 = 1146 rpm
10.DC motors
Answer: Pmax = 96 W
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Power as a function of the back-EMF
P(E) = E·(V − E)/Ra
dP/dE = 0 → E = V/2 = 12 V
Maximum power
Pmax = (V/2)²/Ra = V²/(4Ra) = 24²/(4·1.5) = 96 W
Answer
Pmax = 96 W
At this point the efficiency is only 50 %, so real motors run well above half speed.