Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 208 VNZ = 6 + j8 Ωper phase

A balanced Y-connected load with an impedance of 6 + j8 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.

VL = 208 VZ = 6 + j8 Ω per phase
P = kW
2.Three-phase powerHard
P = 100 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 100 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 100 kWpf1 = 0.75pf2 = 0.92VL = 480 Vf = 50 Hz
Cph = µF
3.TransformersMedium
RL​ = 12 Ω51600 VV2​I1​ = ?I2​

An ideal transformer with a turns ratio N₁:N₂ = 5:1 has 600 V applied to its primary winding. A 12 Ω resistor is connected across the secondary winding. Find the primary current I1.

N1:N2 = 5:1V1 = 600 VRL = 12 Ω
I1 = A
4.TransformersHard
100 kVA

A single-phase 100 kVA transformer has a core loss of 300 W and a copper loss of 450 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?

S = 100 kVAPcore = 300 WPcu,fl = 450 W
Sη,max = kVA
5.AC power & power factorMedium
240 V12 kW, 0.65212 kW, 0.95I

Two loads are connected in parallel to a 240 V single-phase supply: a 2 kW load at a power factor of 0.65 lagging and a 12 kW load at a power factor of 0.95 leading. Find the overall power factor cos φ seen by the supply.

V = 240 VP1 = 2 kW, pf1 = 0.65 laggingP2 = 12 kW, pf2 = 0.95 leading
cos φ =
6.AC power & power factorHard
50 V50 HzRs​ = 25 ΩXs​ = j3 ΩZL​ = ?

A 50 V (rms), 50 Hz source has an internal impedance Zs = 25 + j3 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.

Vs = 50 V (rms)f = 50 HzZs = 25 + j3 Ω
Pmax = W
7.AC impedance & phasorsMedium
Vf0​ = 60 HzRL = 100 mHC = ?

A series RLC circuit with L = 100 mH must resonate at 60 Hz. Find the capacitance C needed.

f0 = 60 HzL = 100 mH
C = µF
8.AC impedance & phasorsHard
120 V100 HzR = 50 ΩL = 50 mHC = 22 µFI

A series RLC circuit is connected to a 120 V (rms), 100 Hz supply. Find the rms current I.

V = 120 V (rms)f = 100 HzR = 50 ΩL = 50 mHC = 22 µF
I = A
9.DC motorsMedium
+−VRa​M+−En = 3000 rpmT = ?

A DC motor delivers 5.5 kW of mechanical power at 3000 rpm. Find the shaft torque T.

P = 5.5 kWn = 3000 rpm
T = N·m
10.DC motorsHard
+−24 VRa​ = 3 ΩM+−EωT

A small DC motor has an armature resistance of 3 Ω and runs from 24 V. Neglecting rotational losses, find the largest mechanical power Pmax it can develop at any speed.

V = 24 VRa = 3 Ω
Pmax = W

3Solutions

1.Three-phase power

Answer: P = 2.596 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Phase voltage

Vph = 208/√3 = 120.1 V

Phase current

|Z| = √(6² + 8²) = 10 Ω
Iph = 120.1/10 = 12.01 A

Total real power

Only the resistive part of each impedance absorbs real power.

P = 3·Iph²·R = 3·12.01²·6 = 2.596 kW

Answer

P = 2.596 kW

Check: cos φ = R/|Z| = 0.6, and √3·VL·IL·cos φ gives the same power.

2.Three-phase power

Answer: Cph = 629.9 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 100·tan(acos 0.75) = 100·0.8819 = 88.19 kvar
Q2 = 100·tan(acos 0.92) = 100·0.426 = 42.6 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 45.59 kvar

Capacitance per phase

In a Y bank each capacitor is connected between a line and the star point.

V = 480/√3 = 277.1 V, ω = 2π·50 = 314.2 rad/s
Cph = (QC/3)/(ω·V²) = 15197/(314.2·277.1²) = 629.9 µF

Answer

Cph = 629.9 µF
3.Transformers

Answer: I1 = 2 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Secondary voltage and current

V2 = 600/5 = 120 V
I2 = 120/12 = 10 A

Primary current

An ideal transformer has no losses: V₁·I₁ = V₂·I₂.

I1 = I2/5 = 2 A

Answer

I1 = 2 A

Check: the load seen from the primary is a²·RL = 300 Ω, and 600/300 gives the same current.

4.Transformers

Answer: Sη,max = 81.65 kVA

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss equals core loss

x²·450 = 300 → x = √(300/450) = 0.8165

Load at maximum efficiency

Sη,max = x·S = 0.8165·100 = 81.65 kVA

Answer

Sη,max = 81.65 kVA
5.AC power & power factor

Answer: cos φ = 0.9935

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power of each load

A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).

Q1 = 2·tan(arccos 0.65) = 2.338 kvar
Q2 = −12·tan(arccos 0.95) = −3.944 kvar

Totals

P = 2 + 12 = 14 kW
Q = 2.338 + (−3.944) = −1.606 kvar
S = √(14² + (−1.606)²) = 14.09 kVA

Overall power factor

cos φ = P/S = 14/14.09 = 0.9935 leading

Answer

cos φ = 0.9935
6.AC power & power factor

Answer: Pmax = 25 W

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Conjugate match

The load reactance cancels the source reactance, and the load resistance equals the source resistance.

ZL = Zs* = 25 − j3 Ω

Maximum power

I = Vs/(2Rs) = 50/50 = 1 A
Pmax = I²·RL = Vs²/(4Rs) = 50²/(4·25) = 25 W

Answer

Pmax = 25 W
7.AC impedance & phasors

Answer: C = 70.36 µF

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonance condition

At resonance the inductive and capacitive reactances cancel: ωL = 1/(ωC).

ω₀ = 2π·60 = 377 rad/s
C = 1/(ω₀²·L) = 1/(377²·0.1) = 70.36 µF

Answer

C = 70.36 µF
8.AC impedance & phasors

Answer: I = 1.857 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

ω = 2πf = 2π·100 = 628.3 rad/s
XL = ωL = 628.3·0.05 = 31.42 Ω
XC = 1/(ωC) = 1/(628.3·22·10⁻⁶) = 72.34 Ω

Impedance

In series the impedances add as complex numbers: Z = R + j(XL − XC).

|Z| = √(R² + (XL − XC)²) = √(50² + (−40.93)²) = 64.61 Ω

Current

The same current flows through every element of a series circuit.

I = V/|Z| = 120/64.61 = 1.857 A

Answer

I = 1.857 A
9.DC motors

Answer: T = 17.51 N·m

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Speed in rad/s

ω = 2π·3000/60 = 314.2 rad/s

Torque

T = P/ω = 5500/314.2 = 17.51 N·m

Answer

T = 17.51 N·m
10.DC motors

Answer: Pmax = 48 W

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Power as a function of the back-EMF

P(E) = E·(V − E)/Ra
dP/dE = 0 → E = V/2 = 12 V

Maximum power

Pmax = (V/2)²/Ra = V²/(4Ra) = 24²/(4·3) = 48 W

Answer

Pmax = 48 W

At this point the efficiency is only 50 %, so real motors run well above half speed.

ExamProblems · examproblems.com/courses/power-systems