Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 400 VIL​ = ?M15 kW, η = 94%cos φ = 0.9

A three-phase induction motor delivers 15 kW of mechanical output power at full load. At this load its efficiency is 94% and its power factor is 0.9 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.

Pout = 15 kWη = 94%cos φ = 0.9VL = 400 V
IL = A
2.Three-phase powerHard
P = 75 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 75 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 75 kWpf1 = 0.75pf2 = 0.98VL = 480 Vf = 60 Hz
Cph = µF
3.TransformersMedium
10000 V400 VIHV​ILV​ = ?25 kVA

A single-phase 25 kVA, 10000/400 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.

S = 25 kVAV1 = 10000 VV2 = 400 V
ILV = A
4.TransformersHard
200 kVA

A single-phase 200 kVA transformer has a core loss of 1200 W and a copper loss of 4800 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?

S = 200 kVAPcore = 1200 WPcu,fl = 4800 W
Sη,max = kVA
5.AC power & power factorMedium
230 V16 kW, 0.8218 kW, 0.85I

Two loads are connected in parallel to a 230 V single-phase supply: a 6 kW load at a power factor of 0.8 lagging and an 18 kW load at a power factor of 0.85 leading. Find the overall power factor cos φ seen by the supply.

V = 230 VP1 = 6 kW, pf1 = 0.8 laggingP2 = 18 kW, pf2 = 0.85 leading
cos φ =
6.AC power & power factorHard
12 V1000 HzRs​ = 50 ΩXs​ = j10 ΩZL​ = ?

A 12 V (rms), 1000 Hz source has an internal impedance Zs = 50 + j10 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.

Vs = 12 V (rms)f = 1000 HzZs = 50 + j10 Ω
Pmax = W
7.AC impedance & phasorsMedium
120 V1000 HzR = 25 ΩL = 100 mHC = 1 µFI

A series RLC circuit is connected to a 120 V (rms), 1000 Hz supply. Find the rms current I.

V = 120 V (rms)f = 1000 HzR = 25 ΩL = 100 mHC = 1 µF
I = A
8.AC impedance & phasorsHard
VfR = 20 ΩL = 10 mHC = 0.47 µF

A series RLC circuit has R = 20 Ω, L = 10 mH and C = 0.47 µF. Find its bandwidth B (the width of the band between the half-power frequencies), in Hz.

R = 20 ΩL = 10 mHC = 0.47 µF
B = Hz
9.DC motorsMedium
T (N·m)n (rpm)9 N·mn0​nFL​

A DC motor (k = 0.6 V·s/rad, Ra = 0.4 Ω) runs from 110 V. At full load it draws 15 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.

V = 110 Vk = 0.6 V·s/radRa = 0.4 ΩIFL = 15 A
SR = %
10.DC motorsHard
+−220 VD = ?Ra​ = 0.2 ΩM+−En = 800 rpmT = 24 N·m

A DC chopper feeds a motor (k = 0.6 V·s/rad, Ra = 0.2 Ω) from a 220 V DC bus. The average armature voltage is D·220 V. Find the duty cycle D that runs the motor at 800 rpm with a load of 24 N·m.

Vdc = 220 Vk = 0.6 V·s/radRa = 0.2 ΩT = 24 N·mn = 800 rpm
D = %

3Solutions

1.Three-phase power

Answer: IL = 25.59 A

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Electrical input power

Pin = Pout/η = 15/0.94 = 15.96 kW

Line current

IL = Pin/(√3·VL·cos φ) = 15957/(√3·400·0.9) = 25.59 A

Answer

IL = 25.59 A
2.Three-phase power

Answer: Cph = 586.2 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 75·tan(acos 0.75) = 75·0.8819 = 66.14 kvar
Q2 = 75·tan(acos 0.98) = 75·0.2031 = 15.23 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 50.91 kvar

Capacitance per phase

In a Y bank each capacitor is connected between a line and the star point.

V = 480/√3 = 277.1 V, ω = 2π·60 = 377 rad/s
Cph = (QC/3)/(ω·V²) = 16971/(377·277.1²) = 586.2 µF

Answer

Cph = 586.2 µF
3.Transformers

Answer: ILV = 62.5 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Rated current

Both windings carry the same apparent power.

ILV = S/V = 25000/400 = 62.5 A

Answer

ILV = 62.5 A
4.Transformers

Answer: Sη,max = 100 kVA

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss equals core loss

x²·4800 = 1200 → x = √(1200/4800) = 0.5

Load at maximum efficiency

Sη,max = x·S = 0.5·200 = 100 kVA

Answer

Sη,max = 100 kVA
5.AC power & power factor

Answer: cos φ = 0.9636

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power of each load

A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).

Q1 = 6·tan(arccos 0.8) = 4.5 kvar
Q2 = −18·tan(arccos 0.85) = −11.16 kvar

Totals

P = 6 + 18 = 24 kW
Q = 4.5 + (−11.16) = −6.655 kvar
S = √(24² + (−6.655)²) = 24.91 kVA

Overall power factor

cos φ = P/S = 24/24.91 = 0.9636 leading

Answer

cos φ = 0.9636
6.AC power & power factor

Answer: Pmax = 0.72 W

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Conjugate match

The load reactance cancels the source reactance, and the load resistance equals the source resistance.

ZL = Zs* = 50 − j10 Ω

Maximum power

I = Vs/(2Rs) = 12/100 = 0.12 A
Pmax = I²·RL = Vs²/(4Rs) = 12²/(4·50) = 0.72 W

Answer

Pmax = 0.72 W
7.AC impedance & phasors

Answer: I = 0.2554 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·1000 = 6283 rad/s
XL = ωL = 6283·0.1 = 628.3 Ω
XC = 1/(ωC) = 1/(6283·1·10⁻⁶) = 159.2 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(25² + (469.2)²) = 469.8 Ω

Current

The same current flows through every element of a series circuit.

I = V/|Z| = 120/469.8 = 0.2554 A

Answer

I = 0.2554 A
8.AC impedance & phasors

Answer: B = 318.3 Hz

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonant frequency

f0 = 1/(2π·√(0.01·0.47·10⁻⁶)) = 2322 Hz

Quality factor

Q compares the reactance at resonance with the resistance: Q = ω₀L/R.

Q = (1/R)·√(L/C) = (1/20)·√(0.01/(0.47·10⁻⁶)) = 7.293

Bandwidth

B = f0/Q = 2322/7.293 = 318.3 Hz

Answer

B = 318.3 Hz
9.DC motors

Answer: SR = 5.769 %

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

No-load and full-load speed

n₀ = 60·110/(2π·0.6) = 1751 rpm
nFL = 60·(110 − 15·0.4)/(2π·0.6) = 1655 rpm

Speed regulation

SR = (1751 − 1655)/1655·100 = 5.769 %

Answer

SR = 5.769 %
10.DC motors

Answer: D = 26.48 %

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Required armature voltage

Va = 0.6·83.78 + 40·0.2 = 58.27 V

Duty cycle

D = 58.27/220 = 26.48 %

Answer

D = 26.48 %

ExamProblems · examproblems.com/courses/power-systems