Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VNZ = 15 + j20 Ωper phase

A balanced Y-connected load with an impedance of 15 + j20 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.

VL = 208 VZ = 15 + j20 Ω per phase
P = kW
2.Three-phase powerHard
P = 75 kWφ1​S1​Q2​QC​ = ?

A balanced three-phase load takes 75 kW at a power factor of 0.8 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.

P = 75 kWpf1 = 0.8pf2 = 0.95VL = 480 Vf = 60 Hz
QC = kvar
3.TransformersMedium
6600 V230 VIHV​ILV​ = ?15 kVA

A single-phase 15 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.

S = 15 kVAV1 = 6600 VV2 = 230 V
ILV = A
4.TransformersHard
200 kVA

A single-phase 200 kVA transformer has a core loss of 1000 W and a copper loss of 4000 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?

S = 200 kVAPcore = 1000 WPcu,fl = 4000 W
Sη,max = kVA
5.AC power & power factorMedium
240 VZ15 + j20 ΩI

A load with impedance Z = 15 + j20 Ω is connected to a 240 V (rms) single-phase supply. Find the reactive power Q it absorbs.

V = 240 VZ = 15 + j20 Ω
Q = var
6.AC power & power factorHard
P1​ = 94 kWQ1​S1​φ

A 200 kVA single-phase transformer supplies a load of 94 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?

Smax = 200 kVAP1 = 94 kWpf1 = 0.75
ΔP = kW
7.AC impedance & phasorsMedium
Vf0​ = 60 HzRL = 5 mHC = ?

A series RLC circuit with L = 5 mH must resonate at 60 Hz. Find the capacitance C needed.

f0 = 60 HzL = 5 mH
C = µF
8.AC impedance & phasorsHard
50 V60 HzR = 25 ΩL = 50 mHC = 22 µFI

A series RLC circuit is connected to a 50 V (rms), 60 Hz supply. Find the rms current I.

V = 50 V (rms)f = 60 HzR = 25 ΩL = 50 mHC = 22 µF
I = A
9.DC motorsMedium
T (N·m)n (rpm)Tst​ = ?n0​

A DC motor with k = 1 N·m/A and Ra = 1.5 Ω is connected to 120 V. Find its stall torque Tstall, the torque at zero speed.

V = 120 Vk = 1 N·m/ARa = 1.5 Ω
Tstall = N·m
10.DC motorsHard
+−24 VRa​ = 1.2 ΩM+−EωT

A small DC motor has an armature resistance of 1.2 Ω and runs from 24 V. Neglecting rotational losses, find the largest mechanical power Pmax it can develop at any speed.

V = 24 VRa = 1.2 Ω
Pmax = W

3Solutions

1.Three-phase power

Answer: P = 1.038 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Phase voltage

Vph = 208/√3 = 120.1 V

Phase current

|Z| = √(15² + 20²) = 25 Ω
Iph = 120.1/25 = 4.804 A

Total real power

Only the resistive part of each impedance absorbs real power.

P = 3·Iph²·R = 3·4.804²·15 = 1.038 kW

Answer

P = 1.038 kW

Check: cos φ = R/|Z| = 0.6, and √3·VL·IL·cos φ gives the same power.

2.Three-phase power

Answer: QC = 31.6 kvar

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 75·tan(acos 0.8) = 75·0.75 = 56.25 kvar
Q2 = 75·tan(acos 0.95) = 75·0.3287 = 24.65 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 31.6 kvar

Answer

QC = 31.6 kvar
3.Transformers

Answer: ILV = 65.22 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Rated current

Both windings carry the same apparent power.

ILV = S/V = 15000/230 = 65.22 A

Answer

ILV = 65.22 A
4.Transformers

Answer: Sη,max = 100 kVA

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss equals core loss

x²·4000 = 1000 → x = √(1000/4000) = 0.5

Load at maximum efficiency

Sη,max = x·S = 0.5·200 = 100 kVA

Answer

Sη,max = 100 kVA
5.AC power & power factor

Answer: Q = 1843 var

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Current

|Z| = √(15² + 20²) = 25 Ω
I = V/|Z| = 240/25 = 9.6 A

Reactive power

Q = I²·X = 9.6²·20 = 1843 var

Answer

Q = 1843 var
6.AC power & power factor

Answer: ΔP = 88.01 kW

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power of the existing load

Q1 = 94·tan(arccos 0.75) = 82.9 kvar

Largest total real power

At full rating S = Smax, and Q is unchanged by the resistive load.

P = √(Smax² − Q1²) = √(200² − 82.9²) = 182 kW

Extra real power

ΔP = 182 − 94 = 88.01 kW

Answer

ΔP = 88.01 kW
7.AC impedance & phasors

Answer: C = 1407 µF

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonance condition

At resonance the inductive and capacitive reactances cancel: ωL = 1/(ωC).

ω₀ = 2π·60 = 377 rad/s
C = 1/(ω₀²·L) = 1/(377²·0.005) = 1407 µF

Answer

C = 1407 µF
8.AC impedance & phasors

Answer: I = 0.4773 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·60 = 377 rad/s
XL = ωL = 377·0.05 = 18.85 Ω
XC = 1/(ωC) = 1/(377·22·10⁻⁶) = 120.6 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(25² + (−101.7)²) = 104.7 Ω

Current

The same current flows through every element of a series circuit.

I = V/|Z| = 50/104.7 = 0.4773 A

Answer

I = 0.4773 A
9.DC motors

Answer: Tstall = 80 N·m

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Stall current

Ia = V/Ra = 120/1.5 = 80 A

Stall torque

Tstall = 1·80 = 80 N·m

Answer

Tstall = 80 N·m
10.DC motors

Answer: Pmax = 120 W

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Power as a function of the back-EMF

P(E) = E·(V − E)/Ra
dP/dE = 0 → E = V/2 = 12 V

Maximum power

Pmax = (V/2)²/Ra = V²/(4Ra) = 24²/(4·1.2) = 120 W

Answer

Pmax = 120 W

At this point the efficiency is only 50 %, so real motors run well above half speed.

ExamProblems · examproblems.com/courses/power-systems