A load takes 18.5 kW of real power and 6.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A load takes 45.5 kW of real power and 29.5 kvar of reactive power (lagging). Find the apparent power S.
A load with impedance Z = 4 + j3 Ω is connected to a 120 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase motor takes 11 kW at a power factor of 0.6 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase load takes 14 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A 230 V (rms), 50 Hz source has an internal impedance Zs = 10 + j40 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. cos φ = 0.9435
- 2. S = 54.23 kVA
- 3. Q = 1728 var
- 4. Q = 14.67 kvar
- 5. cos φ = 0.6724
- 6. Pmax = 1323 W
Full step-by-step solutions: practise this topic on examproblems.com.