A load takes 39 kW of real power and 31.5 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A load takes 18.5 kW of real power and 9.5 kvar of reactive power (lagging). Find the apparent power S.
A load with impedance Z = 5 + j12 Ω is connected to a 230 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A load with impedance Z = 4 + j3 Ω is connected to a 240 V (rms) single-phase supply. Find the real power P it absorbs.
A single-phase load takes 25 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
A single-phase load takes 5 kW at a power factor of 0.75 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. S = 50.13 kVA
- 2. S = 20.8 kVA
- 3. Q = 3756 var
- 4. P = 9216 W
- 5. QC = 13.83 kvar
- 6. Inew = 24.15 A
Full step-by-step solutions: practise this topic on examproblems.com.