1Formulas and methods
Three-phase power
Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η
Transformers
Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)
AC power & power factor
Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)
AC impedance & phasors
Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z
Method
Convert the frequency: ω = 2πf.
Find each reactance: XL = ωL and XC = 1/(ωC).
Add impedances like resistors, with Z = R + jX.
Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.
DC motors
Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc
Method
Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
Use V = E + Ia·Ra to link voltage, current and back-EMF.
Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.
2Practice problems
1.Three-phase powerMedium
A three-phase induction motor delivers 11 kW of mechanical output power at full load. At this load its efficiency is 93% and its power factor is 0.88 lagging. The supply has a line-to-line voltage of 480 V. Find the line current IL.
Pout = 11 kWη = 93%cos φ = 0.88VL = 480 V
IL = A
2.Three-phase powerHard
A balanced three-phase load takes 120 kW at a power factor of 0.65 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 120 kWpf1 = 0.65pf2 = 0.92VL = 690 Vf = 50 Hz
QC = kvar
3.TransformersMedium
A single-phase 500 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
S = 500 kVAV1 = 6600 VV2 = 230 V
IHV = A
4.TransformersHard
A single-phase 100 kVA transformer has a core loss of 800 W. At rated load and a power factor of 0.95 lagging its efficiency is 96.5%. Find the full-load copper loss Pcu,fl in watts.
S = 100 kVAPcore = 800 Wpf = 0.95η = 96.5%
Pcu,fl = W
5.AC power & power factorMedium
Two loads are connected in parallel to a 230 V single-phase supply: a 20 kW load at a power factor of 0.65 lagging and a 15 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A 120 V (rms), 50 Hz source has an internal impedance Zs = 25 + j10 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Vs = 120 V (rms)f = 50 HzZs = 25 + j10 Ω
Pmax = W
7.AC impedance & phasorsMedium
A series RLC circuit with L = 5 mH must resonate at 5000 Hz. Find the capacitance C needed.
f0 = 5000 HzL = 5 mH
C = µF
8.AC impedance & phasorsHard
A resistor R1 is connected in series with a parallel combination of R2 and a capacitor C, across a 100 V (rms), 500 Hz supply. Find the rms current I.
V = 100 V (rms)f = 500 HzR1 = 40 ΩR2 = 60 ΩC = 10 µF
I = A
9.DC motorsMedium
A DC motor (k = 0.12 V·s/rad, Ra = 1 Ω) runs from 24 V. At full load it draws 2 A. Neglecting the no-load current, find its speed regulation SR = (n₀ − nFL)/nFL in percent.
V = 24 Vk = 0.12 V·s/radRa = 1 ΩIFL = 2 A
SR = %
10.DC motorsHard
A DC motor with k = 1.2 V·s/rad and Ra = 1.5 Ω must drive a load of 7.2 N·m at 750 rpm. Find the armature voltage V it needs.
k = 1.2 V·s/radRa = 1.5 ΩT = 7.2 N·mn = 750 rpm
V = V
3Solutions
1.Three-phase power
Answer: IL = 16.17 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 11/0.93 = 11.83 kW
Line current
IL = Pin/(√3·VL·cos φ) = 11828/(√3·480·0.88) = 16.17 A
Answer
IL = 16.17 A
2.Three-phase power
Answer: QC = 89.18 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 120·tan(acos 0.65) = 120·1.169 = 140.3 kvar
Q2 = 120·tan(acos 0.92) = 120·0.426 = 51.12 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 89.18 kvar
Answer
QC = 89.18 kvar
3.Transformers
Answer: IHV = 75.76 A
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
IHV = S/V = 500000/6600 = 75.76 A
Answer
IHV = 75.76 A
4.Transformers
Answer: Pcu,fl = 2646 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.
Output and input power
Pout = 100·0.95 = 95 kW
Pin = 95000/0.965 = 98446 W
Total and copper losses
Ploss = 98446 − 95000 = 3446 W
Pcu,fl = 3446 − 800 = 2646 W
Answer
Pcu,fl = 2646 W
5.AC power & power factor
Answer: cos φ = 0.8315
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Reactive power of each load
A lagging load takes reactive power (Q > 0); a leading load supplies it (Q < 0).
Q1 = 20·tan(arccos 0.65) = 23.38 kvar
Q2 = 0 = 0 kvar
Totals
P = 20 + 15 = 35 kW
Q = 23.38 + 0 = 23.38 kvar
S = √(35² + 23.38²) = 42.09 kVA
Overall power factor
cos φ = P/S = 35/42.09 = 0.8315 lagging
Answer
cos φ = 0.8315
6.AC power & power factor
Answer: Pmax = 144 W
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Conjugate match
The load reactance cancels the source reactance, and the load resistance equals the source resistance.
ZL = Zs* = 25 − j10 Ω
Maximum power
I = Vs/(2Rs) = 120/50 = 2.4 A
Pmax = I²·RL = Vs²/(4Rs) = 120²/(4·25) = 144 W
Answer
Pmax = 144 W
7.AC impedance & phasors
Answer: C = 0.2026 µF
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Resonance condition
At resonance the inductive and capacitive reactances cancel: ωL = 1/(ωC).
ω₀ = 2π·5000 = 31416 rad/s
C = 1/(ω₀²·L) = 1/(31416²·0.005) = 0.2026 µF
Answer
C = 0.2026 µF
8.AC impedance & phasors
Answer: I = 1.704 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactance
XC = 1/(2π·500·10·10⁻⁶) = 31.83 Ω
Parallel combination
Multiply top and bottom by the complex conjugate to split Zp into real and imaginary parts.
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.
No-load and full-load speed
n₀ = 60·24/(2π·0.12) = 1910 rpm
nFL = 60·(24 − 2·1)/(2π·0.12) = 1751 rpm
Speed regulation
SR = (1910 − 1751)/1751·100 = 9.091 %
Answer
SR = 9.091 %
10.DC motors
Answer: V = 103.2 V
DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.