A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 16 A and 2944 W. Find the reactive power Q taken by the load.
AC power & power factor worksheet with answers
A single-phase load draws 12 A (rms) from a 400 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
A single-phase motor takes 23 kW at a power factor of 0.7 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase motor takes 20 kW at a power factor of 0.6 lagging from a 240 V supply. Find the line current I.
A single-phase load takes 40 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
A single-phase load takes 26 kW at a power factor of 0.75 lagging from a 240 V, 50 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. Q = 2208 var
- 2. P = 3840 W
- 3. Q = 23.46 kvar
- 4. I = 138.9 A
- 5. Inew = 170.1 A
- 6. I = 129.3 A
Full step-by-step solutions: practise this topic on examproblems.com.