Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VNZ = 3 + j4 Ωper phase

A balanced Y-connected load with an impedance of 3 + j4 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.

VL = 208 VZ = 3 + j4 Ω per phase
P = kW
2.Three-phase powerHard
P = 50 kWφ1​S1​Q2​QC​ = ?

A balanced three-phase load takes 50 kW at a power factor of 0.78 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.

P = 50 kWpf1 = 0.78pf2 = 0.98VL = 690 Vf = 50 Hz
QC = kvar
3.TransformersMedium
2400 V240 VIHV​ = ?ILV​100 kVA

A single-phase 100 kVA, 2400/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.

S = 100 kVAV1 = 2400 VV2 = 240 V
IHV = A
4.TransformersHard
pf 0.8150 kVA, 25% load

A single-phase 150 kVA transformer has a core loss of 600 W and a copper loss of 900 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.

S = 150 kVAPcore = 600 WPcu,fl = 900 Wx = 0.25pf = 0.8
Ploss = W
5.AC power & power factorMedium
P = 26 kWQSφ

A single-phase motor takes 26 kW at a power factor of 0.65 lagging from a 240 V supply. Find the line current I.

P = 26 kWpf = 0.65V = 240 V
I = A
6.AC power & power factorHard
P = 30 kWQ1​S1​φ1​QC​

A single-phase load takes 30 kW at a power factor of 0.75 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.

P = 30 kWpf1 = 0.75pf2 = 0.98V = 400 Vf = 60 Hz
C = µF
7.AC impedance & phasorsMedium
Vf0​ = 100 HzRL = ?C = 47 µF

A series RLC circuit with C = 47 µF must resonate at 100 Hz. Find the inductance L needed.

f0 = 100 HzC = 47 µF
L = mH
8.AC impedance & phasorsHard
24 Vf0​R = 15 ΩL = 100 mHC = 0.47 µF

A series RLC circuit is driven by a 24 V (rms) source whose frequency is set to the resonant frequency of the circuit. Find the rms voltage VL across the inductor.

V = 24 V (rms)R = 15 ΩL = 100 mHC = 0.47 µF
VL = V
9.DC motorsMedium
T (N·m)n (rpm)Tst​ = ?n0​

A DC motor with k = 0.4 N·m/A and Ra = 0.4 Ω is connected to 110 V. Find its stall torque Tstall, the torque at zero speed.

V = 110 Vk = 0.4 N·m/ARa = 0.4 Ω
Tstall = N·m
10.DC motorsHard
+−240 VRst​ = ?Ra​ = 0.25 Ω50 AM+−E = 0n = 0T

A 240 V DC motor has an armature resistance of 0.25 Ω. Find the series starting resistance Rst that limits the starting current to 50 A.

V = 240 VRa = 0.25 ΩImax = 50 A
Rst = Ω

3Solutions

1.Three-phase power

Answer: P = 5.192 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Phase voltage

Vph = 208/√3 = 120.1 V

Phase current

|Z| = √(3² + 4²) = 5 Ω
Iph = 120.1/5 = 24.02 A

Total real power

Only the resistive part of each impedance absorbs real power.

P = 3·Iph²·R = 3·24.02²·3 = 5.192 kW

Answer

P = 5.192 kW

Check: cos φ = R/|Z| = 0.6, and √3·VL·IL·cos φ gives the same power.

2.Three-phase power

Answer: QC = 29.96 kvar

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 50·tan(acos 0.78) = 50·0.8023 = 40.11 kvar
Q2 = 50·tan(acos 0.98) = 50·0.2031 = 10.15 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 29.96 kvar

Answer

QC = 29.96 kvar
3.Transformers

Answer: IHV = 41.67 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Rated current

Both windings carry the same apparent power.

IHV = S/V = 100000/2400 = 41.67 A

Answer

IHV = 41.67 A
4.Transformers

Answer: Ploss = 656.3 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss at this load

Pcu = x²·Pcu,fl = 0.0625·900 = 56.25 W

Total losses

The core loss is the same at any load.

Ploss = 600 + 56.25 = 656.3 W

Answer

Ploss = 656.3 W

The efficiency at this load is η = 97.86%.

5.AC power & power factor

Answer: I = 166.7 A

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Line current

Only the real part of the power does work, so divide by the power factor.

I = P/(V·cos φ) = 26000/(240·0.65) = 166.7 A

Answer

I = 166.7 A
6.AC power & power factor

Answer: C = 337.6 µF

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = P·tan φ1 = 30·tan(41.41°) = 26.46 kvar
Q2 = P·tan φ2 = 30·tan(11.48°) = 6.092 kvar
QC = Q1 − Q2 = 20.37 kvar

Capacitance

A capacitor across the supply delivers Q = V²·ωC.

C = QC/(2πf·V²) = 20366/(2π·60·400²) = 337.6 µF

Answer

C = 337.6 µF
7.AC impedance & phasors

Answer: L = 53.89 mH

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonance condition

At resonance the inductive and capacitive reactances cancel: ωL = 1/(ωC).

ω₀ = 2π·100 = 628.3 rad/s
L = 1/(ω₀²·C) = 1/(628.3²·47·10⁻⁶) = 53.89 mH

Answer

L = 53.89 mH
8.AC impedance & phasors

Answer: VL = 738 V

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonance

At resonance the reactances cancel, so the impedance is just R.

ω₀ = 1/√(LC) = 1/√(0.1·0.47·10⁻⁶) = 4613 rad/s
I = V/R = 24/15 = 1.6 A

Voltage across the inductor

XL = ω₀L = 4613·0.1 = 461.3 Ω
VL = I·XL = 1.6·461.3 = 738 V

Answer

VL = 738 V

This is Q = 30.75 times the supply voltage.

9.DC motors

Answer: Tstall = 110 N·m

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Stall current

Ia = V/Ra = 110/0.4 = 275 A

Stall torque

Tstall = 0.4·275 = 110 N·m

Answer

Tstall = 110 N·m
10.DC motors

Answer: Rst = 4.55 Ω

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Total resistance

Ra + Rst = 240/50 = 4.8 Ω

Starting resistor

Rst = 4.8 − 0.25 = 4.55 Ω

Answer

Rst = 4.55 Ω

The resistor is cut out step by step as the motor speeds up and the back-EMF grows.

ExamProblems · examproblems.com/courses/power-systems