A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 19.5 A and 3042 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 13 A and 2184 W. Find the power factor cos φ of the load.
An inductive load takes 4.5 A and 324 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
An inductive load takes 12 A and 1224 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 5 kW at a power factor of 0.75 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
A single-phase load takes 45 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. cos φ = 0.65
- 2. cos φ = 0.7
- 3. R = 16 Ω
- 4. X = 5.268 Ω
- 5. Inew = 23.63 A
- 6. C = 1677 µF
Full step-by-step solutions: practise this topic on examproblems.com.