Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 400 VIL​ = ?M55 kW, η = 95%cos φ = 0.84

A three-phase induction motor delivers 55 kW of mechanical output power at full load. At this load its efficiency is 95% and its power factor is 0.84 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.

Pout = 55 kWη = 95%cos φ = 0.84VL = 400 V
IL = A
2.Three-phase powerHard
P = 50 kWφ1​S1​Q2​QC​ = ?

A balanced three-phase load takes 50 kW at a power factor of 0.72 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.

P = 50 kWpf1 = 0.72pf2 = 0.98VL = 415 Vf = 50 Hz
QC = kvar
3.TransformersMedium
RL​ = 10 Ω1012400 VV2​I1​ = ?I2​

An ideal transformer with a turns ratio N₁:N₂ = 10:1 has 2400 V applied to its primary winding. A 10 Ω resistor is connected across the secondary winding. Find the primary current I1.

N1:N2 = 10:1V1 = 2400 VRL = 10 Ω
I1 = A
4.TransformersHard
pf 0.8200 kVA, 50% load

A single-phase 200 kVA transformer has a core loss of 1600 W and a copper loss of 3200 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.

S = 200 kVAPcore = 1600 WPcu,fl = 3200 Wx = 0.5pf = 0.8
Ploss = W
5.AC power & power factorMedium
400 V126 kW, 0.75217 kW, 0.85I

Two loads are connected in parallel to a 400 V single-phase supply: a 26 kW load at a power factor of 0.75 lagging and a 17 kW load at a power factor of 0.85 leading. Find the overall power factor cos φ seen by the supply.

V = 400 VP1 = 26 kW, pf1 = 0.75 laggingP2 = 17 kW, pf2 = 0.85 leading
cos φ =
6.AC power & power factorHard
230 V50 Hzload8 kW, 0.6C100 µFI

A single-phase load takes 8 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.

P = 8 kWpf1 = 0.6V = 230 Vf = 50 HzC = 100 µF
cos φ =
7.AC impedance & phasorsMedium
50 V100 HzR = 80 ΩL = 50 mHI

A resistor and an inductor are connected in parallel across a 50 V (rms), 100 Hz supply. Find the magnitude of the impedance |Z|.

V = 50 V (rms)f = 100 HzR = 80 ΩL = 50 mH
|Z| = Ω
8.AC impedance & phasorsHard
120 V100 HzR = 80 ΩL = 200 mHC = 1 µFI

A series RLC circuit is connected to a 120 V (rms), 100 Hz supply. Find the rms current I.

V = 120 V (rms)f = 100 HzR = 80 ΩL = 200 mHC = 1 µF
I = A
9.DC motorsMedium
T (N·m)n (rpm)n0​ = ?

A DC motor with k = 0.3 V·s/rad runs from 48 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.

V = 48 Vk = 0.3 V·s/rad
n0 = rpm
10.DC motorsHard
+−110 VRa​ = 0.5 ΩM+−En = ?T = 18 N·m

A separately excited DC motor (k = 1.5 V·s/rad at full field, Ra = 0.5 Ω, V = 110 V) drives a constant load torque of 18 N·m. The field flux is reduced to 80 % of its full value. Find the new speed n.

V = 110 Vk = 1.5 V·s/radRa = 0.5 ΩT = 18 N·mΦ = 80 %
n = rpm

3Solutions

1.Three-phase power

Answer: IL = 99.48 A

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Electrical input power

Pin = Pout/η = 55/0.95 = 57.89 kW

Line current

IL = Pin/(√3·VL·cos φ) = 57895/(√3·400·0.84) = 99.48 A

Answer

IL = 99.48 A
2.Three-phase power

Answer: QC = 38.04 kvar

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 50·tan(acos 0.72) = 50·0.9639 = 48.19 kvar
Q2 = 50·tan(acos 0.98) = 50·0.2031 = 10.15 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 38.04 kvar

Answer

QC = 38.04 kvar
3.Transformers

Answer: I1 = 2.4 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Secondary voltage and current

V2 = 2400/10 = 240 V
I2 = 240/10 = 24 A

Primary current

An ideal transformer has no losses: V₁·I₁ = V₂·I₂.

I1 = I2/10 = 2.4 A

Answer

I1 = 2.4 A

Check: the load seen from the primary is a²·RL = 1000 Ω, and 2400/1000 gives the same current.

4.Transformers

Answer: Ploss = 2400 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss at this load

Pcu = x²·Pcu,fl = 0.25·3200 = 800 W

Total losses

The core loss is the same at any load.

Ploss = 1600 + 800 = 2400 W

Answer

Ploss = 2400 W

The efficiency at this load is η = 97.09%.

5.AC power & power factor

Answer: cos φ = 0.9609

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power of each load

A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).

Q1 = 26·tan(arccos 0.75) = 22.93 kvar
Q2 = −17·tan(arccos 0.85) = −10.54 kvar

Totals

P = 26 + 17 = 43 kW
Q = 22.93 + (−10.54) = 12.39 kvar
S = √(43² + 12.39²) = 44.75 kVA

Overall power factor

cos φ = P/S = 43/44.75 = 0.9609 lagging

Answer

cos φ = 0.9609
6.AC power & power factor

Answer: cos φ = 0.6642

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = 8·tan(arccos 0.6) = 10.67 kvar
QC = V²·2πf·C = 230²·2π·50·100·10⁻⁶ = 1662 var = 1.662 kvar
Q2 = 10.67 − 1.662 = 9.005 kvar

New apparent power

S2 = √(8² + 9.005²) = 12.05 kVA

New power factor

cos φ = P/S2 = 8/12.05 = 0.6642

Answer

cos φ = 0.6642
7.AC impedance & phasors

Answer: |Z| = 29.24 Ω

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactance

XL = ωL = 2π·100·0.05 = 31.42 Ω

Branch currents

Both branches are connected straight across the supply, so each sees the full voltage V.

IR = V/R = 50/80 = 0.625 A
IX = V/XL = 50/31.42 = 1.592 A

Total current

The resistor current is in phase with V and the reactive current is 90° out of phase, so they add like the sides of a right triangle.

I = √(IR² + IX²) = √(0.625² + 1.592²) = 1.71 A

Impedance

|Z| = V/I = 50/1.71 = 29.24 Ω

Answer

|Z| = 29.24 Ω
8.AC impedance & phasors

Answer: I = 0.08174 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·100 = 628.3 rad/s
XL = ωL = 628.3·0.2 = 125.7 Ω
XC = 1/(ωC) = 1/(628.3·1·10⁻⁶) = 1592 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(80² + (−1466)²) = 1468 Ω

Current

The same current flows through every element of a series circuit.

I = V/|Z| = 120/1468 = 0.08174 A

Answer

I = 0.08174 A
9.DC motors

Answer: n0 = 1528 rpm

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

No-load speed

ω₀ = V/k = 48/0.3 = 160 rad/s
n0 = 60·160/(2π) = 1528 rpm

Answer

n0 = 1528 rpm
10.DC motors

Answer: n = 815.7 rpm

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Weakened motor constant

k₂ = 0.8·1.5 = 1.2 V·s/rad

New armature current

Ia = 18/1.2 = 15 A

New speed

ω = (110 − 15·0.5)/1.2 = 85.42 rad/s → n = 815.7 rpm

Answer

n = 815.7 rpm

Field weakening is how a DC drive runs above its base speed.

ExamProblems · examproblems.com/courses/power-systems