1Formulas and methods
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
Transformers
Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
AC impedance & phasors
Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z
Method
Convert the frequency: ω = 2πf.
Find each reactance: XL = ωL and XC = 1/(ωC).
Add impedances like resistors, with Z = R + jX.
Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
2Practice problems
1.Three-phase powerMedium
A balanced Δ-connected load with an impedance of 7 + j24 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.
VL = 208 VZ = 7 + j24 Ω per phase
P = kW
2.Three-phase powerHard
A balanced three-phase load takes 75 kW at a power factor of 0.8 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
P = 75 kWpf1 = 0.8pf2 = 0.9VL = 690 Vf = 50 Hz
Cph = µF
3.TransformersMedium
An ideal transformer with a turns ratio N₁:N₂ = 5:1 has 600 V applied to its primary winding. A 12 Ω resistor is connected across the secondary winding. Find the primary current I1.
N1:N2 = 5:1V1 = 600 VRL = 12 Ω
I1 = A
4.TransformersHard
A single-phase 250 kVA transformer has a core loss of 2000 W. At rated load and a power factor of 0.95 lagging its efficiency is 98.5%. Find the full-load copper loss Pcu,fl in watts.
S = 250 kVAPcore = 2000 Wpf = 0.95η = 98.5%
Pcu,fl = W
5.AC power & power factorMedium
An inductive load takes 11 A and 2376 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
V = 240 VI = 11 AP = 2376 W
X = Ω
6.AC power & power factorHard
A single-phase load takes 30 kW at a power factor of 0.6 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
P = 30 kWpf1 = 0.6pf2 = 0.98V = 240 Vf = 50 Hz
Inew = A
7.AC impedance & phasorsMedium
A resistor and an inductor are connected in parallel across a 100 V (rms), 50 Hz supply. Find the phase angle φ of the impedance, in degrees (positive when the current lags the voltage).
V = 100 V (rms)f = 50 HzR = 30 ΩL = 100 mH
φ = °
8.AC impedance & phasorsHard
A resistor R1 is connected in series with a parallel combination of R2 and a capacitor C, across a 12 V (rms), 200 Hz supply. Find the rms current I.
V = 12 V (rms)f = 200 HzR1 = 15 ΩR2 = 150 ΩC = 10 µF
I = A
9.DC motorsMedium
A DC motor (k = 0.15 N·m/A, Ra = 0.4 Ω) runs from 24 V and drives a load torque of 0.3 N·m. Find its speed n in rpm.
V = 24 Vk = 0.15 N·m/ARa = 0.4 ΩT = 0.3 N·m
n = rpm
10.DC motorsHard
A separately excited DC motor on 120 V (Ra = 0.2 Ω) runs at 900 rpm with an armature current of 30 A. The load changes and the current becomes 60 A, with the field unchanged. Find the new speed n2.
V = 120 VRa = 0.2 Ωn1 = 900 rpmIa1 = 30 AIa2 = 60 A
n2 = rpm
3Solutions
1.Three-phase power
Answer: P = 1.454 kW
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Phase voltage
Vph = VL = 208 V
Phase current
|Z| = √(7² + 24²) = 25 Ω
Iph = 208/25 = 8.32 A
Total real power
Only the resistive part of each impedance absorbs real power.
P = 3·Iph²·R = 3·8.32²·7 = 1.454 kW
Answer
P = 1.454 kW
Check: cos φ = R/|Z| = 0.28, and √3·VL·IL·cos φ gives the same power.
2.Three-phase power
Answer: Cph = 44.41 µF
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 75·tan(acos 0.8) = 75·0.75 = 56.25 kvar
Q2 = 75·tan(acos 0.9) = 75·0.4843 = 36.32 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 19.93 kvar
Capacitance per phase
In a Δ bank each capacitor is connected between two lines.
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Secondary voltage and current
V2 = 600/5 = 120 V
I2 = 120/12 = 10 A
Primary current
An ideal transformer has no losses: V₁·I₁ = V₂·I₂.
I1 = I2/5 = 2 A
Answer
I1 = 2 A
Check: the load seen from the primary is a²·RL = 300 Ω, and 600/300 gives the same current.
4.Transformers
Answer: Pcu,fl = 1617 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.
Output and input power
Pout = 250·0.95 = 237.5 kW
Pin = 237500/0.985 = 241117 W
Total and copper losses
Ploss = 241117 − 237500 = 3617 W
Pcu,fl = 3617 − 2000 = 1617 W
Answer
Pcu,fl = 1617 W
5.AC power & power factor
Answer: X = 9.51 Ω
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Resistance from the real power
R = P/I² = 2376/11² = 19.64 Ω
Reactance from the impedance
|Z| = V/I = 240/11 = 21.82 Ω
X = √(|Z|² − R²) = √(21.82² − 19.64²) = 9.51 Ω
Answer
X = 9.51 Ω
6.AC power & power factor
Answer: Inew = 127.6 A
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power before and after
The real power P does not change; only the reactive power drawn from the supply does.
Q1 = P·tan φ1 = 30·tan(53.13°) = 40 kvar
Q2 = P·tan φ2 = 30·tan(11.48°) = 6.092 kvar
QC = Q1 − Q2 = 33.91 kvar
New line current
Inew = P/(V·cos φ2) = 30000/(240·0.98) = 127.6 A
Answer
Inew = 127.6 A
7.AC impedance & phasors
Answer: φ = 43.68 °
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactance
XL = ωL = 2π·50·0.1 = 31.42 Ω
Branch currents
Both branches are connected straight across the supply, so each sees the full voltage V.
IR = V/R = 100/30 = 3.333 A
IX = V/XL = 100/31.42 = 3.183 A
Total current
The resistor current is in phase with V and the reactive current is 90° out of phase, so they add like the sides of a right triangle.
I = √(IR² + IX²) = √(3.333² + 3.183²) = 4.609 A
Phase angle
The inductor current lags V, so the total current lags and the angle is positive.
φ = arctan(IX/IR) = arctan(3.183/3.333) = 43.68°
Answer
φ = 43.68°
8.AC impedance & phasors
Answer: I = 0.153 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactance
XC = 1/(2π·200·10·10⁻⁶) = 79.58 Ω
Parallel combination
Multiply top and bottom by the complex conjugate to split Zp into real and imaginary parts.
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
Armature current
Ia = T/k = 0.3/0.15 = 2 A
Back-EMF and speed
E = 24 − 2·0.4 = 23.2 V
ω = E/k = 154.7 rad/s → n = 1477 rpm
Answer
n = 1477 rpm
10.DC motors
Answer: n2 = 852.6 rpm
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.