A single-phase load draws 2 A (rms) from a 240 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 20 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
A single-phase motor takes 30 kW at a power factor of 0.9 lagging from a 400 V supply. Find the reactive power Q it draws.
Two loads are connected in parallel to a 240 V single-phase supply: a 3 kW load at a power factor of 0.8 lagging and a 20 kW load at a power factor of 0.8 lagging. Find the total current I drawn from the supply.
A single-phase load takes 8 kW at a power factor of 0.75 lagging from a 400 V, 60 Hz supply. A 22 µF capacitor is connected in parallel with the load. Find the new line current I.
A 100 kVA single-phase transformer supplies a load of 31 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. P = 312 W
- 2. P = 7200 W
- 3. Q = 14.53 kvar
- 4. I = 119.8 A
- 5. I = 24.6 A
- 6. ΔP = 67.14 kW